Honeywell W8735ER Installation Instructions Manual Download Page 6

W8735ER WIRELESS OUTDOOR RESET MODULE

66-1202—01

6

Fig. 5. Outdoor temperature setback curve with boost.

As Outdoor Temp reaches the Warm Weather Shutdown set-

point (if enabled), the boiler is kept from cycling and will only 

service DHW demands if the Aquastat Zr terminal is 

configured for Domestic Hot Water request. See Table 4 on 

page 6.

Table 3. Warm Weather Shutdown Settings and Defaults.

Parameter name

Minimum 

value

Maximum 

Value

Default

Warm Weather 

Shutdown

40

F (or Off) 70

F

Off

HIGH LIMIT

 

 

BOILER

TEMPERATURE

 

M29557

MINIMUM BOILER

TEMPERATURE

MINIMUM

OUTDOOR

TEMPERATURE

MAXIMUM

OUTDOOR

TEMPERATURE

OUTDOOR

TEMPERATURE

BOOST

STEP

BOOST

Table 4. Programming Parameters.

Aquastat

HL_

High Limit.

Hdf

High Limit Differential.

LL**_

Low Limit.

Ldf

Low Limit Differential.

ELL***

ZR input configured as External Low Limit (ON/OFF)

duu

ZR input configured as external Domestic Hot Water 

(DHW) request (ON/OFF)

ASC

Anti Short Cycle Timeout (seconds); “OFF” is 

disabled.

otL

Outdoor Temperature Low (minimum) parameter for 

the outdoor reset curve (

F or 

C)*

otH

Outdoor Temperature High (maximum) parameter for 

outdoor reset curve (

F or 

C)*

btL

Boiler Temperature Low (minimum) parameter for 

outdoor reset curve*

bP

Boost Period (minutes). “OFF” is displayed if Boost is 

inactive*

bS

Boost step (

F or 

C) shown only if Boost is active 

(bP=ON)*

UUS

Warm Weather Shutdown Temperature (

F or 

C)*

tPL**

Thermal Purging Limit Temperature (

F or 

C),

“OFF” if disabled.

tPt**

Thermal Purging Time Delay (minutes), shown only 

if tPL is enabled

PC

Pump Cycling (ON/OFF)

F-C

Temperature units (

F or 

C) 

*Settings available for adjustment on the 3-digit Aquastat 

display only when the “Outdoor Reset Module” is installed.

**Not displayed when connected to an L7248 Aquastat 

Control.

***Only displayed when connected to an L7248L Aquastat 

Control.

IBC

HL_

High Limit.

Hdf

High Limit Differential.

Or_

Pump Overrun Time

otL

Outdoor Temperature Low (minimum) parameter for 

the outdoor reset curve (

F or 

C)

otH

Outdoor Temperature High (maximum) parameter for 

outdoor reset curve (

F or 

C)

btL

Boiler Temperature Low (minimum) parameter for 

outdoor reset curve

tPL

Thermal purging minimal temperature (Parameter is 

available only if outdoor temperature is invalid)

tPt

Maximal Thermal Purge time (Parameter is available 

only if outdoor temperature is invalid)

rSt

Reset Lockout

F-C

Temperature units (

F or 

C) 

Summary of Contents for W8735ER

Page 1: ...munication protocol Fast wireless connection to outdoor sensor Enables Boiler Outdoor Temperature Reset Enables Warm Weather Shutdown Enables Boost Override Simple low voltage 3 wire installation to combustion control 3 EnviraCOM EnviraCOM RedLink Enabled INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardo...

Page 2: ...ower on 5 Bind the C7089R Wireless Outdoor Sensor to the Wire less Outdoor Reset Module See Sensor Binding on page 3 Fig 1 W8735ER Wireless Outdoor Reset Module wiring diagram C7089R INSTALLATION Mount Outdoor Sensor Before installing the C7089 sensor make sure 2 AA lithium preferred batteries are inserted See Fig 2 Fig 2 Battery Installation 1 Mount the sensor bracket on a vertical wall at least ...

Page 3: ...e positioned at least 3 feet apart during the binding process 5 Once the flashing rate goes back to 1 blink second press the CONNECT button on the W8735ER to end the binding process 6 Once the C7089R sensor and the W8735ER bind the CONNECTED LED on the W8735ER will be ON solid green 7 Place sensor cover back on the sensor and return the sensor to the bracket See Fig 3 NOTE Pressing the CONNECT but...

Page 4: ...rature to a point below its local high limit setting and above the boiler s condensation temperature by using the EnviraCOM communication bus to directly adjust the Aquastat set point Should a call for Domestic Hot Water be detected the boiler temperature is commanded to return to the High Limit setting ensuring a hot water supply is available When the Domestic Hot Water demand is met the Outdoor ...

Page 5: ...oint does not reset the Boost Continuous Boost calls may be an indication of a poorly set Outdoor Reset Curve for the environment or faulty equipment For the Aquastat a Boost warning will be indicated on the 3 digit Aquastat display if Boost is required on 60 consecutive cycles See Table 5 For the Aquastat the Boost Period can be set from OFF to a range of 5 minutes to 30 minutes adjustable in 1 m...

Page 6: ...ture High maximum parameter for outdoor reset curve F or C btL Boiler Temperature Low minimum parameter for outdoor reset curve bP Boost Period minutes OFF is displayed if Boost is inactive bS Boost step F or C shown only if Boost is active bP ON UUS Warm Weather Shutdown Temperature F or C tPL Thermal Purging Limit Temperature F or C OFF if disabled tPt Thermal Purging Time Delay minutes shown on...

Page 7: ...power if the alarm condition is no longer present Table 5 Aquastat Outdoor Reset Related Error Codes Error Code Cause Action EnviraCOM Alarm Err 9a Warning Outdoor Reset System failure communication to Outdoor Reset Module lost Outdoor Reset Module failure multiple outdoor temperature sensors detected on the bus or outdoor temperature sensor failure Check EnviraCOM wiring 1 2 3 check sensor wiring...

Page 8: ... to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Wireless adapter To comply with FCC and Industry Canada RF...