background image

TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

3

69-1706

Fig. 5. Typical hookup of conventional single-stage 

heat and cool system with single transformer 

(1H/1C conventional).

Fig. 6. Typical hookup of conventional single-stage 

heat and cool system with two transformers 

(1H/1C conventional).

Fig. 7. Typical hookup of heat-only system 

(1H conventional).

Fig. 8. Typical hookup of heat only system with fan 

(1H conventional).

COMPRESSOR

CONTACTOR

M19895

OUTDOOR/INDOOR

TEMPERATURE

SENSOR

HEAT RELAY

FAN

RELAY

R

C

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 

FACTORY INSTALLED JUMPER.

OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.  AVAILABLE 
ON SELECT MODELS.  WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.

1

1

3

2

3

OPTIONAL

24 VAC  

COMMON

CONNECTION

Y2

RC

S1

R

S2

W

W2

Y

G

C

2

CONVENTIONAL

C

R

1

COMPRESSOR

CONTACTOR

M19896

OUTDOOR/INDOOR

TEMPERATURE

SENSOR

HEAT RELAY

FAN

RELAY

R

C

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 

REMOVE FACTORY INSTALLED JUMPER.

OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.  AVAILABLE 
ON SELECT MODELS.  WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.

1

1

3

2

3

OPTIONAL

24 VAC  

COMMON

CONNECTION

Y2

RC

S1

R

S2

W

W2

Y

G

C

2

CONVENTIONAL

M19897

OUTDOOR/INDOOR

TEMPERATURE

SENSOR

HEAT RELAY

R

C

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 

FACTORY INSTALLED JUMPER.

OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.  AVAILABLE 
ON SELECT MODELS.  WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.

1

1

3

2

3

OPTIONAL

24 VAC  

COMMON

CONNECTION

Y2

RC

S1

R

S2

W

W2

Y

G

C

2

CONVENTIONAL

M19898

OUTDOOR/INDOOR

TEMPERATURE

SENSOR

HEAT RELAY

FAN

RELAY

R

C

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD 
PROTECTION AS REQUIRED. 

FACTORY INSTALLED JUMPER.

OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR.  AVAILABLE 
ON SELECT MODELS.  WIRES MUST HAVE A CABLE SEPARATE  
FROM THE THERMOSTAT CABLE.

1

1

3

2

3

OPTIONAL

24 VAC  

COMMON

CONNECTION

Y2

RC

S1

R

S2

W

W2

Y

G

C

2

CONVENTIONAL

Summary of Contents for VisionPRO TH8320U

Page 1: ...fully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Selecting Location Install the thermostat about 5 ...

Page 2: ... FIG 5 16 All wiring must comply with local electrical codes and ordinances 1 Select set of terminal identifications Table 2 that corresponds with system type conventional or heat pump in Fig 3 2 Loosen the screws for the appropriate system type selected see Table 2 Insert wires in the terminal block under the loosened screw See Fig 4 3 Securely tighten each screw 4 Push excess wire back into the ...

Page 3: ...HEAT RELAY FAN RELAY R C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 3 2 3 OPTIONAL 24 VAC COMMON CONNECTION Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL M19897 OUTDOOR INDOOR TEMPERATURE SENSOR HEAT RELAY R C PO...

Page 4: ...R SERIES 20 MOTOR OR VALVE M19900 OUTDOOR INDOOR TEMPERATURE SENSOR FAN RELAY R C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 3 2 3 OPTIONAL 24 VAC COMMON CONNECTION Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL COMPRESS...

Page 5: ...NSTALLED JUMPER REMOVED OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABL SEPARATE FROM THE THERMOSTAT CABLE OPTIONAL 24 VAC COMMON CONNECTION MUST COME FROM THE COOLING TRANSFORMER 3 OUTDOOR INDOOR TEMPERATURE SENSOR RC R O B Y G C Y2 L E AUX SI S2 HEATPUMP COMPRESSOR M19903 CHANGEOVER VALVE FAN RELAY R C 1 1 2 2 3 4 3 3 4 OPTIONAL 24 VAC COMMON CONNECTION...

Page 6: ...R INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE OUTDOOR INDOOR TEMPERATURE SENSOR R O B Y G C Y2 L E AUX SI S2 HEATPUMP COMPRESSOR RELAY M19905 CHANGEOVER VALVE FAN RELAY HEAT 2 RELAY AUXILIARY HEAT R C 1 1 2 2 3 4 5 6 6 6 4 5 5 OPTIONAL 24 VAC COMMON CONNECTION EQUIPMENT MONITOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECT...

Page 7: ...he device See Fig 17 Fig 17 Installing batteries on thermostat back Mounting the Thermostat 1 Align the terminal screw blocks with the pins on the back of the thermostat 2 Push the thermostat straight onto the wallplate See Fig 18 R O B Y G C Y2 L E AUX SI S2 HEATPUMP COMPRESSOR 2 COMPRESSOR 1 M19906 CHANGEOVER VALVE FAN RELAY HEAT 2 RELAY AUXILIARY HEAT R C 1 1 2 2 3 4 5 6 6 6 3 5 5 OPTIONAL 24 V...

Page 8: ... on the back of the thermostat in the lower left corner must be removed for this feature to be active Using the Thermostat The thermostat has a touch screen interface Words or symbols appear highlighting the keys as necessary to complete tasks Always press the keys with your finger tips Sharp instruments like a pen or pencil point can damage the thermostat 1 Use the arrow keys to set the Year Mont...

Page 9: ...tructions on changing the program INSTALLER SETUP This Universal Thermostat works with many different system types To operate correctly the thermostat must be set up to operate the installed heating and or cooling system Installer Setup Menus Main Menu Offers the most commonly used options It is necessary to enter this menu to set the thermostat to the type of system it is operating Many applicati...

Page 10: ...omize themselves as you make selections to the Installer Setup Therefore not all Installer Setup Selections are shown or are available to change DONE O MON WED THU FRI SAT A AT SUN INSTALLER SETUP NUMBER FACTORY SETTING ADVANCE TO NEXT INSTALLER SETUP PRESS TO EXIT INSTALLER SETUP CHANGE THE FACTORY SETTING M19922 A U Table 4 Main Installer Setup Menu Select Installer Setup Number Factory Setting ...

Page 11: ... to electric Reversing Valve O B Operation 0190 0 O B terminal is energized for reversing valve in cooling 1 O B terminal is energized for reversing valve in heating Only shown if heat pump system is chosen Backup Heat Source Auxiliary Heat 0200 0 Heat pump backup heat source is electric 1 Heat pump backup heat source is fossil fuel Only shown if 2 heat 1 cool or 3 heat 2 cool heat pump is chosen ...

Page 12: ... this stage changes default cph for 2nd stage heat Cycles per hour cph for 2nd Stage Heat 0250 5 Cycles per hour cph for 2nd Stage Conventional Heat or Auxiliary Heat for 2 H 1C Heat Pump Systems 1 12 1 12 available typical settings 1 1 cph used for steam orgravity system 3 3 cph for hot water systems or high efficiency 90 or better fossil fuel forced air systems 5 5 cph for standard fossil fuel f...

Page 13: ...s 5 5 cph for standard fossil fuel forced air systems 9 9 cph for electric heat systems Onlyshownif 2 heat 1 cool or 3 heat 2 cool heat pump is selected Continuous Backlight 0280 0 Backlight not on continuously Thermostat backlight comes on with each key press 1 Backlight is on continuously thermostat must have a common wire attached for this function Option is always shown however continuously on...

Page 14: ...setpoints can be set no closer than 3 F 1 5 C 2 thru 9 Heating and cooling setpoints can be set no closerthanchosen value 2 2 F 1 C 3 3 F 2 C 4 4 F 2 5 C 5 5 F 3 C 6 6 F 3 5 C 7 7 F 4 C 8 8 F 4 5 C 9 9 F 5 C Shown only if automatic changeover is selected Temperature Indication Scale 0320 0 Temperature is displayed in F 1 Temperature is displayed in C Daylight Savings 0330 1 Daylight savings enable...

Page 15: ...5 40 45 No lockout 15 F 9 5 C 20 F 6 5 C 25 F 4 C 30 F 1 C 35 F 1 5 C 40 F 4 5 C 45 F 7 C Default depends on other selections Shown if Outdoor Temperature for control is selected See Advanced Features section for more information Heat Pump Auxiliary Lockout 0360 0 No heat pump auxiliary lockout 40 45 50 55 60 No lockout 40 F 4 5 C 45 F 7 C 50 F 10 C 55 F 13 C 60 F 15 5 C Shown if electric is chose...

Page 16: ...e Number of Periods 0540 4 Four periods available Wake Leave Return Sleep 2 Two periods available Wake and Sleep Not shown if non programmable is selected 2 or 4 applies to all days of the week Minimum Compressor Off Time 0580 5 Five minute minimum off time for compressor 0 2 3 4 Minimum number of minutes compressor is off between calls for compressor Heat Temperature Range Stop 0600 90 Highest he...

Page 17: ... temperature overshoot Choose 3 if getting temperature undershoot Temperature Control in Cool 0690 2 Standard temperature control in cooling 1 3 1 less aggressive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp Choose 1 if getting temperature overshoot Choose 3 if getting temperature undershoot ...

Page 18: ...g Installer System Test Avoid cycling compressor quickly Table 7 System Test s Select Installer Setup Number Factory Setting Other Choices Comments Options Description Options Description Installer Test Cool Test 1 0 Cool is off 1 2 0 cooloff 1 cool stage 1 turns on 2 cool stages 1 and 2 on System selection determines which tests are available and the number of stages shown Installer Test Fan Test...

Page 19: ...here is only one source of non compressor heat and the E terminal is jumped to the Aux terminal Heat Pump with Electric Auxiliary Backup Heat and Outdoor Temperature Sensor 1 Choose correct heat pump application in Installer Setup Number 0170 2 Choose Electric as Auxiliary Backup Heat Source in Installer Setup Number 0200 3 Choose Outdoor Temperature Sensor for Control Option in Installer Setup Nu...

Page 20: ... locked Check Installer Setup Number 0670 to change keypad locked options Heating or cooling does not come on Thermostat minimum off time is activated Wait up to five minutes for the system to respond System selection is not set to Heat or Cool Set system Selection to correct position O B terminal is not set correctly Heat Pumps only Check Installer Setup Number 0190 and set correctly System type ...

Reviews: