W6215, W7215, W7460 ECONOMIZER LOGIC MODULES

63-2544—3

6

Table 3. W6215, W7215, W7460 Economizer Purge, 

Shutdown, and Air Change I/O Logic.

a

Purge present only on W6215A, W7215A, and W7460A.

Shutdown

One contact closure shuts down all systems. When terminals 

SD and SD1 connect through relay contacts or a jumper:

1.

Outdoor damper drives fully closed.

2.

Exhaust fan turns off.

3.

Indoor fan turns off.

Air Change

When terminals AC and AC1 connect through relay contacts 

or a jumper:

1.

Outdoor damper drives fully open.

2.

Exhaust fan turns on.

3.

Indoor fan turns on.

NOTE: With Purge, Shutdown, and Air Change de-

energized, Exhaust will be de-energized unless the 

signal exceeds the exhaust fan setpoint; other logic 

module functions remain unaltered.

SETTINGS AND ADJUSTMENTS

Potentiometers with screwdriver adjustment slots, located on 

the device face, provide adjustments for several parameters 

(see Fig. 5 for locations on device):
— ISI setpoint.

— OSI setpoint (W7215B and W7460B only).

— Minimum damper position.

— Maximum damper position.
— Enthalpy changeover.

— Exhaust setpoint (W6215A, W7215A and W7460A only).

Indoor Sensor Input Setpoint

The logic module modulates the outdoor damper to provide 
ventilation based on the 2-10 Vdc ISI. With no cooling signal, 

the ISI overrides the outdoor air damper when ventilation 

requires outdoor air.

Outdoor Sensor Input Setpoint
(W7215B and W7460B 

only

)

The OSI logic operates from a 2-10 Vdc sensor signal. The 

operation of these logic modules is slightly different from the 

other models, see Table 4.

Table 4. W7215B and W7460B OSI Operation.

a

Modulation based on signal from mixed air sensor.

b

With ISI signal greater than mixed air sensor signal:

Modulation, based on ISI signal, between minimum and 

maximum positions.

c

With ISI signal less than mixed air sensor signal:

Modulation, based on mixed air sensor signal, between:

M7215B: Minimum and full open positions

M7460B: Minimum and maximum positions.

d

Modulation based on mixed air sensor signal; 

Alarm

 terminals 

connect to energize warning light, audio alarm, or air cleaner.

Table 5. W6215, W7215, W7460 Economizer I/O Logic.

a

For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.

b

If both stages of cooling are off, the system is off and the damper is at:

• Minimum position if ISI is below setpoint.

• Modulating if ISI is above setpoint.

c

W6215, W7460: Modulation, based on the mixed air sensor signal, between minimum and maximum positions.

W7215: Modulation, based on the mixed air sensor signal, between minimum and full-open positions.

d

Modulation, based on the ISI, between minimum and maximum positions.

e

Modulation, based on the greater of ISI and mixed air sensor signals, between minimum and either maximum position (ISI) or 

fully open (mixed air signal).

NOTE: Each sensor has it’s own setpoint for threshold and LED indication.

INPUTS

OUTPUTS

Purge

a

Shut-

down

Air 

Change

Damper

Unit 

Control

Indoor 

Fan Exhaust

On

-

-

Fully Closed Off

Off

On

Off

On

-

Off

Off

On

Fully Open

On

On

OSI

ISI

Actuator

OSI LED

Alarm

Below set Below set Modulates

a

Off

Off

Above set Modulates

b

Modulates

c

Above set Below set Fully closed On

Off

Above set Modulates

d

On

On

INPUTS

OUTPUTS

ISI

Enthalpy

a

Y1

b

Y2

b

Damper

Compressor

Outdoor

Return

1

2

Below set 

(ISI LED Off)

High (Free Cooling LED Off)

Low

On

On

Minimum position On

On

On

Off

On

Off

Low (Free Cooling LED On)

High

On

On

Modulating

c

On

Off

On

Off

Off

Off

Above set 
(ISI LED On)

High (Free Cooling LED Off)

Low

On

On

Modulating

d

On

On

On

Off

On

Off

Low (Free Cooling LED On)

High

On

On

Modulating

e

On

Off

On

Off

Off

Off

Summary of Contents for W6215 Series

Page 1: ...emotely in a mechanical room Mounting screws included The W6215 and W7215 are used with Honeywell Series 62 and Series 72 actuators respectively The W7460 is used with Honeywell M7415 Damper Actuators Combines minimum and maximum damper position potentiometers and compressor staging relay functions with solid state enthalpy or dry bulb changeover control this control can be tempered by ISI and fan...

Page 2: ...F 32 C to 52 C Humidity Noncondensing 5 to 95 percent rh Inputs Enthalpy C7400 2 wire 18 20 22 AWG connection Dry Bulb Temperature C7650 2 wire 18 20 22 AWG connection Discharge Air C7046 2 wire 18 20 22 AWG connection Mixed Air C7150 2 wire 18 20 22 AWG connection Indoor Sensor 2 10 Vdc control signal Outdoor Sensor W7215B and W7460B only 2 10 Vdc control signal Outputs W7215 2 10 Vdc W6215 Serie...

Page 3: ...erential sensing both sensors must be of the same type enthalpy or dry bulb OUTDOOR AIR SENSING 1 Mount sensor in any orientation that exposes it to freely circulating air and protects it from rain snow and direct sunlight 2 Connect it to the SO and terminals of the device RETURN AIR SENSING 1 Ensure differential enthalpy control has a second sensor in the return air duct 2 Connect this sensor to ...

Page 4: ...1 are ac dc common connections Optional Applications Remote Minimum Position Control Remote control of outdoor air dampers is desirable when requiring temporary additional ventilation One potentiometer controls the damper minimum position another potentiometer controls the damper maximum position The addition of S963B1128 Remote Potentiometers allows occupants to open or close the dampers beyond m...

Page 5: ...inals PG and PG1 connect through relay contacts or a jumper 1 Outdoor damper drives fully closed 2 Exhaust fan turns on Fig 4 S963B1128 Remote Potentiometer used with W6215 W7215 W7460 for remote damper control Logic Module Actuator Enthalpy Changeover Figure Comments W6215A Honeywell Series 62 Single 8 Single stage cooling system Single or Differential 9 Two stage cooling system W7215A Honeywell ...

Page 6: ...tion based on ISI signal between minimum and maximum positions c With ISI signal less than mixed air sensor signal Modulation based on mixed air sensor signal between M7215B Minimum and full open positions M7460B Minimum and maximum positions d Modulation based on mixed air sensor signal Alarm terminals connect to energize warning light audio alarm or air cleaner Table 5 W6215 W7215 W7460 Economiz...

Page 7: ...mixed air temperature reaches the calculated value NOTE Ensure that the sensed air is well mixed Equation 1 Formula to aid in minimum position adjustment Where TO Outdoor air temperature OA Percent of outdoor air TR Return air temperature RA Percent of return air TM Resulting mixed air temperature IMPORTANT This procedure requires use of a quality thermometer capable of reading to 0 5 F 0 25 C NOT...

Page 8: ...e exhaust setpoint at an actual damper position percentage open from fully closed Fixed Exhaust Setpoint W7215B and W7460B The W7215B and W7460B Logic Modules have a fixed exhaust setpoint The logic module uses an exhaust setpoint of 60 percent When the damper reaches 60 percent open from fully closed the logic module calls for exhaust Fig 6 W7215A used with Honeywell Series 90 Actuator Fig 7 W621...

Page 9: ...C7046A DISCHARGE AIR SENSOR MINIMUM POSITION ADJUSTMENT MAXIMUM POSITION ADJUSTMENT Q1 Q AQ1 AQ SD1 AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD NOT BE REMOVED DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING SYSTEMS OR SINGLE STAGE COOLING THERMOSTATS FOR T7300 ONLY FOR T7300 USE CONTACTS A1 AND A2 INSTEAD...

Page 10: ...PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN THE COMMON FOR THE W6215A IS DIFFERENT THAN THE COMMON WIPER FOR THE SERIES 62 ACTUATORS BE SURE TO CONNECT EACH TO A DIFFERENT CIRCUIT FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY FOR T7300 ONLY FOR T7300 USE CONTACTS A1 AND A2 INSTEAD OF THE T...

Page 11: ... MIXED AIR OR C7046A DISCHARGE AIR SENSOR MINIMUM POSITION ADJUSTMENT MAXIMUM POSITION ADJUSTMENT Q1 Q AQ1 AQ SD1 AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD NOT BE REMOVED DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING SYSTEMS OR SINGLE STAGE COOLING THERMOSTATS FOR T7300 ONLY FOR T7300 USE CONTACTS A1 ...

Page 12: ...AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN FOR THE ML7295A C USE THE 4 20 mA MODEL ACTUATOR THESE MODELS HAVE 500 OHM INPUT IMPEDENCE THAT ALLOWS THE ACTUATOR TO ACCEPT A 2 10 VDC SIGNAL FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY FOR T7300 ONLY FOR T7300 USE CONTACTS A1 AND A2 INST...

Page 13: ...N ADJUSTMENT MAXIMUM POSITION ADJUSTMENT Q1 Q AQ1 AQ SD1 AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN FOR THE ML7295A C USE THE 4 20 MA MODEL ACTUATOR THESE MODELS HAVE 500 OHM INPUT IMPEDENCE THAT ALLOWS THE ACTUATOR TO ACCEPT A 2 10 VDC SIGNAL FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTH...

Page 14: ... ACCEPT A 2 10 VDC SIGNAL FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD NOT BE REMOVED DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING SYSTEMS OR SINGLE STAGE COOLING THERMOSTATS FOR T7300 ONLY FOR T7300 USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER FOR TWO STAGE THERMOSTATS ONLY C7400 OUTDOOR AIR ENTHALPY SENSOR UNOCCUPIED ST6008 TIMER L1 HOT L2 FDR FDR FAN HEAT 1 HEAT ...

Page 15: ...ENCE THAT ALLOWS THE ACTUATOR TO ACCEPT A 2 10 VDC SIGNAL FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY FOR T7300 ONLY FOR T7300 USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER C7400 OUTDOOR AIR ENTHALPY SENSOR UNOCCUPIED ST6008 TIMER L1 HOT L2 FDR FDR FAN HEAT 1 HEAT 2 COOL 1 HVAC EQUIPMENT TERMINAL STRIP T...

Page 16: ...0 mA MODEL ACTUATOR THESE MODELS HAVE 500 OHM INPUT IMPEDENCE THAT ALLOWS THE ACTUATOR TO ACCEPT A 2 10 VDC SIGNAL FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY T775 REQUIRES A MINIMUM OF THREE RELAY OUTPUTS TWO FOR COOLING AND ONE FOR FAN CONTROL A MAXIMUM OF ONE STAGE HEATING IS POSSIBLE WHEN THE SYSTE...

Page 17: ...IMUM POSITION ADJUSTMENT Q1 Q AQ1 AQ SD1 AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD NOT BE REMOVED DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING SYSTEMS OR SINGLE STAGE COOLING THERMOSTATS FOR T7300 ONLY FOR T7300 USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER FOR TWO STAGE THERMOSTATS ONLY 2 10 VDC INDOO...

Page 18: ...MUM POSITION ADJUSTMENT MAXIMUM POSITION ADJUSTMENT Q1 Q AQ1 AQ SD1 AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN FOR T7300 USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY FOR T7300 ONLY 2 10 VDC INDOOR AIR SENSOR SHUT DOWN PURGE AIR CHANGE C7400...

Page 19: ...OULD NOT BE REMOVED DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE WITH SINGLE STAGE COOLING SYSTEMS OR SINGLE STAGE COOLING THERMOSTATS FOR T7300 ONLY FOR T7300 USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER FOR TWO STAGE THERMOSTATS ONLY C7400 OUTDOOR AIR ENTHALPY SENSOR UNOCCUPIED ST6008 TIMER L1 HOT L2 FDR FDR FAN HEAT 1 HEAT 2 COOL 1 HVAC EQUIPMENT TERMINAL STRIP T7300 OR T874 THERMOSTAT 1 C G W1...

Page 20: ...ACTS A1 AND A2 INSTEAD OF THE TIMER FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY FOR T7300 ONLY C7400 OUTDOOR AIR ENTHALPY SENSOR UNOCCUPIED ST6008 TIMER L1 HOT L2 FDR FDR FAN HEAT 1 HEAT 2 COOL 1 HVAC EQUIPMENT TERMINAL STRIP T7300 OR T874 THERMOSTAT 1 C G W1 Y1 Y2 R W2 RC RH G X W1 Y1 Y2 W2 OCCUPIED 6...

Page 21: ... 5 2K W6215 W7215 W7460 ECONOMIZER 1K 1S 1S1 HONEYWELL ACTUATOR 1 3 2 1 2 3 W R AT72A 40 VA TRANSFORMER L2 L1 HOT W7100 COOL 6 COOL 5 COOL 4 COOL 3 COOL 2 COOL 1 POWER SUPPLY POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED 510 OHM 1 4 WATT 5 PERCENT RESISTOR CONTAINED IN 4074EFV BAG ASSEMBLY ELIMINATES ECONOMIZER DELAYS ACTUATOR MODEL DEPENDENT ON LOGIC MODULE MODEL M1189...

Page 22: ...POSITION ADJUSTMENT Q1 Q AQ1 AQ SD1 AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY FOR T7300 ONLY CONNECT ONLY THE MASTER ACTUATOR TO THE W6215 FEEDBACK OUTPUT THE COMMON FOR THE W6215A IS DIFFERENT THAN THE COMMON WIPER FOR THE SERIES 62 ACTU...

Page 23: ...0 OHM RESISTOR 24 VAC HOT 24 VAC COM MINIMUM POSITION ADJUSTMENT MAXIMUM POSITION ADJUSTMENT Q1 Q AQ1 AQ SD1 AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN FOR T7300 USE CONTACTS A1 AND A2 INSTEAD OF THE TIMER FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY FOR T7300 ONLY 2 10 VDC INDOOR AI...

Page 24: ...6A DISCHARGE AIR SENSOR 620 OHM RESISTOR 24 VAC HOT 24 VAC COM MINIMUM POSITION ADJUSTMENT MAXIMUM POSITION ADJUSTMENT Q1 Q AQ1 AQ SD1 AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN FOR T7300 ONLY FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY 2 10 VDC INDOOR AIR SENSOR SHUT DOWN PURGE AIR...

Page 25: ...SOR 620 OHM RESISTOR 24 VAC HOT 24 VAC COM MINIMUM POSITION ADJUSTMENT MAXIMUM POSITION ADJUSTMENT Q1 Q AQ1 AQ SD1 AC1 PG1 SD AC PG FREE COOL UNIT CONTROL EXHAUST FAN INDOOR FAN ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE LOAD OF ALL ACTUATORS FACTORY INSTALLED 620 OHM 1 WATT 5 RESISTOR SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO SR AND FOR DIFFERENTIAL ENTHALPY FOR T7300 ON...

Page 26: ...r controls Use a small screwdriver when adjusting enthalpy changeover and minimum damper position controls 1 3 4 2 5 2K W6215 W7215 W7460 LOGIC MODULE 1K 1S 1S1 HONEYWELL ACTUATOR 1 2 1 2 W R L2 L1 HOT COOL 3 COOL 2 COOL 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ACTUATOR MODEL DEPENDENT ON LOGIC MODULE MODEL M11991A 2 1 COOL 3 HEAT 3 COOL 2 1 HEAT MOD HEAT WH BH R...

Page 27: ...AQ1 are open LED for both ISI and Exhaust should be off Actuator drives fully closed c Connect 9V battery positive to AQ and negative to AQ1 LED for both ISI and Exhaust turn on Actuator drives 90 to 95 percent open d Turn Exhaust potentiometer CW until Exhaust LED turns off Exhaust LED turns off with potentiometer at approximately 90 percent Actuator remains in position e Turn ISI potentiometer C...

Page 28: ...contacts open Exhaust Fan contacts close Actuator drives fully closed i Jumper Shutdown terminals 8 MIXED AIR INPUT a Execute step one Checkout Preparation b Set enthalpy potentiometer to A Free cool LED turns on c Replace 6 8K ohm resistor across T and T1 with 5 6K ohm resistor Actuator drives to between 20 and 80 percent open d Remove 5 6K ohm resistor and jumper T to T1 Actuator drives fully op...

Reviews: