49
TR80 - Installation and Operation Guide
Default values allow the following overrides
3. 13. 5 Auto-reset of occupancy override
The TR80 can be configured to automatically cancel a user occupancy override when the mas
-
ter occupancy mode changes (holding register 1500).
Bit definitions:
Bit0: When master mode changes to UNOCC, cancel UNOCC override
Bit1: When master mode changes to UNOCC, cancel STBY override
Bit2: When master mode changes to UNOCC, cancel OCC override
Bit3: reserved
Bit4 When master mode changes to OCC, cancel BYPASS override
Bit5: When master mode changes to OCC, cancel OCC override
By default, all bits are set
3.14 LIGHTING CONTROL
TR 80 wall module supports upto four lighting groups. General lighting configuration parame
-
ters are as follows:
Override mode
Values
From OFF
none
From UNOCCUPIED
Holiday and Bypass
From STANDBY
Occupied, Holiday and Bypass
From OCCUPIED
Unoccupied, Holiday and Bypass
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Unit
Range
Default
value
Holding
2508
42509
R/W
Occupancy Auto
Reset
508
enum
see
below
55
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
Parameter
Unit
Range
Default
Value
Holding
2300
42301
R/W
Light Group
Count
300
int
0…4
2
Holding
2301
42302
R/W
Light
adjustment
step size
301
enum
0: 1%
1: 2%
2: 5%
3: 10%
4: 20%
3
Holding
1308
41309
R/W
Group light
state
-
bitwise
Bit0: Group 1 is ON
Bit1: Group 2 is ON
Bit2: Group 3 is ON
Bit3: Group 4 is ON