background image

TH8320U AND TH8321U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

19

69-1706

ADVANCED FEATURES

Outdoor or Indoor Temperature Sensor

Allow outdoor or indoor temperature sensor to absorb the 
air for a minimum of five minutes before taking a reading. 
See the Sensor instructions for more information.

Special Heat Pump Features

Heat Pump with Fossil Fuel Auxiliary Heat (Dual 
Fuel) and Outdoor Temperature Sensor

In this operation, there is no external fossil fuel kit (dual 
fuel kit) installed; the thermostat controls this function.

1.

Choose correct heat pump application in Installer 
Setup Number 0170.

2.

Choose 

Fossil Fuel Option

 as the backup heat 

source in Installer Setup Number 0200.

3.

Choose 

No External Fossil Fuel Kit Option

 is 

controlling back up heat in Installer Setup Number 
0210.

4. Outdoor Temperature Sensor for Control

 

Option

 is automatically chosen in Installer Setup 

Number 0340 (0340 is not shown).

5.

Choose appropriate 

Balance Point Temperature

 

in Installer Setup Number 0350.

OPERATION IN HEAT MODE ABOVE BALANCE POINT 
(OUTDOOR TEMPERATURE)

When the outdoor temperature is above the selected 
Balance Point Temperature (ISU 0350), only the 
compressor operates and the fan (G terminal) energizes 
when the thermostat calls for heat.

OPERATION IN HEAT MODE BELOW BALANCE POINT 
(OUTDOOR TEMPERATURE)

When the outdoor temperature is below the selected 
Balance Point Temperature (ISU 0350), only the Fossil 
Fuel (auxiliary heat) operates and the fan (G terminal) 
does not energize when the thermostat calls for heat.

OPERATION IN EMERGENCY HEAT MODE

The balance point (outside) temperature is not used in 
the Emergency heat mode. When the thermostat is 
moved to the Emergency Heat position, the compressor 
is locked out. The first stage of heat is whatever is 
connected to the E terminal. The second stage of heat is 
what is connected to the Aux. terminal. Often there is 
only one source of non-compressor heat and the E 
terminal is jumped to the Aux. terminal.

Heat Pump with Electric Auxiliary (Backup) Heat 
and Outdoor Temperature Sensor

1.

Choose correct heat pump application in Installer 
Setup Number 0170.

2.

Choose Electric as 

Auxiliary (Backup) Heat 

Source

 in Installer Setup Number 0200.

3.

Choose 

Outdoor Temperature Sensor for 

Control Option 

in Installer Setup Number 0340.

4.

Choose 

Compressor Lockout Temperature

 in 

Installer Setup Number 0350.

5.

Choose 

Auxiliary Lockout Temperature 

in 

Installer Setup Number 0360.

NOTE: There is a 5°F deadband between the         

Compressor and Auxiliary Heat Lockout 
Temperatures

Operation in Heat Mode

When the outdoor temperature is below the Compressor 
Lockout Temperature, only the Auxiliary Heat operates.

When the outdoor temperature is above the Auxiliary 
Lockout Temperature, only the Compressor operates. 
See Fig. 24.

Fig. 24. Heat Pump Operation with Lockout 

Temperatures Set.

When the outdoor temperature is between the two 
temperatures, both the Compressor and Auxiliary Heat 
operate. 

Operation in the Emergency Heat Mode

Once the thermostat is placed into the Emergency Heat 
mode, the compressor and auxiliary lockout features are 
turned off. In the Emergency heat mode, the compressor 
is locked out. The first stage of heat is whatever is 
connected to the E terminal. The second stage of heat is 
connected to the Aux. terminal. Usually the emergency 
and auxiliary heat sources are electric strip heat in these 
cases.

Dehumidification Droop Control

The dehumidification control attempts to control to the 
user's humidity setpoint by turning on the air conditioner. 
In extremely high humidity conditions, the thermostat 
keeps the air conditioner running for up to 3

°

F below the 

temperature setpoint. It does this while trying to achieve 
the desired humidity setpoint and balancing that with the 
temperature setpoint.

35

M19950

COMPRESSOR
LOCKOUT
TEMPERATURE

AUXILIARY
LOCKOUT
TEMPERATURE

COMPRESSOR ONLY

BOTH COMPRESSOR AND

AUXILIARY HEAT

AUXILIARY ONLY

50

OUTDOOR TEMPERATURE

Summary of Contents for VisionPRO TH8320U

Page 1: ...fully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Selecting Location Install the thermostat about 5 ...

Page 2: ... FIG 5 16 All wiring must comply with local electrical codes and ordinances 1 Select set of terminal identifications Table 2 that corresponds with system type conventional or heat pump in Fig 3 2 Loosen the screws for the appropriate system type selected see Table 2 Insert wires in the terminal block under the loosened screw See Fig 4 3 Securely tighten each screw 4 Push excess wire back into the ...

Page 3: ...HEAT RELAY FAN RELAY R C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 3 2 3 OPTIONAL 24 VAC COMMON CONNECTION Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL M19897 OUTDOOR INDOOR TEMPERATURE SENSOR HEAT RELAY R C PO...

Page 4: ...R SERIES 20 MOTOR OR VALVE M19900 OUTDOOR INDOOR TEMPERATURE SENSOR FAN RELAY R C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 3 2 3 OPTIONAL 24 VAC COMMON CONNECTION Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL COMPRESS...

Page 5: ...NSTALLED JUMPER REMOVED OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABL SEPARATE FROM THE THERMOSTAT CABLE OPTIONAL 24 VAC COMMON CONNECTION MUST COME FROM THE COOLING TRANSFORMER 3 OUTDOOR INDOOR TEMPERATURE SENSOR RC R O B Y G C Y2 L E AUX SI S2 HEATPUMP COMPRESSOR M19903 CHANGEOVER VALVE FAN RELAY R C 1 1 2 2 3 4 3 3 4 OPTIONAL 24 VAC COMMON CONNECTION...

Page 6: ...R INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE OUTDOOR INDOOR TEMPERATURE SENSOR R O B Y G C Y2 L E AUX SI S2 HEATPUMP COMPRESSOR RELAY M19905 CHANGEOVER VALVE FAN RELAY HEAT 2 RELAY AUXILIARY HEAT R C 1 1 2 2 3 4 5 6 6 6 4 5 5 OPTIONAL 24 VAC COMMON CONNECTION EQUIPMENT MONITOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECT...

Page 7: ...he device See Fig 17 Fig 17 Installing batteries on thermostat back Mounting the Thermostat 1 Align the terminal screw blocks with the pins on the back of the thermostat 2 Push the thermostat straight onto the wallplate See Fig 18 R O B Y G C Y2 L E AUX SI S2 HEATPUMP COMPRESSOR 2 COMPRESSOR 1 M19906 CHANGEOVER VALVE FAN RELAY HEAT 2 RELAY AUXILIARY HEAT R C 1 1 2 2 3 4 5 6 6 6 3 5 5 OPTIONAL 24 V...

Page 8: ... on the back of the thermostat in the lower left corner must be removed for this feature to be active Using the Thermostat The thermostat has a touch screen interface Words or symbols appear highlighting the keys as necessary to complete tasks Always press the keys with your finger tips Sharp instruments like a pen or pencil point can damage the thermostat 1 Use the arrow keys to set the Year Mont...

Page 9: ...tructions on changing the program INSTALLER SETUP This Universal Thermostat works with many different system types To operate correctly the thermostat must be set up to operate the installed heating and or cooling system Installer Setup Menus Main Menu Offers the most commonly used options It is necessary to enter this menu to set the thermostat to the type of system it is operating Many applicati...

Page 10: ...omize themselves as you make selections to the Installer Setup Therefore not all Installer Setup Selections are shown or are available to change DONE O MON WED THU FRI SAT A AT SUN INSTALLER SETUP NUMBER FACTORY SETTING ADVANCE TO NEXT INSTALLER SETUP PRESS TO EXIT INSTALLER SETUP CHANGE THE FACTORY SETTING M19922 A U Table 4 Main Installer Setup Menu Select Installer Setup Number Factory Setting ...

Page 11: ... to electric Reversing Valve O B Operation 0190 0 O B terminal is energized for reversing valve in cooling 1 O B terminal is energized for reversing valve in heating Only shown if heat pump system is chosen Backup Heat Source Auxiliary Heat 0200 0 Heat pump backup heat source is electric 1 Heat pump backup heat source is fossil fuel Only shown if 2 heat 1 cool or 3 heat 2 cool heat pump is chosen ...

Page 12: ... this stage changes default cph for 2nd stage heat Cycles per hour cph for 2nd Stage Heat 0250 5 Cycles per hour cph for 2nd Stage Conventional Heat or Auxiliary Heat for 2 H 1C Heat Pump Systems 1 12 1 12 available typical settings 1 1 cph used for steam orgravity system 3 3 cph for hot water systems or high efficiency 90 or better fossil fuel forced air systems 5 5 cph for standard fossil fuel f...

Page 13: ...s 5 5 cph for standard fossil fuel forced air systems 9 9 cph for electric heat systems Onlyshownif 2 heat 1 cool or 3 heat 2 cool heat pump is selected Continuous Backlight 0280 0 Backlight not on continuously Thermostat backlight comes on with each key press 1 Backlight is on continuously thermostat must have a common wire attached for this function Option is always shown however continuously on...

Page 14: ...setpoints can be set no closer than 3 F 1 5 C 2 thru 9 Heating and cooling setpoints can be set no closerthanchosen value 2 2 F 1 C 3 3 F 2 C 4 4 F 2 5 C 5 5 F 3 C 6 6 F 3 5 C 7 7 F 4 C 8 8 F 4 5 C 9 9 F 5 C Shown only if automatic changeover is selected Temperature Indication Scale 0320 0 Temperature is displayed in F 1 Temperature is displayed in C Daylight Savings 0330 1 Daylight savings enable...

Page 15: ...5 40 45 No lockout 15 F 9 5 C 20 F 6 5 C 25 F 4 C 30 F 1 C 35 F 1 5 C 40 F 4 5 C 45 F 7 C Default depends on other selections Shown if Outdoor Temperature for control is selected See Advanced Features section for more information Heat Pump Auxiliary Lockout 0360 0 No heat pump auxiliary lockout 40 45 50 55 60 No lockout 40 F 4 5 C 45 F 7 C 50 F 10 C 55 F 13 C 60 F 15 5 C Shown if electric is chose...

Page 16: ...e Number of Periods 0540 4 Four periods available Wake Leave Return Sleep 2 Two periods available Wake and Sleep Not shown if non programmable is selected 2 or 4 applies to all days of the week Minimum Compressor Off Time 0580 5 Five minute minimum off time for compressor 0 2 3 4 Minimum number of minutes compressor is off between calls for compressor Heat Temperature Range Stop 0600 90 Highest he...

Page 17: ... temperature overshoot Choose 3 if getting temperature undershoot Temperature Control in Cool 0690 2 Standard temperature control in cooling 1 3 1 less aggressive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp Choose 1 if getting temperature overshoot Choose 3 if getting temperature undershoot ...

Page 18: ...g Installer System Test Avoid cycling compressor quickly Table 7 System Test s Select Installer Setup Number Factory Setting Other Choices Comments Options Description Options Description Installer Test Cool Test 1 0 Cool is off 1 2 0 cooloff 1 cool stage 1 turns on 2 cool stages 1 and 2 on System selection determines which tests are available and the number of stages shown Installer Test Fan Test...

Page 19: ...here is only one source of non compressor heat and the E terminal is jumped to the Aux terminal Heat Pump with Electric Auxiliary Backup Heat and Outdoor Temperature Sensor 1 Choose correct heat pump application in Installer Setup Number 0170 2 Choose Electric as Auxiliary Backup Heat Source in Installer Setup Number 0200 3 Choose Outdoor Temperature Sensor for Control Option in Installer Setup Nu...

Page 20: ... locked Check Installer Setup Number 0670 to change keypad locked options Heating or cooling does not come on Thermostat minimum off time is activated Wait up to five minutes for the system to respond System selection is not set to Heat or Cool Set system Selection to correct position O B terminal is not set correctly Heat Pumps only Check Installer Setup Number 0190 and set correctly System type ...

Reviews: