TR80 - Installation and Operation Guide
48
3. 13. 3 Holiday & Bypass overrides
When the user activates Holiday override, the system will remain off (or in building protec
-
tion mode) until the set time (number of days) expires.
When the user activates Bypass override, the system will remain in comfort mode until the
set time (number of minutes) expires.
When the user overrides occupancy to holiday or bypass mode and sets the desired time,
the relevant remaining time register will be set to the user selected value and displayed on
the screen (for example as scrolling text “HOLIDAY FOR 7 DAYS”). The wall module will not
automatically count back from the set time. It is the responsibility of the master controller
to keep time and update the remaining days/minutes in the relevant register.
3. 13. 4 Allowed Overrides
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Unit
Range
Default
value
Holding
2501
42502
R/W
Holiday
default time
501
days
1-45 or unlimited
7 days
Holding
2502
42503
R/W
Bypass
default time
502
mins
10-1440 mins
(or 65535 =
unlimited)
180
mins
Holding
2503
42504
R/W
Bypass
adjust step
503
enum
0: 10 mins
1: 20 mins
2: 30 mins
3: 60 mins
2
Holding
1502
41503
R/W
Bypass
remaining
minutes
-
Int
0
Holding
1503
41504
R/W
Holiday
remaining
time
-
int
0
Holding
2509
42510
R/W
Bypass time
max
509
mins
30-1440 mins
180
mins
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Range
Default
value
Holding
2504
42505
R/W
Allowed overrides
from OFF
504
bit0: unused
bit1: unused
bit2: Allow override to
OCCUPIED
bit3: Allow override to OFF
bit4: Allow override to
HOLIDAY
bit5: Allow override to UNOCC
bit6: Allow override to
STANDBY
bit7: Allow override to BYPASS
0
Holding
2505
42506
R/W
Allowed overrides
from UNOCC
505
144
Holding
2506
42507
R/W
Allowed overrides
from STANDBY
506
148
Holding
2507
41508
R/W
Allowed overrides
from OCC
507
176