CAUTION

Do not check operation by shorting across termi-
nals of system controls. This will damage the heat
anticipator.

IMPORTANT: To assure accurate temperature control, do

not touch or breathe on bimetal of thermometer.

HEATING

With system switch set at HEAT and fan switch at AUTO,

move the temperature setting lever about 10

°

  F

[6

°

 C] above room temperature.
Gas- or oil-fired systems—heating should start; fan

should start after a short delay.

Single-stage heat pump or central electric heat sys-

tems—both heating and fan should start immediately.

Move temperature setting lever 10

°

 F [6

°

 C] below room

temperature.

Gas- or oil-fired systems—heating should shut off and

fan should shut off after a short delay.

Single-stage heat pump or central electric heat sys-

tems—heating and fan should shut off immediately.

8. With the system operating through the ammeter, wait

one minute, then read the ammeter.

9. Turn the system switch to OFF, and turn off power.

10. Adjust the heat anticipator to match the reading on the

ammeter.

11. Disconnect the ammeter, reconnect the W wire, and

mount the thermostat. Continue with system checkout.

NOTE: The heat anticipator may require further adjustment

for best performance. To lengthen burner-on time, move
the indicator in the direction of the longer arrows—not
more than a half scale marking at a time. To shorten
burner-on time, move indicator in opposite direction.

HEAT ANTICIPATOR SETTINGS (Fig. 4 only)
Heat Pump Systems (for about 3 cycles per hour)
Using ‘B’ Terminal

Set adjustable anticipator to 140 percent of combined

current draw of compressor and fan relays.

Using ‘O’ Terminal

Set adjustable anticipator to maximum scale setting. Limit

combined load current of compressor and fan relays to 0.8
amp, because cooling anticipator provides anticipation dur-
ing heat cycle in this hookup.

Electric Systems (with auto fan in heating and cooling)

Set adjustable anticipator to combined current draw of

heating and fan relays.

Gas- and Oil- Fired Systems
 (without auto fan in heating)

Set adjustable anticipator to current draw of heat relay or

valve.

4

9. Adjust temperature setting lever so mercury bulb is in

horizontal position. See Fig. 1.

10. Carefully replace thermostat cover.

IMPORTANT: An incorrectly leveled thermostat will cause

the temperature control to deviate from setpoint.

Setting and Adjustment

TEMPERATURE SETTING

Push the temperature setting lever to the desired control

point on the temperature scale. The same lever controls both
heating and cooling.

SYSTEM AND FAN SWITCHING

The T834C features SYSTEM and FAN switches for

control of the heating-cooling and fan systems.

The SYSTEM switch controls system operation as fol-

lows:

HEAT: Heating system only operates.
OFF: Both heating and cooling control systems are dis-

connected.

COOL: Cooling system only operates.
The FAN switch controls fan operation as follows:
AUTO: For gas- or oil-fired systems, the fan operates in

response to the thermostat in cooling; fan operates in
response to the plenum fan control in heating. For
single-stage heat pump and electric heat systems, the
fan operates in response to the thermostat in both
heating and cooling.

ON: The fan runs continuously.
To switch positions, use thumb and index finger to slide

lever to desired position. Switch lever must stop directly over
desired function indicator mark for proper circuit operation.

HEAT ANTICIPATOR SETTING

IMPORTANT: The T834C Thermostat has an adjustable

heat anticipator and equipment will cycle properly
ONLY IF THE ANTICIPATOR IS ADJUSTED TO
MATCH THE CURRENT DRAW OF THE ENTIRE
SYSTEM or as recommended by the equipment
manufacturer. Use this thermostat only on systems
with current draws that fall within the range of the
heat anticipator. Do not use this device on Powerpile
(millivolt) Systems.

A current rating is usually stamped in the nameplate of the

primary control. Set the adjustable heat anticipator indicator
to match the value given on the nameplate, except on thermo-
stats used in systems as shown in Figs. 2-4. See Heat
Anticipator Settings (Figs. 2-4).

If current rating is not available, proceed as follows to

determine the rating:

1. Turn off power.
2. Wire thermostat, but do not mount it on the wall.
3. Connect ammeter between W wire and W terminal on

the thermostat.

4. Prepare the system for operation.
5. Turn on power.
6. Turn system switch to heat.
7. Increase thermostat setpoint as necessary to get system

operating.

Summary of Contents for TRADELINE T834C1137

Page 1: ... equipment damage Contact your local waste management authority for in structions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube If you have questions call Honeywell Inc at 1 800 468 1502 J H Rev 2 93 Honeywell Inc 1993 Form Number 69 0434 5 T834C Heating CoolingThermostat TRADELINE Application T834C Thermostats control 24 to 30...

Page 2: ...ble heat anticipator indicator to match the current draw of the primary heating control or as recom mended by the equipment manufacturer see Heat Anticipa tor Setting 4 Connect the wires to the terminals on the back of the thermostat See Figs 3 5 for internal schematic and typical hookup diagrams If using electric heat compatible thermo stat in central electric heat applications jumper terminals 1...

Page 3: ... O 2 G R 1 2 CHANGEOVER RELAY COOL 3 4 4 Fig 4 Internal schematic and typical hookup for T834C1541 in gas or oil fired or central electric heat system Fig 5 Internal schematic and typical hookup for T834C2267 in gas or oil fired single stage heat pump or central electric heat system M2690 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED IN ELECTRIC HEAT OR SINGLE STAGE HEA...

Page 4: ...emperature setting lever so mercury bulb is in horizontal position See Fig 1 10 Carefully replace thermostat cover IMPORTANT Anincorrectlyleveledthermostatwillcause the temperature control to deviate from setpoint Setting andAdjustment TEMPERATURE SETTING Push the temperature setting lever to the desired control point on the temperature scale The same lever controls both heating and cooling SYSTEM...

Page 5: ...stat last turned the compressor off or from when the system first received power This delay protects the compressor WiththesystemswitchsetatCOOLandthefanswitch set at AUTO move the temperature setting lever about 10 F 6 C belowroomtemperature Coolingandfanshould start see NOTE above Move the temperature setting lever about10 F 6 C aboveroomtemperature Coolingandfan should shut off FAN With the sys...

Page 6: ...Automation and Control Solutions Honeywell Internationals Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley Minnesota 55422 Scarborough Ontario M1V 4Z9 ...

Reviews: