V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL

3

65-0029—01

Fig. 1. Approximate mounting dimensions of V4055 actuators and V5055 valves, in in. (mm).

INSTALLATION

When installing this product...

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous

condition.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced, flame safeguard 

control technician.

4.

After installation is complete, check out product opera-

tion as provided in these instructions.

CAUTION

Electrical Shock and Equipment Damage Hazard.

Can cause serious injury or death.

1. Disconnect power supply before making wiring 

connections to prevent electrical shock and 

equipment damage.

2. All wiring must comply with all applicable electrical 

codes, ordinances and regulations. All wiring must 

be NEC Class 1.

3. Voltage and frequency of the power supply 

connected to this control must agree with those 

marked on the device.

4. Maximum total connected load to both switches (if 

used) must not exceed 1800 VA.

9-3/16

(233)

D

3/4 (19) BOLT

HOLES [8] ON

3-3/4 (95)

RADIUS

M23960

3/4
1
1-1/4
1-1/2
2
2-1/2
3
4

VALVE 

SIZE

INCH

13-1/8
13-1/8
13-1/8
13-1/8
13-1/4
13-3/4
13-3/4
16-3/16

333.5
333.5
333.5
333.5
336.5
349.0
349.0
411.0

2-3/4
2-3/4
2-3/4
2-3/4
2-7/8
3-3/8
3-3/8

5-13/16

70.0
70.0
70.0
70.0
73.0
85.5
85.5

128.0

  8-3/16
  8-3/16
  8-3/16
  8-3/16
  8-5/16

  8-13/16
  8-13/16
  11-7/32

208.0
208.0
208.0
208.0
211.1
224.0
224.0
285.0

5-3/4
5-3/4
5-3/4
5-3/4
8-3/8
9-1/4
9-1/4

12-1/2

146.0
146.0
146.0
146.0
212.5
235.0
235.0
317.5

2-1/4
2-1/4
2-1/4
2-1/4
2-3/4
2-3/4
2-3/4
4-5/8

57.0
57.0
57.0
57.0
70.0
70.0
70.0

117.0

4-13/16
4-13/16
4-13/16
4-13/16
7-19/32
7-19/32
7-19/32

122.0
122.0
122.0
122.0
192.5
192.5
192.5

2-13/16
2-13/16
2-13/16
2-13/16
3-1/2
4-1/2
4-1/2

71.0
71.0
71.0
71.0
89.0

114.5
114.5

 

DIM A

IN.

MM

DIM B

IN.

MM

DIM C

IN.

MM

DIM D

IN.

MM

DIM E

IN.

MM

DIM F

IN.

MM

OCTAGON

IN.

MM

B

E

F

C

D

A

1

1/8 OR 1/4 INCH NPT

DOWNSTREAM TAP 

AND PLUG (OPTIONAL

ON DOMESTIC MODELS)

1/4 INCH NPT UPSTREAM 

TAP AND PLUG (1/4 BSP ON

INTERNATIONAL MODELS) 

1

KNOCKOUT

FOR1/2 INCH

CONDUIT (4)

OCTAGON

5 (127)

27/32 (22)

3-23/32 (95)

6-3/4 (172)

ALLOW 4 INCHES (102 MM) CLEARANCE FOR ACTUATOR 

REMOVAL.

ADD 1/8 INCH (3 MM) TO DIMENSION FOR MODELS WITH 

NEMA 4 ENCLOSURE.

ADD 1/4 INCH (6 MM) TO DIMENSION FOR A MODELS WITH 

NEMA 4 ENCLOSURE.

1-9/32

(33)

1/2 INCH NPT UPSTREAM 

TAP AND PLUG (OPTIONAL

ON DOMESTIC MODELS) 

3

2

3

2

Summary of Contents for V4055F

Page 1: ...ow only when the gas valve is fully closed Ambient temperature rating of 40 F to 150 F 40 C to 66 C Valve and actuator may be mounted in any position Optional field adjustable spdt auxiliary switch rated at 112 hp 0 37 kW may be added in the field Standard enclosure meets NEMA 1 IP30 general purpose requirements Red light indicates when valve is ready to open Rocker switch allows manual operation ...

Page 2: ...0 Hz and 50 60 Hz models Mounting Means Actuator mounts directly to valve bonnet with 2 setscrews positioned 90 angular degrees apart Valve and actuator can be mounted in any position Mounting Dimensions See Fig 1 Replacement Parts 130928 Red Indicator Lamp Accessories 133568 Auxiliary Switch Bag Assembly 133569 Valve Closed Indication Switch Bag Assembly Approvals UL and FM IRI Approvable Electri...

Page 3: ...HOLES 8 ON 3 3 4 95 RADIUS M23960 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 VALVE SIZE INCH 13 1 8 13 1 8 13 1 8 13 1 8 13 1 4 13 3 4 13 3 4 16 3 16 333 5 333 5 333 5 333 5 336 5 349 0 349 0 411 0 2 3 4 2 3 4 2 3 4 2 3 4 2 7 8 3 3 8 3 3 8 5 13 16 70 0 70 0 70 0 70 0 73 0 85 5 85 5 128 0 8 3 16 8 3 16 8 3 16 8 3 16 8 5 16 8 13 16 8 13 16 11 7 32 208 0 208 0 208 0 208 0 211 1 224 0 224 0 285 0 5 3 4 5 3 4 5 3 4...

Page 4: ... seal Fig 2 V4055 actuator with cover removed NOTE A V5055A B or D valve can also be fitted with a bon net assembly with 2 seals to provide a valve seal overtravel interlock The SPDT valve closed indication switch is installed to make or break a circuit when the valve is in the closed position The switch is not adjustable NOTE Mark the actuator or valve to indicate any changes made To install the ...

Page 5: ...he installation is complete cycle the valve several times with the manual fuel shutoff cock closed before testing the system in actual operation Service The actuator is not field repairable except for replacing the auxiliary switch valve closed indication switch and READY TO OPEN light See INSTALLATION section for procedure Do not disassemble the valve actuator If the actuator should fail to opera...

Page 6: ...ds 12 Replace the damper crank arm assembly 13 Re attach the wires removed from the actuator terminals and turn on the electrical power 14 With the gas still off cycle the actuator to check for proper mechanical operation CAUTION Be sure to perform a bonnet seal and seat leak check after installation Be sure to read and follow all instructions that come with the actuators valves seal and bonnet ki...

Page 7: ...V4055F G FLUID POWER ACTUATOR WITH MANUAL CONTROL 7 65 0029 01 ...

Page 8: ... Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com V4055F G FLUID POWER ACTUATOR WITH MANUAL CONTROL U S Registered Trademark 2007 Honeywell International Inc 65 0029 01 M S Rev 06 07 ...

Reviews: