Table 5. Regional Settings Menu.
Select
Installer
Setup
Number
Factory Setting
Other Choices
Comments
Option
Description
Options
Description
Changeover
0300
0
Manual changeover
1
1—auto
changeover
—
Deadband
0310
3
Heating and cooling
setpoints can be set
no closer than 3
°
F
(1.5
°
C)
2 thru 9
Heating and
cooling setpoints
can be set no
closer than chosen
value:
2
—2
°
F (1
°
C)
3
—3
°
F (2
°
C)
4
—4
°
F (2.5
°
C)
5
—5
°
F (3
°
C)
6
—6
°
F (3.5
°
C)
7
—7
°
F (4
°
C)
8
—8
°
F (4.5
°
C)
9
—9
°
F (5
°
C)
Shown only if
automatic
changeover is
selected.
Temperature
Indication
Scale
0320
0
Temperature is
displayed in
°
F.
1
Temperature is
displayed in
°
C.
—
Daylight
Savings
0330
1
Daylight savings
enabled (United
States).
0
0
—daylight savings
is disabled.
Set to 0 in areas that