Installation Guide

69-2199—05 8

ADVANCED CONFIGURATION

Table 6. Advanced Configuration.

Menu Name

Menu Title (LCD 

top line)

Menu Options (LCD bottom 

line; defaults in bold)

Menu option description

Notes:

Heat Fan

HEAT FAN 

CONTROL

[HVAC] PANEL

Fan control by HVAC

In heat mode, fan controlled by HVAC or 

turned on by panel in call for heat.

 HVAC [PANEL]

Fan control by Panel

Stage 2 Timer

STAGE 2 TIMER

     [5 MIN]   > – 

<   [60 MIN]  

     [5 MIN]   >

5 minutes–60 minutes

Number of minutes to delay before engaging 

second stage.

Purge Timer

PURGE TIME

[2] 3.5  5  MIN

2.0 minutes

Number of minutes panel will purge following 

call for heat or cool.

 2 [3.5]  5  MIN

3.5 minutes

 2  3.5  [5] MIN

5.0 minutes

Purge Fan

FAN IN PURGE

[HVAC] PANEL

Fan control by HVAC

Fan controlled by HVAC or panel during purge.

 HVAC [PANEL]

Fan control by Panel

Purge Dampers

PURGE DAMPERS

[UNCHANGD] OPEN

Dampers Unchanged

Damper position unchanged or all dampers 

open during purge.

 UNCHANGD [OPEN]

Dampers All Open

Auto Changeover Delay  CHANGEOVER 

DELAY

[15] 20  30  MIN

15 minutes auto changeover timer

Number of minutes to delay auto changeover 

when one zone is calling for heat and another 

is calling for cooling.

 15 [20] 30  MIN

20 minutes auto changeover timer

 15  20 [30] MIN

30 minutes auto changeover timer

DATS Enabled

DISCHARGE 

SENSOR

[NO] YES

Disabled

Enables or disables DATS. If Disabled, the 

Multistage DATS Inhibit setting is Disabled.

 NO [YES]

Enabled

DATS High Limit

DAT HIGH LIMIT

    [110 F]    > – <   [180 F]     

<   [160 F]    >

110 deg F–180 deg F

High temperature limit.

DATS Low Limit

DAT LOW LIMIT

     [30 F]    > – <    [60 F]     

<    [40 F]    >

30 deg F–60 deg F

Low temperature limit.

OT Temp Enabled*

OT SENSOR

[NO] YES

Disabled

Enables or disables wireless outdoor tempera-

ture sensor. If Disabled, the Multistage OT 

Temp Lockout setting is Disabled.

 NO [YES]

Enabled

OT Trip Point for 

Multistage Lockout

OT LOCKOUT 

TEMP

      [0 F]    > – <    [50 F]    

<    [50 F]    >

0 deg F–50 deg F

Above this temperature 2nd stage heat is 

locked out.

Multistage DATS 

Inhibit

DAT MSTG INHIBIT

NO [YES]

Enabled

Allow panel to downstage multistage equip-

ment when near DATS high or low limit.

 [NO] YES

Disabled

LCD Contrast Adjust

LCD CONTRAST

     [1]     > – <    [10]    

<   [5]     >

Contrast value 1–10

Sets LCD display contrast for ease of viewing. 

Lowest contrast is 1, highest contrast is 10.

Save Changes

SAVE CHANGES?

[NO] YES

Disabled

Saves or rejects the configuration settings.

 NO [YES]

Enabled

Use the Adjust Setting, Next, and Back buttons to configure the zone panel. See the Configuration section on page 

7 for instructions on using these buttons.

* Used only if Wireless Adapter THM4000R and Wireless Outdoor Sensor C7089R are used.

Press the Mode button until the Wireless LED lights 

up. The TrueZONE must be configured for wireless 

devices to select Wireless mode.

4

CONNECT WIRELESS DEVICES

HOME

MODE

BACK

NEXT

CONFIG

CHECK OUT

ADJUST SETTING

M28194

WIRELESS

Press Next to add devices.
While the display alternates the Press Connect and 

Exit screens, push the Connect button(s) on the 

wireless device(s).
-OR-
Follow the instructions that came with the wireless 

device(s).
Press Next to exit.

Fig. 15

Summary of Contents for TRUEZONE HZ322

Page 1: ...HZ322 TrueZONE Zone Panel Professional Installation Guide 69 2199 05 ...

Page 2: ...90 RH non condensing Temperature Ratings Shipping 20 to 150 F 29 to 66 C Operating 40 to 165 F 40 to 74 C Dimensions See below Emissions Complies with FCC Class B part 15 requirements Read and save these instructions Need Help For assistance with this product please visit http customer honeywell com and or call Honeywell Zoning Hotline toll free at 1 800 828 8367 U S Registered Trademark US Patent...

Page 3: ...r Zone 100 F 38 C 28 8 160 F 71 C 16 8 Use an SDCR Slave Damper Control Relay for addi tional dampers Maximum dampers per panel is limited by transform er size Ensure transformer is large enough to power the panel 7 5 VA and dampers Table 5 Accessories Accessory Description 40 VA transformer AT140A1042 75 VA transformer AT175A1008 Discharge Air Temperature Sensor DATS C7735A1000 SDCR Slave Damper ...

Page 4: ...se and use the base as a template to drill mounting holes Attach the base to the wall stud roof truss or duct with appropriate screws not included Use two screws for attaching to a stud or roof truss or four screws for duct or drywall plaster installations Fig 2 Fig 3 SUPPLY DUCT DATS AT LEAST 3 FT FROM PLENUM DATS ALTERNATE LOCATION TrueZONE PANEL MOUNTED ON RETURN DUCT TrueZONE PANEL MOUNTED ON ...

Page 5: ...zone panel To connect wire to the panel strip approximately 1 4 in of insulation and push wire into terminal To release wire press the button on top of the terminal In retrofit applications trim end of wire if not straight 3 Install dampers using instructions provided with dampers Connect dampers to zone panel NOTE Multiple dampers can be wired in parallel 4 M28023 Rc R C W W2 Y Y2 G M1 M4 M6 R C ...

Page 6: ... assistance with the DATS see the Discharge Air Temperature Installation Instructions Form Number 69 1521 5 Connect equipment as shown here and on page 5 and 6 6 C7735A1000 M28024 SENSOR DATS DATS 8 Connect a dedicated transform er as shown DEDICATED TRANSFORMER R C M24806 R C POWER L1 HOT L2 RH RC W1 E W2 Y1 Y2 G O B DS BK M28025 HVAC FAN RELAY 24 VOLT TRANS G Y Y2 C R W COMPRESSOR RELAY W2 EQUIP...

Page 7: ...C W W2 Y Y2 G RC R C W W2 Y Y2 G RC R C W W2 Y Y2 G RH RC W1 E W2 Y1 Y2 G O B DS BK HZ322 HEAT 1 HEAT 2 COOL 1 COOL 2 FAN PURGE EM HEAT ZONE 1 ZONE 2 ZONE 3 EMERGENCY HEAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L ZONE 1 DAMPER THERMOSTAT M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L ZONE 2 DAMPER THERMOSTAT SENSOR DATS DATS EQUIPMENT R C POWER M1 M4 M6 R C W1 E W2 Y1 Y2 G O B L ZONE 3 DAMPER THERMOSTAT A B C D WIR...

Page 8: ...LIARY AND EMERGENCY HEAT JUMPER W1 E AND W2 4 ABCD TERMINALS FOR THE THM4000R WIRELESS ADAPTER ONLY NEVER WIRE A THM5320R WIRELESS EIM TO THESE TERMINALS 4 M4 OPEN M6 CLOSED M1 COMMON M28020 R C L1 HOT L2 AIR HANDLER FAN RELAY EM HEAT AUX HEAT G Y 24 VOLT TRANS C R E W2 C7735A1000 DATS HEAT PUMP Y C R DEDICATED TRANSFORMER ARD OR ZD DAMPER SPRING OPEN POWER CLOSED ARD OR ZD DAMPER SPRING OPEN POWE...

Page 9: ... CONVENTIONAL NON HEAT PUMP THERMOSTATS OPTIONS TSTAT TIMER ZONES OFF ADVANCED CONFIG NO YES SAVE CHANGES NO YES COMPRESSOR STAGES 1 2 1 2 3 1 AUX HT ENABLED YES NO SET TO YES IF WIRELESS RADIO FREQUENCY THERMOSTATS AND THM4000R ADAPTER ARE USED 2 YES OPTIONS 1 2 3 ZONES INSTALLED 3 OPTIONS 1 2 3 ASKS THIS FOR EVERY ZONE ZONES INSTALLED 3 RF YES ALLOWS YOU TO VIEW CHANGE THE ADVANCED CONFIGURATION...

Page 10: ...imit DAT HIGH LIMIT 110 F 180 F 160 F 110 deg F 180 deg F High temperature limit DATS Low Limit DAT LOW LIMIT 30 F 60 F 40 F 30 deg F 60 deg F Low temperature limit OT Temp Enabled OT SENSOR NO YES Disabled Enables or disables wireless outdoor tempera ture sensor If Disabled the Multistage OT Temp Lockout setting is Disabled NO YES Enabled OT Trip Point for Multistage Lockout OT LOCKOUT TEMP 0 F 5...

Page 11: ...til the Check out LED lights up Use the Adjust Setting and Next buttons to work through the checkout menu as listed below See the Configuration section on page 7 for instructions on using these buttons Steps 3 10 cycle through heating and cooling stages and open and close dampers to verify proper operation of the equipment and dampers These steps energize the equipment and damper terminals Steps 1...

Page 12: ...our 24 months from date of installation unless specified otherwise Variable frequency drive devices VFD and accessories new products for thirty six 36 months and factory refurbished drives for twelve 12 months from date of installation when start up and commissioning is performed by Honeywell VFD Authorized and trained personnel All VFD warranty return products must have prior authorization Form N...

Reviews: