W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
9
63-2544—3
Fig. 8. W6215A used in single-stage cooling system with single enthalpy changeover and Honeywell Series 62 Actuator.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA
LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED
BY A 24 VAC INPUT.
THE COMMON FOR THE W6215A IS DIFFERENT THAN THE
COMMON (WIPER) FOR THE SERIES 62 ACTUATORS. BE SURE
TO CONNECT EACH TO A DIFFERENT CIRCUIT.
M11803A
P1
P
T1
1
3
4
2
5
2K
S
1
2
3
3
4
TR
TR1
SO
SR
+
+
W6215A
+
1K
4
5
T
6
7
8
9
9
9
5
1S
1S1
C7150B MIXED
AIR OR
C7046A
DISCHARGE
AIR SENSOR
MINIMUM POSITION
ADJUSTMENT
MAXIMUM
POSITION
ADJUSTMENT
Q1
Q
AQ1
AQ
SD1
AC1
PG1
SD
AC
PG
FREE
COOL
UNIT
CONTROL
EXHAUST
FAN
INDOOR
FAN
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE
REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING
THERMOSTATS.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER.
FOR TWO-STAGE THERMOSTATS ONLY.
+
2-10 VDC
INDOOR AIR
SENSOR
SHUT DOWN
PURGE
AIR CHANGE
C7400
OUTDOOR
AIR
ENTHALPY
SENSOR
UNOCCUPIED
ST6008
TIMER
L1
(HOT)
L2
FDR
FDR
FAN
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENT
TERMINAL STRIP
T7300 OR T874
THERMOSTAT
1
C
G
W1
Y1
R
W2
RC
G
X
W1
Y1
Y2
W2
OCCUPIED
7
8
2
HONEYWELL
SERIES 62
ACTUATOR
(ML6275,
ML6285,
M6275,
M6285)
CLOSE
OPEN
OPEN
WIPER
CLOSED
500 OHM
24 VAC HOT
24 VAC COM
FAN
DELAY
RELAY
W
R
T6031 AMBIENT
LOCKOUT
CONTROL
50 F SETPOINT
6
620 OHM
RESISTOR
RH