39
TR80 - Installation and Operation Guide
Ring brightness in normal operation and ring brightness in SLEEP mode can be individually
set.
The ring colour and style
(note: check document for consistency of 'colour'/'color' normally changes automatically
based on hvac mode (heating = orange, cooling = blue…) received from controller. The master
controller can override the automatically determined colour by writing a value to the ‘Ring
Colour’ register. The format is RGB565 (5 bits red, 6 bits green, 5 bits blue from most signifi
-
cant to least). A value of 0 (corresponding to black) represents AUTO mode, meaning the LED
ring changes colour according to currently active hvac mode.
The controller can also override the ring style.
3. 11. 3 Temperature display configuration
It is possible to disable temperature unit change on the wall module and have it fixed in Celsius
or Fahrenheit.
Holding
1101
41102
R/W
Ring style
-
enum
0: auto
1: off
2: steady
3: slow breath
4: medium breath
5: fast breath
6: blink
7: fast blink
1
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Type
Range
Default
value
Register
type
Relative
Address
Absolute
Address
Dir
Name
Config
parameter
Type
Range
Default
value
Holding
2106
42107
R/W
Room
temperature
display
resolution
104
Enum
0: don't display
1: 1 deg
resolution
2: 0.5 deg
resolution
3: 0.1 deg
resolution
1
Holding
2107
42108
R/W
Outdoor
temperature
display
resolution
105
enum
0: 1 deg
resolution
1: 0.5 deg
resolution
2: 0.1 deg
resolution
2
Holding
2108
42109
R/W
Temperature
unit & user
change
option
106
enum
0: °C (user can
change)
1: °F (user can
change)
2: °C (fixed)
3: °F (fixed)
0