Installing and Operating Instructions 

1592020022

 

 

1592020022 XR20CX GB ES m&M r1.1 05.03.2007.doc 

XR20CX 

1/4 

Digital controller with off cycle defrost 

 

XR20CX 

 

CONTENTS 
1.

 

GENERAL WARNING ___________________________________________________1

 

2.

 

GENERAL DESCRIPTION _______________________________________________1

 

3.

 

CONTROLLING LOADS _________________________________________________1

 

4.

 

FRONT PANEL COMMANDS _____________________________________________1

 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION_______________________________1

 

6.

 

MAIN FUNCTIONS _____________________________________________________1

 

7.

 

PARAMETERS ________________________________________________________2

 

8.

 

DIGITAL INPUT ________________________________________________________3

 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS ___________________________3

 

10.

 

X-REP OUTPUT – OPTIONAL ____________________________________________3

 

11.

 

INSTALLATION AND MOUNTING _________________________________________3

 

12.

 

ELECTRICAL CONNECTIONS ____________________________________________3

 

13.

 

HOW TO USE THE HOT KEY_____________________________________________3

 

14.

 

ALARM SIGNALS ______________________________________________________3

 

15.

 

TECHNICAL DATA _____________________________________________________3

 

16.

 

CONNECTIONS _______________________________________________________4

 

17.

 

DEFAULT SETTING VALUES_____________________________________________4

 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and 
quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. 
It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits 
avoiding sudden temperature changes with high atmospheric humidity to prevent  
formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be 
opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to 
“Dixell S.p.A.” (see address) with a detailed description of the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far 
enough from each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) 
in parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

Model XR20C, format 32 x 74 mm,  is a digital thermostat with off cycle defrost designed for 
refrigeration applications at normal temperature. It provides a relay output to drive the 
compressor.  It is also provided with 2 NTC or PTC probe inputs, the first one for temperature 
control, the second one, optional, to connect to the HOT KEY terminals to signal the 
condenser temperature alarm or to display a temperature. The digital input can operate as 
third temperature probe. 
The HOT KEY output allows to connect the unit, by means of the external module XJ485-CX,  
to a network line ModBUS-RTU compatible such as the 

  

monitoring units  of X-WEB 

family. It allows to program the controller by means the HOT KEY programming  keyboard.  
The instrument is fully configurable through special parameters that can be easily 
programmed through the keyboard. 

3.

 

CONTROLLING LOADS 

3.1

 

COMPRESSOR 

The regulation is performed 
according to the temperature 
measured by the thermostat probe 
with a positive differential from the 
set point: if the temperature 
increases and reaches set point plus 
differential the compressor is started 
and then turned off when the 
temperature reaches the set point 
value again. 

Time

Temper.

Compr.

SET

ON

 

In case of fault in the thermostat probe the start and stop of the compressor are timed through 
parameters “COn” and “COF”. 

3.2

 

DEFROST  

Defrost is performed through a simple stop of the compressor. Parameter “IdF” controls the 
interval between defrost cycles, while its length is controlled by parameter “MdF”. 

4.

 

FRONT PANEL COMMANDS 

 

 

: To display target set point; in programming mode it  selects a parameter  or confirm 

an operation. 

 (DEF) 

To start a manual defrost 

 

  (UP): To see the max. stored temperature; in programming mode it browses the 

parameter codes or increases the displayed value. 

  (DOWN) To see the min stored temperature; in programming mode it browses the 

parameter codes or decreases the displayed value. 

 

To activate / deactivate the  energy saving cycle.  

 Not 

enabled 

KEY COMBINATIONS: 

  

 

To lock & unlock the keyboard. 

 

+

  

 

To enter in programming mode. 

  

+

  

To return to the room temperature display. 

4.1

 

USE OF LEDS 

Each LED function is described in the following table. 

LED 

MODE 

FUNCTION 

 

ON Compressor 

enabled 

 

Flashing 

Anti-short cycle delay enabled 

 

ON Defrost 

enabled 

  ON 

An alarm is occurring 

  ON 

Continuous cycle is running 

  ON Energy 

saving 

enabled 

°C/°F  ON Measurement 

unit 

°C/°F  Flashing Programming 

phase 

5.

 

MAX & MIN TEMPERATURE MEMORIZATION 

5.1

 

HOW TO SEE THE MIN TEMPERATURE 

1. 

 

Press and release the 

8

 key. 

2. 

 

The “Lo” message will be displayed followed by the minimum temperature recorded. 

3. 

 

By pressing the 

8

 key again or by waiting 5s the normal display will be restored. 

5.2

 

HOW TO SEE THE MAX TEMPERATURE 

1. 

 

Press and release the 

9

 key. 

2. 

 

The “Hi” message will be displayed followed by the maximum  temperature recorded. 

3. 

 

By pressing the 

9

 key again or by waiting 5s the normal display will be restored. 

5.3

 

HOW TO RESET THE MAX AND MIN TEMPERATURE RECORDED 

1.

 

Hold press the SET key for more than 3s, while the max. or min temperature is 
displayed. (rSt message will be displayed) 

2.

 

To confirm the operation the “rSt” message starts blinking and the normal temperature 
will be displayed. 

6.

 

MAIN FUNCTIONS 

6.1

 

HOW TO SEE THE SETPOINT 

 

1.

 

Push and immediately release the SET key: the display will show 
the Set point value; 

2.

 

Push and immediately release the SET key or wait for 5 seconds to  

display the probe value again. 

6.2

 

HOW TO CHANGE THE SETPOINT 

1.

 

Push the SET key for more than 2 seconds to change the Set point value; 

2.

 

The value of the set point will be displayed and the “°C” or “°F” LED starts blinking; 

3.

 

To change the Set value push the 

or 

8

 arrows within 10s. 

4.

 

To memorise the new set point value push the SET key again or wait 10s. 

6.3

 

HOW TO START A MANUAL DEFROST 

 

Push the DEF key for more than 2 seconds and a manual defrost will 
start. 

Summary of Contents for XR20CX

Page 1: ...rd temperature probe The HOT KEY output allows to connect the unit by means of the external module XJ485 CX to a network line ModBUS RTU compatible such as the monitoring units of X WEB family It allows to program the controller by means the HOT KEY programming keyboard The instrument is fully configurable through special parameters that can be easily programmed through the keyboard 3 CONTROLLING ...

Page 2: ...mpressor is OFF in case of faulty thermostat probe With COF 0 compressor is always active CH Type of action CL cooling Ht heating DISPLAY CF Temperature measurement unit C Celsius F Fahrenheit WARNING When the measurement unit is changed the SET point and the values of the parameters Hy LS US Ot ALU and ALL have to be checked and modified if necessary rES Resolution for C in 1 C dE 0 1 C allows de...

Page 3: ...ature range allowed for correct operation is 0 60 C Avoid places subject to strong vibrations corrosive gases excessive dirt or humidity The same recommendations apply to probes Let air circulate by the cooling holes 12 ELECTRICAL CONNECTIONS The instrument is provided with screw terminal block to connect cables with a cross section up to 2 5 mm2 Before connecting cables make sure the power supply...

Page 4: ...mpressor ON time with faulty probe 0 255 min 15 Pr2 COF Compressor OFF time with faulty probe 0 255 min 30 Pr2 CH Kind of action CL cooling Ht heating cL Pr1 CF Temperature measurement unit C F C F Pr2 rES Resolution in integer dE dec point dE in Pr1 dLy Display temperature delay 0 20 0 min 10 sec 0 Pr2 IdF Interval between defrost cycles 1 120 ore 8 Pr1 MdF Maximum length for defrost 0 255 min 20...

Reviews: