W6215, W7215, W7460 ECONOMIZER LOGIC MODULES
63-2544—3
12
Fig. 11. W7215A used in two-stage cooling system with Honeywell Series 72 Actuator.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED.
ACTUATOR SPRING-RETURNS CLOSED WHEN FAN IS NOT RUNNING.
ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA
LOAD OF THE ECONOMIZER AND ACTUATOR.
1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED
BY A 24 VAC INPUT.
M11801A
P1
P
T1
1
3
4
2
5
2K
S
1
2
3
3
4
TR
TR1
SO
SR
+
+
W7215A
+
6
1K
4
5
T
6
7
8
5
1S
1S1
C7150B MIXED
AIR OR
C7046A
DISCHARGE
AIR SENSOR
620 OHM
RESISTOR
MINIMUM POSITION
ADJUSTMENT
MAXIMUM
POSITION
ADJUSTMENT
Q1
Q
AQ1
AQ
SD1
AC1
PG1
SD
AC
PG
FREE
COOL
UNIT
CONTROL
EXHAUST
FAN
INDOOR
FAN
FOR THE ML7295A,C, USE THE 4-20 mA MODEL ACTUATOR. THESE
MODELS HAVE 500 OHM INPUT IMPEDENCE THAT ALLOWS THE
ACTUATOR TO ACCEPT A 2-10 VDC SIGNAL.
FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED
ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND + FOR
DIFFERENTIAL ENTHALPY.
FOR T7300 ONLY.
FOR T7300, USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER.
+
–
2-10 VDC
INDOOR
AIR SENSOR
SHUT DOWN
PURGE
AIR CHANGE
C7400
OUTDOOR
AIR
ENTHALPY
SENSOR
UNOCCUPIED
ST6008
TIMER
L1
(HOT)
L2
FDR
FDR
FAN
HEAT 1
HEAT 2
COOL 1
HVAC EQUIPMENT
TERMINAL STRIP
T7300 OR T874
THERMOSTAT
1
C
G
W1
Y1
Y2
R
W2
RC
RH
G
X
W1
Y1
Y2
W2
OCCUPIED
7
8
2
COOL 2
24 VAC HOT
24 VAC COM
FAN
DELAY
RELAY
W
R
T6031 AMBIENT
LOCKOUT
CONTROL
50
°
F SETPOINT
2-10V
OUT
+
–
HONEYWELL
SERIES 72
ACTUATOR
(ML7275,
ML7285,
ML7295A,C
M7275,
M7285)
+
–