V4043H MOTORISED ZONE VALVE

95C-10819—04

2

INSTALLATION

V4043H incorporates a manual lever, the lever should 

normally be in ‘AUTO’ position, but can be moved to ‘MAN. 

OPEN’ position for system draindown and filling purposes 

only.

Before fitting the valve, read through the plumbing and wiring 

instructions.

This product MUST be installed by a competent person. The 

installation MUST conform to I.E.E. Regulations and with The 

Electricity at Work Regulations.

A Class ‘A’ switch (having contact separation of at least 3 mm 

in all poles) must be incorporated in the fixed wiring as a 

means of disconnecting the supply. The system must be 

appropriately fused.

PLUMBING

The valve may be plumbed in at any angle, but must not be 

mounted so that the valve head is below the horizontal level of 

the pipework. In the unlikely event of a leak, a safety hazard 

could result.

Do not grip the valve head while making and tightening up 

plumbing connections. Attach a spanner (32 mm or 1 1/4” AF) 

onto the valve body at each port, whilst tightening up the nuts. 

Tighten compression nuts enough to make a watertight seal.

TAKE CARE NOT TO OVERTIGHTEN.

AUTO

MAN

OPEN

AUTO

MAN

OPEN

AUTO

MAN

OPEN

NO

M32224

NO

Summary of Contents for V4043H

Page 1: ...applications SPECIFICATIONS Voltage 230 240V 50 Hz Power Consumption 6W Lead Supplied 1 metre 5 core Operating Temperature Range 5 to 88 C Maximum Ambient Temperature 52 C Pipe Fitting Sizes 22 mm 28 mm compression fitting 3 4 1 BSP Dimensions and KV values See diagrams SPARES AVAILABLE Powerhead Part No 40003916 001 Motor Part No 40002737 003 Ball O Ring Kit Part No 272742A CARD Fig 1 Dimensions ...

Page 2: ...eparation of at least 3 mm in all poles must be incorporated in the fixed wiring as a means of disconnecting the supply The system must be appropriately fused PLUMBING The valve may be plumbed in at any angle but must not be mounted so that the valve head is below the horizontal level of the pipework In the unlikely event of a leak a safety hazard could result Do not grip the valve head while maki...

Page 3: ...terminal 4 or 6 at junction box then link terminal 4 to terminal 6 with a link wire S Plan C Plan Fig 3 Wiring Diagram Note If using the V4043H1080 1 BSP or V4043H1106 28mm the white wire must be electrically isolated S Plan only HEATING ZONE VALVE T6360B ROOM STAT L641A CYLINDER STAT BLUE G YELLOW BROWN GREY G YELLOW GREY ORANGE ORANGE BROWN BLUE L L N N 3 E L N E 4 5 ST699 PROGRAMMER BOILER PUMP...

Page 4: ... pump C Plan or valve S Plan it should get hot COMPLETION Reset both thermostats to temperature required normally 60 C for cylinder thermostat and 20 C for room thermostat Return programmer to Auto or mode selected by householder Full installation wiring and operating instructions for SUNDIAL products are included in every product pack For special wiring diagrams or applications contact Honeywell ...

Reviews: