Honeywell W8735ER Installation Instructions Manual Download Page 5

W8735ER WIRELESS OUTDOOR RESET MODULE

5

66-1202—01

(design temperature) is the point at which the boiler should be 

set to its high limit setting. Setting the boiler temperature too 

low during the coldest periods will result in the inability to keep 

up with heat demand. This is the critical setting in avoiding 

call-backs.

High Outdoor Temperature:

 This is the outdoor temperature 

for which the Low Boiler Temperature is set. This is the 

parameter that most impacts energy savings. Setting the High 

Outdoor Temperature too high results in less energy savings 

as the boiler may run at a higher temperature during warmer 

weather than necessary to maintain comfort in the space. 

Setting this parameter too low will result in too narrow a range 

for the control to be adjusting boiler temperature. In most 

cases the default of 40 °F (4.4 °C) is fine.

NOTE: In many cases these parameters will not need to 

be adjusted as their default values are designed 

to accommodate mid-Atlantic and lower New 

England areas.

CAUTION

Possible Equipment Damage

When enabling the Outdoor Reset function, be sure to 

refer to the boiler OEM’s instructions for the lowest 

return water setting to avoid condensation in the heat 

exchanger, which can result in equipment damage. 

1

Minimum values, Maximum values and Default High Limit 

settings shown are for the L7224U and the S9361 IBC. Val-

ues may change for other Aquastats and IBCs. Check the 

specific Aquastat and/or IBC Installation Instruction manual 

for more information on default settings.

Boost

If heat demand is not met within a certain time period while 

the boiler is in setback mode (following the Outdoor Reset 

curve), a Boost Period is invoked where the boiler set point is 

increased by a value called the Boost Step. Each time the 

Boost Period elapses and heat demand is not satisfied, the 

boiler set-point is again increased by the Boost

 

Step, up to the 

maximum setting provided by the High Limit setting (see Table 

2 and Fig. 5). Boost is reset when the heat demand is satisfied 

(local or remote call for heating has ended). Simply reaching 

the boiler set-point does not reset the Boost. Continuous 

Boost calls may be an indication of a poorly set Outdoor Reset 

Curve for the environment or faulty equipment. For the 

Aquastat, a Boost warning will be indicated on the 3-digit 

Aquastat display if Boost is required on 60 consecutive cycles. 

See Table 5.

For the Aquastat, the Boost Period can be set from OFF to a 

range of 5 minutes to 30 minutes, adjustable in 1 minute 

increments. The default setting is 10 minutes. The Boost Step 

can be set from Off to a range of 5

F (-15

C) to 20

F (-7

C).

For the IBC, the Boost Period is fixed at 30 minutes and the 

Boost Step is fixed at 5 °F. See Table 2.

1

 For the IBC, both the Boost Period and Boost Step are fixed 

parameters and can not be adjusted.

Warm Weather Shutdown - Aquastat

The Warm Weather Shutdown feature causes a “Warm Start” 

boiler to shut down when the outdoor temperature exceeds a 

specified value. Warm Start boilers maintain a minimum 

temperature by setting the Low Limit on the Aquastat. If 

enabled this features cancels the Low Limit setting when the 

outdoor temperature exceeds a specified value.

CAUTION

Zone Panel Settings

In applications with zoning panels having a priority 

zone for domestic hot water: Disable the warm 

weather shutdown feature on the Aquastat.

The Warm Weather Shutdown feature can be set from OFF to 

a range of 40 °F (4.4°C) to 70 °F (21 °C), adjustable in 10 

degree increments. The default setting is OFF. See Table 3.

Table 1. Outdoor Reset Curve Settings and Defaults.

1

Aquastat

Parameter

Minimum 

value

Maximum 

value

Default

High Limit

130 °F

(54 °C)

240 °F

(116 °C)

180 °F

(82 °C)

Minimum Outdoor 

Temperature

-40 °F

(-40 °C)

40 °F

(4.4 °C)

0 °F

(-18 °C)

Minimum Boiler 

temperature 

80 °F

(27 °C)

180 °F

(82 °C)

130 °F

(54 °C)

Maximum Outdoor 

Temperature

30 °F

(-1 °C)

70 °F

(21 °C)

40 °F

(4.4 °C)

IBC

Parameter

Minimum 

value

Maximum 

value

Default

High Limit

130 °F

(54 °C)

220 °F

(104 °C)

180 °F

(82 °C)

Minimum Outdoor 

Temperature

-40 °F

(-40 °C)

40 °F

(4.4 °C)

0 °F

(-18 °C)

Minimum Boiler 

temperature 

130 °F

(54 °C)

150 °F

(56 °C)

140 °F

(60 °C)

Maximum Outdoor 

Temperature

40°F

(12.7 °C)

70 °F

(21 °C)

40°F

(12.7°C)

Table 2. Boost Settings and Defaults.

Aquastat

Parameter name

Minimum 

value

Maximum 

Value

Default

Boost Period

5 minutes 

(or Off)

30 minutes

10 minutes

Boost Step

5

F (or Off)

20

F

10

F

IBC

Parameter name

Value

1

Boost Period

30 minutes

Boost Step

5

F (or Off)

Summary of Contents for W8735ER

Page 1: ...munication protocol Fast wireless connection to outdoor sensor Enables Boiler Outdoor Temperature Reset Enables Warm Weather Shutdown Enables Boost Override Simple low voltage 3 wire installation to combustion control 3 EnviraCOM EnviraCOM RedLink Enabled INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could damage the product or cause a hazardo...

Page 2: ...ower on 5 Bind the C7089R Wireless Outdoor Sensor to the Wire less Outdoor Reset Module See Sensor Binding on page 3 Fig 1 W8735ER Wireless Outdoor Reset Module wiring diagram C7089R INSTALLATION Mount Outdoor Sensor Before installing the C7089 sensor make sure 2 AA lithium preferred batteries are inserted See Fig 2 Fig 2 Battery Installation 1 Mount the sensor bracket on a vertical wall at least ...

Page 3: ...e positioned at least 3 feet apart during the binding process 5 Once the flashing rate goes back to 1 blink second press the CONNECT button on the W8735ER to end the binding process 6 Once the C7089R sensor and the W8735ER bind the CONNECTED LED on the W8735ER will be ON solid green 7 Place sensor cover back on the sensor and return the sensor to the bracket See Fig 3 NOTE Pressing the CONNECT but...

Page 4: ...rature to a point below its local high limit setting and above the boiler s condensation temperature by using the EnviraCOM communication bus to directly adjust the Aquastat set point Should a call for Domestic Hot Water be detected the boiler temperature is commanded to return to the High Limit setting ensuring a hot water supply is available When the Domestic Hot Water demand is met the Outdoor ...

Page 5: ...oint does not reset the Boost Continuous Boost calls may be an indication of a poorly set Outdoor Reset Curve for the environment or faulty equipment For the Aquastat a Boost warning will be indicated on the 3 digit Aquastat display if Boost is required on 60 consecutive cycles See Table 5 For the Aquastat the Boost Period can be set from OFF to a range of 5 minutes to 30 minutes adjustable in 1 m...

Page 6: ...ture High maximum parameter for outdoor reset curve F or C btL Boiler Temperature Low minimum parameter for outdoor reset curve bP Boost Period minutes OFF is displayed if Boost is inactive bS Boost step F or C shown only if Boost is active bP ON UUS Warm Weather Shutdown Temperature F or C tPL Thermal Purging Limit Temperature F or C OFF if disabled tPt Thermal Purging Time Delay minutes shown on...

Page 7: ...power if the alarm condition is no longer present Table 5 Aquastat Outdoor Reset Related Error Codes Error Code Cause Action EnviraCOM Alarm Err 9a Warning Outdoor Reset System failure communication to Outdoor Reset Module lost Outdoor Reset Module failure multiple outdoor temperature sensors detected on the bus or outdoor temperature sensor failure Check EnviraCOM wiring 1 2 3 check sensor wiring...

Page 8: ... to try to correct the interference by one of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult the dealer or an experienced radio TV technician for help Wireless adapter To comply with FCC and Industry Canada RF...

Reviews: