background image

THX9321 PRESTIGE

®

 2.0 AND THX9421 PRESTIGE

®

 IAQ WITH EIM

68-0311—02

148

Fig. 338. Wood stove with heat pump and backup electric strips. (For applications in which the thermostat only needs to 

run the blower fan when stove is hot).

1 Select Geothermal Radiant Heat at ISU 2010. Connect Fan to U1, U2, or U3 as shown in the wiring diagram.
2 “U” terminals are normally open dry contacts when set up for geothermal radiant heat.
3 L/A terminal sends continuous output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD. 

See “Economizer Module Wiring Diagrams” beginning on page 151.

4 Y2 used with heat pumps that have 2 compressor stages.

NOTE: In Fig. 338, the thermostat will energize only the fan with a call for stage 1 heat. If the wood stove is hot, heat 

comes from the fan coil. If the wood stove is cold, only the fan runs. The thermostat will upstage to the heat 

pump and backup heat as needed to maintain the temperature.

O/B

AUX1

AUX2

O

W

Y

Y2

G

R

C

O

Y

Y2

R

C

L/A

TO THERMOSTAT

THERMOSTAT/EIM

HEAT PUMP

AIR HANDLER

HEAT PUMP

M31487

2

4

4

1

Summary of Contents for THX9321 Prestige 2.0

Page 1: ...ou for assistance Requires Equipment Interface Module Delta T Installer Test Save time by viewing Delta T while running a system test to verify proper operation Requires Equipment Interface Module Universal Inputs EIM S1 S2 S3 S4 Assignable inputs allow you to setup Indoor and Outdoor Temperature Sensors Discharge and Return Air Sensors or Dry Contact Devices Dry Contact Devices can be used to tri...

Page 2: ...onal Accessories 70 Alerts and Diagnostics 87 Delta T Diagnostics 87 Before You Set Up Delta T Diagnostics 87 Setting up Alerts and Diagnostics 88 Delta T Alerts 90 Delta T Alerts and Utility Saver Switches 91 Data Logs 91 Alerts Log 92 User Interactions Log 93 Dry Contact Alerts 95 Installer Tests 68 Using the Equipment Test 69 Using the Wireless Signal Strength Test 69 Indoor Air Quality IAQ Con...

Page 3: ...t Indication Prestige 2 0 and Prestige IAQ 2 0 displays Auxiliary Heat On when the thermostat turns the auxiliary heat on Interstage Differential Comfort The thermostat keeps the indoor temperature within 1 degree of the setpoint droop less control The thermostat turns on stage 2 when the capacity on stage 1 reaches 90 When the interstage differential is set to 1 0 or higher the ther mostat stages...

Page 4: ...Prestige 2 0 thermostat in in mm Fig 4 Dimensions of THX9321 Prestige 2 0 cover plate in in mm Fig 5 Dimensions of Equipment Interface Module in in mm M34630 3 5 16 84 3 1 2 89 4 1 2 115 7 8 22 M34262 1 25 32 46 5 33 64 140 2 1 8 54 4 21 64 110 1 25 32 46 6 7 8 175 2 1 8 54 5 127 M33329A 6 13 16 173 3 5 16 84 1 7 16 36 3 7 8 99 M33330 3 19 64 84 7 29 32 201 5 1 2 140 M33331 4 53 64 123 8 7 8 225 9...

Page 5: ...Front Gray Side THM5421R1021 Equipment Interface Module C7089R1013 Wireless Outdoor Sensor 50062329 001 Discharge Return Sensors Qty 2 Prestige IAQ Kit YTHX9421R5085WW THX9421R5021WW Thermostat White Front White Side THM5421R1021 Equipment Interface Module 50062329 001 Discharge Return Sensors Qty 2 Prestige IAQ Kit YTHX9421R5085BB THX9421R5021BB Thermostat Black Front Black Side THM5421R1021 Equi...

Page 6: ...x 38 Arctic White Gray Wireless Entry Exit Remote REM1000R1003 32 to 120 F 0 to 48 9 C 5 to 90 Non Condensing 20 to 120 F 28 9 to 48 9 C 3 15 16 x 1 15 16 x 5 8 101 x 50 x 16 Arctic White Wireless Vent and Filter Boost Remote HVC20A1000 32 to 120 F 0 to 48 9 C 5 to 90 Non Condensing 20 to 120 F 28 9 to 48 9 C 3 15 16 x 1 15 16 x 5 8 101 x 50 x 16 Arctic White Wireless Outdoor Sensor C7089R1013 40 ...

Page 7: ...C PIR Sensor 4 to 104 F 20 to 40 C Receiver 3 6 x 3 4 x 1 2 91 4 x 86 4 x 30 5 Door Sensor 1 4 x 2 3 x 0 6 35 8 x 57 6 x 15 2 PIR Sensor 2 8 x 3 9 x 1 1 71 x 100 x 28 White THX9421 Coverplate covers marks left by old thermostats THP2400A1027W Includes 2 cover plates Small 5 33 64 x 4 21 64 140 x 110 Large 6 7 8 x 5 175 x 127 White THX9421 Coverplate covers marks left by old thermostats THP2400A102...

Page 8: ...ompleting installation use these instructions to verify the product operation Finding Your Password Date Code You will need the thermostat password to Make changes to the Installer Setup Setup Diagnostics Perform an Installer Test View Data Logs Add remove rename or view connected RedLINK accessories Reset the thermostat to Factory Default settings The password Date Code is located on the back of ...

Page 9: ...e the connect button on the RedLINK device at the desired mounting loca tion If the RedLINK device connects then it will work reliably during normal operation If the RedLINK device does NOT connect try a new location During the con nection process the signal is sent at low power and during normal operation the signal is sent at high power To connect a RedLINK device make sure to press and quickly ...

Page 10: ...ransformer to the C screw terminal of the EIM Leave the metal jumper wires in place between R RC and RH Two Transformer System Connect the common side of the cooling transformer to the C screw terminal of the EIM Remove the metal jumper wire between RC and RH Connect the hot side of heating transformer to RH and leave the jumper wire between R and RC and connect the hot side of cooling transformer...

Page 11: ...ARGE SENSOR WHEN SETTING THE LIMITS BE SURE TO CONSIDER THE AFFECT THAT THE HUMIDIFIER HAS ON DELTA T MOUNT RETURN SENSOR HERE DOWNSTREAM OF VENTILATOR OR DEHUMIDIFIER MOUNT DISCHARGE SENSOR HERE ABOVE CENTER OF A COIL UPSTREAM OF STEAM OR FAN POWERED HUMIDIFIER VENTILATOR OR DEHUMIDIFIER M33076A HEAT EXCHANGER BLOWER MOUNT RETURN SENSOR HERE DOWNSTREAM OF DEHUMIDIFIER ALTERNATE MOUNTING LOCATION ...

Page 12: ...ot install the thermostat where it can be affected by Drafts or dead spots behind doors and in corners Hot or cold air from ducts Radiant heat from sun or appliances Concealed pipes and chimneys Unheated uncooled areas such as an outside wall behind the thermostat Installing Wallplate CAUTION Electrical Hazard Can cause electrical shock or equipment damage Disconnect power before wiring The thermo...

Page 13: ... C and R terminals of the TrueZONE panel or to a separate 24 volt transformer not provided See Fig 20 2 Snap thermostat onto wallplate after wiring is complete THX9321 Installation THERMOSTAT WIRED DIRECTLY TO THE HVAC EQUIPMENT OR ZONE PANEL 1 Refer to THX9321 Thermostat Wiring Diagrams begin ning on page 141 2 Snap thermostat onto wallplate after wiring is complete INSTALLATION WITH EQUIPMENT IN...

Page 14: ...f used beginning on page 15 3 If no RedLINK accessories are used and there is no EIM or TrueZONE Wireless Adapter skip to Completing Ini tial Setup beginning on page 17 Outdoor Air Sensor 1 Install 2 fresh AA lithium batteries Fig 22 Portable Comfort Control 1 Install 3 fresh AA alkaline batteries Fig 23 Indoor Air Sensor 1 Install 2 fresh AAA alkaline batteries Fig 24 RedLINK Internet Gateway 1 C...

Page 15: ...or zoned Used with or without an Equipment Interface Module THM5421 Used with or without the TrueZONE Wireless Adapter THM4000 1 Follow prompts on the screen to select the appropriate options Fig 28 NOTE If you are connecting the thermostat to the True ZONE Wireless Adapter THM4000 refer to the TrueZONE instructions to link the thermostat and RedLINK accessories Linking Thermostat to Equipment Int...

Page 16: ...t on New Accessories Continue to step 2 NOTE Accessories must be at least 2 feet away from the thermostat or EIM during the linking process 2 While the Add Device screen is displayed listening mode press and quickly release the CONNECT button on each new RedLINK accessory NOTE For locations of CONNECT buttons on RedLINK accessories see Locating the Con nect Buttons on RedLINK Accessories begin nin...

Page 17: ...g RedLINK Accessories to the Thermostat If you want to add RedLINK accessories after the thermostat has been setup follow these steps 1 Touch Menu 2 Select Installer Options Fig 37 3 Enter password date code and touch Done See Find ing Your Password Date Code to Access Installer Options beginning on page 20 for more information Fig 38 4 Select Wireless Device Manager Fig 39 5 Select Add Device to ...

Page 18: ...s on RedLINK Accessories Wireless Outdoor Sensor 1 Press and quickly release the CONNECT button on the Wireless Outdoor Sensor After a short delay up to 15 seconds the thermostat will display Wireless Outdoor Sensor added Fig 43 Wireless outdoor sensor connect button Portable Comfort Control 1 Press CONNECT on the Portable Comfort Control dis play screen Fig 44 Portable Comfort Control connect but...

Page 19: ...e at www mytotalconnectcomfort com Enter the MAC ID and MAC CRC numbers located on the bottom of the Internet Gateway For addi tional information see instructions provided with the device TrueSTEAM 1 Press and quickly release the CONNECT button on THM4000 Wireless Adapter After a short delay the CONNECTED status light will glow steady green Fig 48 Connect button on TrueSTEAM wireless adapter Wirel...

Page 20: ...the status light turns red the remote did not link with the thermostat for the connection process NOTE The thermostat can work with up to 3 Entry Exit remotes Each Entry Exit remote can control up to 16 thermostats NOTE The thermostat can work with up to 6 Vent Boost remotes Finding Your Password Date Code to Access Installer Options You will need the thermostat password to Make changes to the Ins...

Page 21: ...e screen to select the desired setup options See Table 4 for Installer Setup options Table 3 Installer Options Menu Item Description Create Setup Press CREATE SETUP to set all system settings one by one View Edit Current Setup Press VIEW EDIT CURRENT SETUP to select a specific function and make quick changes Set Up Diagnostics Press SET UP DIAGNOSTICS to set up and test Delta T diagnostics Install...

Page 22: ...pter 1030 Device Name Enter Device Name Thermostat Both No The Portable Comfort Control remote and Web Interface displays the name of the thermostat that you enter on this screen 1030 Display on Home Screen No Yes select check box No Commercial No Thermostat location name can be displayed on the home screen This feature is typically used when multiple thermostat s are mounted in a manager s office...

Page 23: ...30 Ventilation High Temperature Lockout ISU 10130 Ventilation High Dew Point Lockout requires Wireless Outdoor Sensor ISU 13070 Allow Heat Delta T Diagnostics when Outdoor Temperature is Out Temp Range ISU 13080 Allow Heat Delta T Diagnostics when Outdoor Humidity is Out Humidity Range ISU 13110 Allow Backup Heat Delta T Diag when Outdoor Temperature is Out Temp Range ISU 13120 Allow Backup Heat D...

Page 24: ...This ISU is only displayed when ISU 2010 Heating Equipment Type is Geothermal Radiant Heat Geothermal Radiant Heat must be wired to a universal terminal U1 U2 or U3 U1 U2 and U3 are normally open dry contacts when configured for a stage of Heat U1 U2 and U3 require power from the system transformer or a separate transformer U3 is only available on the Equipment Interface Module EIM 2040 What Termi...

Page 25: ...10 is Residential 2 if ISU 1010 is Commercial Both No Conventional Cool Stage 3 and 4 are only available if ISU 1010 is Commercial Cool Stage 3 and 4 must be wired to a universal terminal U1 U2 or U3 Heat Pumps Maximum of 2 Compressor Stages for heat pump systems 2020 2070 Heat Stages Backup Heat Stages 1 3 Default is 1 stage if ISU 1010 Application is Residential Default is 2 stages if ISU 1010 A...

Page 26: ...ISU 2010 Heating Equipment Type is Electric Forced Air Hot Water Fan Coil or Other The thermostat automatically defaults to Equipment Controls Fan when ISU 2010 Heating Equipment Type is Standard Efficiency Gas Forced Air High Efficiency Gas Forced Air or Oil Forced Air No Fan is only displayed when ISU 2010 Heating Equipment Type is Other 2120 Backup Heat Type None Standard Efficiency Gas Forced ...

Page 27: ... Forced Air or Other When ISU 2010 Heating Equipment Type is Hot Water Fan Coil Electric Forced Air or Other you can select how the Backup Heat operates The thermostat can be setup to keep the primary heat source on when it calls for Backup Heat or the thermostat can be setup to turn off the primary heat source when it calls for Backup Heat When ISU 2010 Heating Equipment Type is Hot Water Radiant...

Page 28: ...t and there is at least one stage of backup heat See Heat Pump and Backup Heat Operation beginning on page 100 2190 External Fossil Fuel Kit Thermostat Controls Backup Heat External Fossil Fuel Kit Controls Backup Heat Thermostat Controls Backup Heat Both No This ISU is only displayed when ISU 2010 Heating Equipment Type is Air to Air Heat Pump Geothermal Heat Pump or Geothermal Radiant Heat and I...

Page 29: ...L A terminal is energized during Occupied periods and when the user overrides the temperature The terminal is de energized during Unoccupied periods and in Standby mode Economizer The thermostat controls an economizer module to provide ventilation during Occupied periods and free cooling when outdoor conditions are favorable The A L A terminal is energized during Occupied periods and during a call...

Page 30: ... 3 4 or 5 F the thermostat will not show the full Deadband range For example if you set a Deadband of 3 F and an Over Cooling Limit of 2 F the minimum Deadband that you can select will be 5 F This prevents the heating system from turning on when the thermostat over cools to reach the dehumidification setting 3010 Temperature Control Options Basic Options Advanced Options Advanced Options PID Setti...

Page 31: ...at is set to 2 cool stages The indoor temperature must rise to the selected differential setting before the thermostat turns on the stage of cooling For example if stage 2 is set to 2 F 1 0 C the indoor temperature must be 2 F 1 0 C away from the setpoint before stage 2 turns on When set to Comfort the thermostat uses the stage of cooling as needed to keep the indoor temperature within 1 F 0 5 C d...

Page 32: ...t drop to the selected differential setting before the thermostat will turn on the stage of heating For example if stage 2 is set to 2 F 1 0 C the indoor temperature must be 2 F 1 0 C away from the setpoint before stage 2 turns on When set to Comfort the thermostat will use the stage of heating as needed to keep the indoor temperature within 1 F 0 5 C degree of the setpoint 3050 Staging Control He...

Page 33: ...rmal Forced Air System is set to Used for Heating and Cooling The indoor temperature must drop to the selected differential setting before the thermostat will turn on the stage of heating For example if stage 1 is set to 2 F 1 0 C the indoor temperature must be 2 F 1 0 C away from the setpoint before stage 1 turns on When set to Comfort the thermostat will use the stage of heating as needed to kee...

Page 34: ...nced to view or adjust Backup Heat Differential Stage 2 This ISU is only displayed if there are 2 backup heat stages The indoor temperature must drop to the selected differential setting before the thermostat will turn on backup heat stage 2 For example if backup heat stage 2 is set to 2 F 1 0 C the indoor temperature must be 2 F 1 0 C away from the setpoint before backup heat stage 2 turns on Whe...

Page 35: ...n outdoor sensor This ISU is only displayed if ISU 2010 Heating Equipment Type is Air to Air Heat Pump Geothermal Heat Pump or Geothermal Radiant Heat and ISU 2190 External fossil fuel kit is set to Thermostat Controls Backup Heat See Heat pump with outdoor temperature lockouts beginning on page 100 3130 Radiant Heat Cycles Per Hour Stage 1 Note Stage 1 is not displayed if there is only 1 stage of...

Page 36: ...or adjust cycle rate This ISU is only displayed when ISU 2070 Cool Compressor Stages is set to 1 stage Cycle rate limits the maximum number of times the system can cycle in a 1 hour period measured at a 50 load For example when set to 3 CPH at a 50 load the most the system will cycle is 3 times per hour 10 minutes on 10 minutes off The system cycles less often when load conditions are less than or...

Page 37: ...en when load conditions are less than or greater than a 50 load 3140 Cool Cycles Per Hour Stage 4 1 to 6 CPH 3 Commercial No ISU 3010 Temperature Control Options must be set to Advanced to view or adjust cycle rate This ISU is only displayed when ISU 1010 Application is set to Commercial and ISU 2070 Cool Stages is set to 4 stages Cycle rate limits the maximum number of times the system can cycle ...

Page 38: ...CPH Hot Water Radiant Heat 3 CPH Geothermal Radiant Heat 3 CPH Steam 1 CPH Gravity 1 CPH 3150 Heat Cycles Per Hour Stage 2 Note Depending on the application the text displayed on the screen may show the specific heating equipment type 1 to 12 CPH Default varies based on heating equipmenttype selected Both No ISU 3010 Temperature Control Options must be set to Advanced to view or adjust cycle rate ...

Page 39: ... Water Radiant Heat 3 CPH Geothermal Radiant Heat 3 CPH Steam 1 CPH Gravity 1 CPH 3160 Backup Heat Cycles Per Hour Stage 1 Note Stage 1 is not displayed if there is only 1 stage 1 to 12 CPH Default varies based on heating equipmenttype selected Both No ISU 3010 Temperature Control Options must be set to Advanced to view or adjust cycle rate This ISU is only displayed when ISU 2070 or 2130 Backup H...

Page 40: ...Water Fan Coil 3 CPH Hot Water Radiant Heat 3 CPH Geothermal Radiant Heat 3 CPH Steam 1 CPH Gravity 1 CPH 3170 Cooling Throttling Range 1 F to 30 F 2 F Commercial No The default Cooling Throttling range is 2 F 1 5 C which is appropriate for most applications Do not change this setting unless advised to do so by Honeywell technical support The throttling range controls the cycling of the system and...

Page 41: ...on minimum off timer that prevents the compressor from restarting too early after a shutdown The minimum off timer is activated after the compressor turns off If there is a call during the minimum off timer the thermostat shows waiting for equipment in the display 3260 Extended Fan Run Time in Cool 0 30 60 90 seconds 2 3 4 5 6 7 8 9 10 11 12 13 14 15 minutes 0 seconds Both No After the call for co...

Page 42: ... 1 hour to the amount set for the Override Duration 1 12 hours Default setting is 3 hours If set to No Limit the user can adjust the Hold Until time up to 24 hours 4050 Minimum Heat Recovery Ramp Rate Off 1 F hr to 20 F hr 5 F hr Commercial No Off The heating system will begin recovery at the time that is scheduled When a Minimum Recovery Ramp Rate is set the thermostat will begin recovery early t...

Page 43: ... in degrees per hour depending on the outdoor temperature If there is no outdoor sensor the Minimum Recovery Ramp Rate is used 4060 Maximum Heat Recovery Ramp Rate Off 1 F hr to 20 F hr 8 F hr Commercial No Off The heating system will begin recovery at the time that is scheduled When a Maximum Recovery Ramp Rate is set the thermostat will begin recovery early to ensure the temperature is reached a...

Page 44: ...n the outdoor temperature 4070 Minimum Cool Recovery Ramp Rate Off 1 F hr to 20 F hr 3 F hr Commercial No Off The cooling system will begin recovery at the time that is scheduled When a Minimum Recovery Ramp Rate is set the thermostat will begin recovery early to ensure the temperature is reached at the scheduled time Set a Minimum Recovery Ramp Rate based on the rate that the cooling system can r...

Page 45: ... in degrees per hour depending on the outdoor temperature If there is no outdoor sensor the Minimum Recovery Ramp Rate is used 4080 Maximum Cool Recovery Ramp Rate Off 1 F hr to 20 F hr 6 F hr Commercial No Off The cooling system will begin recovery at the time that is scheduled When a Maximum Recovery Ramp Rate is set the thermostat will begin recovery early to ensure the temperature is reached a...

Page 46: ...n heating or cooling recovery early to ensure that the temperature is reached at the scheduled time The thermostat will adjust the start time of the equipment based on how quickly the scheduled temperature was reached on previous days 4100 Minimum Cool Setpoint 50 F to 99 F 50 F Both No The user cannot set the temperature below this level 4100 Maximum Heat Setpoint 40 F to 90 F 90 F Both No The us...

Page 47: ...h No The thermostat maintains this Heat setting when the user presses Away Unoccupied at the Entry Exit Remote Select None to delete this temperature setting The thermostat only responds to the Entry Exit Remote if a temperature is pre set at this screen See Wireless Entry Exit Remote beginning on page 128 4140 Residential Entry Exit Remote Vacation Cool Setpoint Commercial Entry Exit Remote Holid...

Page 48: ...r Name Sensor Name Indoor Sensor Both Yes Wired Sensors requires an EIM Equipment Interface Module Enter a name location of the Wired Indoor Air Temperature Sensor 5020 What Terminals are Wired to the Indoor Temperature Sensor None S1 S2 S3 S4 None Both Yes Wired Sensors requires an EIM Equipment Interface Module 5030 Indoor Temperature Sensor Type 10K 20K 10K if ISU 1010 Application is Residentia...

Page 49: ...an EIM Equipment Interface Module Select 10K or 20K based on the sensor installed Refer to resistance values below 50062329 001 10K ohm 32005180 002 10K ohm C7735A1000 10K ohm C7770A 20K ohm C7041 20K ohm 5090 What Terminals are Wired to the Discharge Air Temperature Sensor None S1 S2 S3 S4 None Both Yes Wired Sensors requires an EIM Equipment Interface Module 5100 Discharge Air Temperature Sensor...

Page 50: ...upied The Dry Contact device is closed when the room is occupied and will open when the room is unoccupied 6030 Remote Setback Time Delay from Occupied to Unoccupied 0 to 30 minutes in 5 minute increments 0 minutes Commercial Yes Remote Setback requires an EIM Equipment Interface Module The Remote Setback Time Delay forces the thermostat to wait before it switches from Occupied to Standby temperat...

Page 51: ...ule Choose an option appropriate for the type of device installed Normally Open The Dry Contact device is normally open and will close when the device detects the drain pan is full Normally Closed The Dry Contact device is normally closed and will open when the device detects the drain pan is full 6070 What Terminals are Wired to the Dirty Filter Alert Dry Contact None S1 S2 S3 S4 None Both Yes Dr...

Page 52: ...lly Open The Dry Contact device is normally open and will close when the device is activated Normally Closed The Dry Contact device is normally closed and will open when the device is activated 6130 What Terminals are Wired to the Service Needed Alert Dry Contact None S1 S2 S3 S4 None Both Yes Dry Contact Alerts require an EIM Equipment Interface Module 6140 Service Needed Alert Dry Contact Setup ...

Page 53: ...odule Choose an option appropriate for the type of device installed Normally Open The Dry Contact device is normally open and will close when the device is activated Normally Closed The Dry Contact device is normally closed and will open when the device is activated 6190 Custom Alert Name View Edit Custom Alert View Edit Custom Alert Both Yes Dry Contact Alerts require an EIM Equipment Interface M...

Page 54: ...be used for Humidification Control Thermostat Internal Sensor Name Remote Sensor Name Remote Sensor Name Remote Sensor Name Remote Sensor Name Remote Sensor Name Remote Up to 6 Remote Sensors Thermostat Internal Both No Select a sensor to control humidification thermostat or an optional remote sensor If multiple sensors are installed you can use a different sensor for dehumidification control See ...

Page 55: ...allow humidification if the last call was for cool A discharge air temperature sensor is required to humidify in the Cool mode Off The thermostat will allow humidification when the system setting is Off See Set up Humidification beginning on page 102 8070 Humidification Control Humidify Only when Heat is On Humidify Only when Fan is On Humidify on Demand Thermostat Controls Fan Humidify on Demand ...

Page 56: ...or Dehumidification Commercial beginning on page 109 9010 Which Sensor will be used for Dehumidification Control Thermostat Internal Sensor Name Remote Sensor Name Remote Sensor Name Remote Sensor Name Remote Sensor Name Remote Sensor Name Remote Up to 6 Remote Sensors Thermostat Internal Both No Select a sensor to control dehumidification thermostat or an optional remote sensor If multiple sensor...

Page 57: ...Open when ISU 9000 Dehumidificati on Equipment is Hot Gas Bypass Both No Choose an option appropriate for the type of equipment installed Normally Open U1 U2 or U3 will normally be open and will close when the thermostat calls for dehumidification Normally Closed U1 U2 or U3 will normally be closed and will open when the thermostat calls for dehumidification Number of Universal Outputs THX9321 The...

Page 58: ...below the cooling setpoint until the desired humidity level is reached 9120 System Modes Allowing Dehumidification Check box on screen for each Heat Cool Off Cool Default varies based on heating cooling equipment selected Both No This ISU is only displayed when ISU 9000 Dehumidification Equipment is set to Dehumidifier Click boxes on screen to select which system modes allow dehumidification If a ...

Page 59: ...ation Equipment is None ISU 9190 to 9200 are only displayed when ISU 9180 Dehumidification Away Mode is Allowed See Dehumidification Away Mode beginning on page 107 9190 Dehumidification Away Mode Fan Control Automatic On Circulate Automatic Both No The On and Circulate settings may re introduce humidity into the living space 9200 Dehumidification Away Mode Low Limit Temperature Setting 70 F to 80...

Page 60: ... ISU 1010 Application is set to Residential Percent on Time is the only choice when ISU 1010 Application is set to Commercial Both No See Ventilation Control Methods ISU 10050 beginning on page 112 10060 Ventilation Fan Control Thermostat Controls Fan Equipment Controls Fan Thermostat Controls Fan Both No Thermostat Controls Fan The thermostat turns on the ventilation equipment and the fan when ve...

Page 61: ...Ventilation screen in the Menu ASHRAE is Priority ASHRAE requires additional ventilation following a long off cycle The thermostat meets the ASHRAE 62 2 ventilation standard by running additional ventilation when outdoor conditions are favorable If ASHRAE cannot be met when outdoor conditions are favorable the thermostat will override the outdoor lockouts and run ventilation When using this option...

Page 62: ...s NOT allowed to run during a call for humidification or dehumidification 10160 Ventilate on High Indoor Humidity Off On Heat Mode Only On Heat Mode Only Both No This ISU is only displayed when ISU 10000 Ventilation Type is set to ERV HRV Off The humidity level has no effect on ventilation On The thermostat removes excess humidity by turning on the ventilator when the indoor humidity rises 10 abov...

Page 63: ...f On On Both Yes This ISU is only displayed when the thermostat is setup for a Non Zoned Cooling System and the thermostat is setup for 10K Discharge and Return Air Sensors at ISU 5000 What Sensors are WIRED to your System This ISU is NOT displayed when the thermostat is setup for an Economizer ISU 2220 See Delta T Diagnostics beginning on page 87 13015 Set Advanced Delta T Diagnostic Options No Y...

Page 64: ... system ONLY when the indoor temperature is within a certain range Set to No Limit to monitor Delta T during all indoor temperature conditions 13050 Maximum Setting No Limit 40 F to 120 F in 5 F increments No Limit Always Both Yes 13060 Allow Heat Delta T Diagnostics when Indoor Humidity is Indoor Humidity Range Minimum Setting No Limit 0 to 95 in 5 increments No Limit Always Both Yes This ISU onl...

Page 65: ...y displayed when ISU 13015 Set Advanced Diagnostic Options is set to Yes The thermostat monitors Delta T of the system ONLY when the indoor humidity is within a certain range Set to No Limit to monitor Delta T during all indoor humidity conditions 13100 Maximum Setting No Limit 5 to 100 in 5 increments No Limit Always Both Yes 13110 Allow Backup Heat Delta T Diagnostics when Outdoor Temperature is...

Page 66: ... No Limit 5 to 100 in 5 increments No Limit Always Both Yes 13150 Allow Cool Delta T Diagnostics when Outdoor Temperature is Outdoor Temperature Range Minimum Setting No Limit 50 F to 135 F in 5 F increments No Limit Always Both Yes This ISU only applies to Cooling This ISU is only displayed when ISU 13015 Set Advanced Diagnostic Options is set to Yes The thermostat monitors Delta T of the system ...

Page 67: ...is entered into the log Yes The thermostat displays a Delta T alert to the user when a Delta T alert is entered into the log See Delta T Alerts beginning on page 90 14000 Clock Format 12 hour 24 hour 12 Both No 14010 Daylight Saving Time Off On On Both No Set to Off in areas that do not follow Daylight Saving Time 14020 Indoor Temperature Display Offset 3 F to 3 F in 1 F increments 0 F Both No 0 F...

Page 68: ...est to verify that the thermostat can communicate properly in the installed location The test measures the signal strength between the Thermostat and the Equipment Interface Module in non zoned applications Thermostat and the TrueZONE Wireless Adapter in zoned applications Accessing Installer Tests 1 Press MENU on the home screen then scroll down and press Installer Options 2 Enter the password da...

Page 69: ...rs The Discharge Return and Delta T are updated every 30 seconds during the test The Run Time counter starts over when the next stage is turned on Fig 62 3 Discharge Return and Delta T are updated every 30 seconds during the equipment test Fig 63 4 When that equipment test is complete press Next Test 5 When system testing is complete press Exit Test Using the Wireless Signal Strength Test 1 On the...

Page 70: ...or on a vertical exterior wall at least 6 inches below any overhang Choose a location protected from direct sunlight 2 Place sensor securely in bracket facing away from wall Fig 67 Mounting Outdoor Sensor MOUNTING C7089U1006 WIRED OUTDOOR TEMPERATURE SENSOR Use the following steps to mount the sensor 1 Remove the sensor from the mounting clip 2 Mark the area on the location selected for mounting t...

Page 71: ...arked positions then tap in supplied wall anchors 5 Place wallplate over anchors insert and tighten mount ing screws see Fig 71 Fig 71 Mount wallplate to wall 6 Replace the cover on the remote sensor Mounting Entry Exit Remote or Vent Boost Remote Mounting the remote is optional 1 Remove the front cover from the remote 2 Use provided screws and wall anchors to fasten the remote to the wall Drill 3...

Page 72: ...hows system mode heat cool outdoor temperature and humidity with optional outdoor sensor HOME Touch to display Home screen FAN Select fan mode SYSTEM Select system mode Heat Cool MENU Touch to display options Start here to set a program schedule Thermostat location Quickly identify which thermostat is in control of a specific area Current schedule Touch an arrow to change temperature setting and s...

Page 73: ...Fan runs randomly about 35 of the time residential use only Follow Schedule Fan controlled by program NOTE In commercial use touch Automatic or On to tem porarily override the programmed fan schedule Setting system mode 1 Touch SYSTEM to display system settings Fig 80 2 Touch desired option Heat Thermostat controls only the heating system Cool Thermostat controls only the cooling system Off Heatin...

Page 74: ...he days to schedule touch Next 4 Touch Wake to set your Wake time for selected day s Fig 84 5 Touch or to set Heat and Cool temperatures for the Wake period then touch Done Fig 85 6 Touch other time periods Leave Return Sleep to set time and temperatures for each 7 Touch Done to save and exit NOTE Touch Delete Period to eliminate any unwanted time period NOTE Touch Fan Settings to customize fan se...

Page 75: ...t the temperature It will be maintained until the hold time you set Fig 87 To change the hold time touch the Hold Until arrow buttons This time can be adjusted up to the maximum time set by the installer Touch Override to use a pre set occupied temperature if a person uses the room during an unoccupied period The new temperature will be maintained for 1 hour and can be adjusted up to the maximum t...

Page 76: ...or further scheduling details including times of day temperature settings return date and return settings Fig 94 4 Review your selections on the last display and touch Done to save your settings Touch Back then Cancel to ignore the changes Fig 95 Setting holiday event schedules commercial use This feature helps you conserve energy when the workplace is unoccupied for special events and holidays 1 ...

Page 77: ...eek week of the month settings length of event and frequency of the event 4 Review the settings and touch Done to save them Touch Back then Cancel to ignore the changes Fig 102 Setting holiday schedule commercial use This feature lets you customize temperature settings to be maintained on specified national holidays The thermostat resumes normal scheduling between selected holidays 1 Select US Hol...

Page 78: ...ing Initiating occupancy mode commercial use This feature keeps temperature at an energy saving level until you touch Press to start occupancy When you arrive touch the button to maintain a comfortable temperature while the room is occupied Fig 110 Touch the or buttons to set the temperature or the Hold Until time The temperature is maintained until the time you set Temperature returns to an energ...

Page 79: ...nsation on your windows during cold outdoor temperatures poorly insulated windows require a lower Window Pro tection setting which will limit how much your humidifier can run 7 After you set the Window Protection setting check for frost condensation on your windows in the morning If frost condensation is present adjust the Window Protec tion setting to the next lowest number and check for frost co...

Page 80: ...t Ventilation Fig 118 2 Touch Setting then select Auto Ventilation runs as programmed by the installer Off Ventilation remains off unless turned on using the timer On Ventilation is always on 3 Touch or to run ventilation temporarily To turn it off set it to zero Fig 119 4 Touch More Settings to set maintenance reminders and lockouts Select Yes to prevent ventilation from running during the Sleep ...

Page 81: ...om screen color or touch Accept Color Selections if you are satisfied with your custom screen color Fig 124 7 Touch the arrows on the slider bars to adjust the color shading and brightness of the background color View changes in the Preview area at the top of the screen Touch Undo to restore the color you originally selected Touch Next when finished Fig 125 8 Touch the arrows on the slider bars to...

Page 82: ...hour clock display Backlight Language choice Scheduling options Adaptive Intelligent Recovery Restore default schedule Daylight saving time Fig 130 3 Touch Done to save your settings Touch Cancel to ignore changes Cleaning the thermostat screen When you select the Clean Screen option the screen is locked so you don t accidentally change settings while you clean 1 Touch MENU 2 Select Clean Screen A...

Page 83: ...nges Use the thermostat to set temporary schedule changes that impact the regular schedule for the heating cooling system This feature is useful if your daily schedule sometimes changes Select an option then follow screen prompts to conserve energy while you re away and maintain a comfortable climate after you return After the times you set the normal program schedule will resume Stay Home From Wo...

Page 84: ...Select the temperatures you would like to adjust based on the Utility Schedule Choose to create a cost saving schedule for the heating system the cooling system or both 4 When asked if you d like to enter the Utility Schedule now press Yes 5 Indicate how many different price levels the Utility Sched ule has then press Next At this and the following screens you can customize how the system operates...

Page 85: ...ouch Cancel to resume normal operation COMPRESSOR PROTECTION The thermostat keeps the compressor off for a few minutes before restarting to prevent equipment damage During this off time the message waiting for equipment is displayed on screen PRE OCCUPANCY PURGE COMMERCIAL USE ONLY This feature turns on the fan 1 to 3 hours before each occupied time period to provide a comfortable workplace when y...

Page 86: ...t was installed the thermostat Home screen will display humidity readings from only one sensor Fig 146 UNIVERSAL OUTPUTS U1 U2 U3 U1 U2 U3 are universal outputs that can be setup to control IAQ equipment and a stage of heating or cooling in the Installer Setup Setup options are listed below See THX9321 Thermostat Wiring Diagrams Using Universal Relays to Control Heating or Cooling beginning on pag...

Page 87: ... the log If configured to do so the system will then display an alert to the homeowner along with your contact information Before You Set Up Delta T Diagnostics Refer to the information below for tips on installation and setup of Delta T Diagnostics 1 Refer to Fig 10 14 for the placement of the Discharge and Return Air Sensors 2 In gas or oil forced air systems Delta T will continue to rise for se...

Page 88: ...eturn and Discharge Air Sensors by selecting the check boxes on the screen These sensors are used to measure Delta T Fig 148 2 Select the terminals that are wired to the Discharge and Return Air Sensors terminals S1 S2 S3 or S4 at the EIM IMPORTANT Be sure to select the correct terminals for the dis charge and return air sensors For example if the return air sensor is wired to S1 select S1 see Fig...

Page 89: ...o cooling and performance related issues that are typically caused by a dirty air filter blocked registers loss of refrigerant dirty a coil frozen a coil cracked heat exchanger dirty burners etc If You Decide to Set Up Diagnostics Later When you are ready to set up diagnostics follow these steps 1 From the Home screen press MENU 2 Scroll down and press Installer Options 3 Enter the passcode and pr...

Page 90: ...or humidity is within a certain range ISUs 13080 13120 13160 Default Always Default is Yes for Dehumidifiers and A C with High Speed Fan The thermostat does NOT allow Delta T diagnostics dur ing dehumidification if it is setup for A C with Low Speed Fan Hot Gas Bypass or Reheat The Delta T Alert Sensitivity is set on a scale of 1 5 in ISU 13180 1 is the least sensitive 5 is the most sensitive By d...

Page 91: ... Alerts and Utility Saver Switches For systems that might be interrupted by a utility saver switch conventional cooling and heat pumps in the heat and cool mode the thermostat will ask if a utility saver switch is installed and provide an option to the user to turn off diagnostics temporarily while power is interrupted by the utility company Diagnostics can be turned off for 1 14 days Fig 162 Fig ...

Page 92: ...r This allows the service technician to dismiss alerts for problems that have been corrected and prevent unnecessary callbacks Fig 164 The Alerts Log contains information about the alert and system information See Fig 165 170 as an example Fig 165 Fig 166 Fig 167 Fig 168 Fig 169 Fig 170 The Alerts Log can include The alert name and description System details at the time of the alert Delta T thermo...

Page 93: ...un Time by Equipment Type Indoor and Outdoor Conditions Log Fig 171 The Performance Log records the following information Minimum and Maximum Delta T Minimum and Maximum Discharge Temperature Minimum and Maximum Return Temperature Minimum and Maximum Outdoor Temperature and Humidity Minimum and Maximum Indoor Temperature and Humidity Run Time of Heating and Cooling per stage Fig 172 You have the o...

Page 94: ...ns Log Fig 174 2 Press Previous Day or Next Day to view user interactions by date 3 Press Search by Event to search for specific user inter actions Fig 175 4 Select the desired user interactions and press Done Using the Performance Logs 1 Follow the steps in Using the Data Logs on page 94 Press Performance Logs Fig 176 2 Select the desired log to view performance history Fig 177 3 For example the ...

Page 95: ...itional run time data Fig 180 TO SAVE A DATA LOG TO A MEMORY STICK 1 Insert memory stick in thermostat USB port 2 The USB options will be displayed Fig 181 3 Press Data Logs 4 Select the log you want to save to USB Fig 182 5 When you insert the memory stick into a computer you can view the data logs in a spreadsheet ADVANCED DATA LOG OPTIONS You can turn the Data Logs off or Reset them from this s...

Page 96: ... provides an alert to the user Fan Failure Alert The Fan Failure Alert protects the equipment when there is no airflow When the dry contact device for example sail switch detects no air flow for 5 minutes after a call for forced air heat cool or fan the thermostat provides an alert to the user indicating that the system was shut down due to a lack of airflow The thermostat will call for the fan an...

Page 97: ...me after you enter it Fig 190 7 Type the custom alert message into the text box and press Done The custom alert message appears when the orange alert button is pressed See Fig 191 You can edit or confirm the alert message after you enter it Fig 191 8 Repeat steps 4 5 for the other Dry Contact if necessary Staging Control Differential Between All Stages The thermostat provides Differential settings...

Page 98: ...l is set to 2 F or higher backup heat is not used unless the indoor temperature drops to the Backup Heat Differential setting or the Backup Heat Upstage Timer expires whichever occurs first The upstage timer starts when the highest stage of the previous equipment type turns on MANUAL TEMPERATURE CHANGE When the Backup Heat Differential is set to Comfort the thermostat uses backup heat as needed to...

Page 99: ...drops to the Backup Heat Differential setting or the Backup Heat Upstage Timer expires whichever occurs first The upstage timer starts when the highest stage of the previous equipment type turns on Backup Heat Upstage Timer options are Off 30 minutes to 16 hours Default is Off Fig 196 Multistage Control Multistage Control keeps the high stage of the equipment running until the desired setpoint is ...

Page 100: ...ant Heat and Geothermal Forced Air Heat stay on when the Backup Heat turns on EMERGENCY HEAT MODE The thermostat turns on the Backup Heat to maintain the desired temperature setting Geothermal Radiant Heat and Geothermal Forced Air Heat are not used Table 8 Heat Pump and Backup Heat Operation Backup Heat Type Backup Heat Operation Backup Heat Fan Operation Electric forced air Allowed to run with h...

Page 101: ...at turns on the Backup Heat to maintain the desired temperature setting Geothermal Radiant Heat and Geothermal Forced Air Heat are not used Set Up Geothermal Radiant Heat 1 Select Geothermal Radiant Heat as shown in Fig 199 Fig 199 2 Select the number of Radiant Heat Stages See Fig 200 Fig 200 3 Select the universal terminals wired to the Geothermal Radiant Heat See Fig 201 Fig 201 4 Select the Ge...

Page 102: ... Limit The thermostat may turn off the humidifier before the desired humidity setting is reached The Window Limit is based on the current outdoor temperature and the user s window protection setting To adjust the Window Protection setting press More Settings from the Humidification screen Window Protection is set on a scale from 1 10 A setting of 1 represents poorly insulated windows and a setting...

Page 103: ...ast call was for heat Cool includes Cool and Auto If the system is in Auto mode the thermostat will allow humidifica tion if the last call was for cool A discharge sensor is required to humidify in the Cool mode The thermostat prevents con densation in the duct work by not allowing the humidifier to run when the discharge tempera ture goes below the dew point temperature The humidifier is allowed ...

Page 104: ...r humidifier can run 7 After you set the Window Protection setting check for frost condensation on your windows in the morning If frost condensation is present adjust the Window Protec tion setting to the next lowest number and check for frost condensation on your windows the next morning Con tinue to adjust the Window Protection setting to a lower number until frost condensation is no longer pres...

Page 105: ... system to reduce humidity by lowering the temperature up to 3 F below the current cool setpoint until the desired humidity level is reached If set for A C with Low Speed Fan configure U1 U2 or U3 as normally open or normally closed ISU 9050 and wire to the Low Speed Fan terminal on the equipment For example if the U1 U2 or U3 terminal is normally closed it will open when the thermostat calls for ...

Page 106: ...unit for dehumidification The thermostat can be set to control dehumidification in all modes Heat Off Cool ISU 9120 Set up Dehumidification With Whole House Dehumidifier Some screens shown in this section may not appear on the thermostat depending on how you set up dehumidification 1 Select the Dehumidification Equipment in ISU 9000 See Fig 222 Fig 222 2 If optional remote wireless indoor sensors ...

Page 107: ...r and the fan when dehumidification is needed Equipment Controls Fan Thermostat turns on the dehumidifier when dehumidification is needed The fan is controlled by the equipment Fig 227 7 Set the desired lockout option See Fig 228 Fig 228 NOTE ISU 10140 gives the option to lockout ventila tion during calls for dehumidification This helps maintain the desired humidity level Dehumidification Away Mod...

Page 108: ...refer then press DONE The dehumidification setting range is 40 80 in 5 increments NOTE When set for A C with Low Speed Fan or A C with High Speed Fan an overcooling limit can be set from 0 F to 3 F ISU 9070 The ther mostat uses the cooling system to reduce humidity by lowering the temperature up to 3 F below the current cool setpoint until the desired humidity level is reached 5 Press MORE SETTING...

Page 109: ...quipment is cycled on The compressor will run for the minimum on time you set until the desired humidity level is reached High Humidity Comfort Reset ISU 9100 This option uses the cooling system to lower the temperature up to 5 F below the current cool setpoint until the desired humidity is reached The high humidity comfort range is from 1 to 5 F High Humidity Comfort Reset with Minimum On Time IS...

Page 110: ...U3 terminals are Normally Open or Normally Closed See Fig 239 Normally Open contacts are normally open and will close during a call for dehumidification Normally Closed contacts are normally closed and will open during a call for dehumidification Fig 239 6 Set the Dehumidification Control See Fig 240 For more information about these options see Dehumidification using the Cooling System on page 109...

Page 111: ...he Dehumidifier See Fig 244 Fig 244 5 Select the system mode s to allow dehumidification See Fig 245 NOTE Heat includes Heat Emergency Heat and Auto If the system is in Auto mode the thermostat will allow dehumidification if the last call was for heat Cool includes Cool and Auto If the system is in Auto mode the thermostat will allow dehumidifi cation if the last call was for cool Fig 245 6 Set De...

Page 112: ...to operate in the same system mode Heat Cool Off and you are sensing humidity from two differ ent locations using a remote wireless indoor sen sor for example main level and crawl space the thermostat will allow humidification and dehumid ification to operate at the same time and there is no deadband between humidification and dehu midification settings Ventilation The thermostat can be set for th...

Page 113: ...ntilation during the Sleep or Unoccupied program periods is not an option when you select ASHRAE is Priority Ventilation Outdoor Condition Lockouts ISU 10130 Ventilation will not operate when outdoor conditions exceed the lockout settings unless you manually call for ventilation or Ventilation Priority ISU 10125 is set to ASHRAE is Priority and ventilation is needed to meet ASHRAE Lockouts can pre...

Page 114: ...i ority on lockouts versus the ASHRAE 62 2 ventilation standard The thermostat will not run ventilation dur ing the following lockout conditions if configured unless you manually call for ventilation 1 Lockout Ventilation during Outdoor Conditions ISU 10130 2 Lockout Ventilation on Humidification or Dehu midification Calls ISU 10140 3 Lockout Ventilation during Sleep Residential or Unoccupied Comm...

Page 115: ...lockout ventilation on humidification or dehumidification calls This feature is used to help reach the user s desired humidity level by not allowing the ven tilation equipment to run during a call for humidification or dehumidification The thermostat will indicate whether this meets or may not meet the ASHRAE 62 2 Standard or the Percent On Time setting See Fig 257 NOTE ISU 10140 Lockout Ventilati...

Page 116: ...displayed if a steam humidifier has been installed Some screens shown in this section may be different from those on the thermostat depending on how you set up IAQ equipment 1 Press MENU then scroll to select Preferences 2 Press Reminders Fig 259 is displayed Fig 259 3 Select the reminder you want to set 4 Press or to set the timer length Ranges incre ments and units will change based on the remin...

Page 117: ...rvice Reminder based on Outdoor Temperature 1 Press Add Custom Reminder see Fig 261 2 Press Fall Service Reminder and press Next Fig 262 3 Press Outdoor Temperature and press Next Fig 263 4 Press the up or down arrows to set the temperature and press Next A seasonal maintenance reminder will appear when the outdoor temperature reaches the level you select after a specified date Fig 264 5 Press the...

Page 118: ...Press Add Custom Reminder see Fig 261 2 Press New Custom Reminder and press Next Fig 268 3 Type the name of the reminder and press Done Fig 269 4 Type the reminder message and press Done Fig 270 5 Press the up or down arrows to set the date when the New Custom Reminder should appear and press Next Fig 271 6 Select how often you want the reminder to appear and press Next Fig 272 ...

Page 119: ...ividually to the thermostat Installer Setup Dealer Information Holiday Event Scheduler commercial Holidays Custom Events Custom Reminders Software Update You can also save Data Logs to a memory stick and view information in a spreadsheet on your computer See To save a Data Log to a memory stick beginning on page 95 Alerts Log User Interactions Log Performance Logs To display USB options insert a m...

Page 120: ...save the file For example if your USB device is letter F navigate to My Computer and then drive F 7 After the file is saved remove the USB device from the computer and connect it to the thermostat See Fig 276 Then select the Dealer Information option on the ther mostat Updating Thermostat Software Prestige IAQ Only New thermostat software can be saved to a USB drive and then uploaded to the Presti...

Page 121: ...set Fig 279 To change the hold time touch the Hold Until arrow buttons This time can be adjusted up to the maximum time set by the installer Touch Override to use a pre set occupied temperature if a person uses the room during an unoccupied period The new temperature will be maintained for 1 hour and can be adjusted up to the maximum time set by the installer Fig 280 The programmed schedule will r...

Page 122: ...week week of the month settings length of event and frequency of the event 4 Review the settings and touch Done to save them Touch Back then Cancel to ignore the changes Fig 287 Setting holiday schedule commercial use This feature lets you customize temperature settings to be maintained on specified national holidays The thermostat resumes normal scheduling between selected holidays 1 Select US Ho...

Page 123: ...u pied program setting Initiating occupancy mode commercial use This feature keeps temperature at an energy saving level until you touch Press to start occupancy When you arrive touch the button to maintain a comfortable temperature while the room is occupied Fig 295 Touch the or buttons to set the temperature or the Hold Until time The temperature is maintained until the time you set Temperature ...

Page 124: ...The thermostat allows you to do REMOTE SETBACK when set up for commercial use This feature requires an occupancy sensor connected to the S1 S2 S3 or S4 terminals at the EIM During occupied periods the sensor tells the thermostat to go to STANDBY setback settings when no one is in the room If someone is in the room then it follows the settings of the occupied period The occupancy sensor is ignored ...

Page 125: ...e when the room is unoccupied Normally Closed when Occupied The Dry Con tact device is closed when the room is occupied and will open when the room is unoccupied Fig 302 4 Select a Remote Setback Time Delay The Remote Set back Time Delay forces the thermostat to wait before it switches from occupied settings to the standby settings When set to 0 minutes the thermostat will switch from occupied set...

Page 126: ...mostat modes The Economizer Module and Time of Day output connect to the A L A terminal at the thermostat or EIM and are set up at ISU 2220 Fig 305 Pre Occupancy Purge The thermostat can be set up for Pre Occupancy Purge in the installer setup ISU 4010 When setup for Pre Occupancy Purge the thermostat runs the fan 1 to 3 hours before each occupied period to provide a comfortable workplace upon arr...

Page 127: ...glow amber for up to 20 seconds Please wait while the indoor sensor restores communication with the wireless network Wireless Outdoor Sensor Replace batteries in your outdoor sensor when a warning appears on the thermostat screen about two months before batteries are depleted After new batteries are installed the outdoor sensor will restore communication with the wireless network within a few seco...

Page 128: ...door Sensors REDLINK INTERNET GATEWAY The Honeywell RedLINK Internet Gateway gives you remote access to your Prestige thermostat from the web smart phone or tablet You can view or adjust indoor temperature system mode and other settings The Gateway can also send alerts to as many as 6 email addresses to notify you if a problem occurs WIRELESS ENTRY EXIT REMOTE This device mounts beside your door f...

Page 129: ...mostat Fig 308 Reading temperature at the Portable Comfort Control If the thermostat is being averaged with remote indoor sensors and you select THERMOSTAT on the Portable Comfort Control you will see the temperature average from the remote indoor sensors and the thermostat NOTE If the thermostat is not part of the temperature average then you will only see the temperature average from the remote ...

Page 130: ...Sensor The wireless indoor sensor senses temperature and humidity in remote locations and communicates that information wirelessly to the thermostat The indoor sensor can be used to do the following Maintain a more consistent temperature throughout the building by averaging temperatures Temperatures from all sensors including the thermostat are weighted equally Relocate sensing location thermostat...

Page 131: ...mperature control In Fig 313 the temperature reading is the average of the thermostat internal sensor and the MAIN LEVEL remote sensor Fig 313 Humidity Display If you are sensing Humidity from one location internal or remote the humidity reading displayed on the home screen is from the sensor that is being used for control In Fig 314 the humidity reading is from the Main Level Remote Sensor Fig 31...

Page 132: ... are sensing Humidity from two separate locations one for humidification and another for dehumidification you can select which humidity reading to display on the home screen In Fig 315 the humidity reading is from the Main Level Remote Sensor based on the setting in ISU Fig 315 ...

Page 133: ...2 2 47092 82 27 8 9020 12 11 1 44732 84 28 9 8659 14 10 0 42506 86 30 0 8315 16 8 9 40394 88 31 1 7986 18 7 8 38400 90 32 2 7672 20 6 7 36519 92 33 3 7372 22 5 6 34743 94 34 4 7086 24 4 4 33063 96 35 6 6813 26 3 3 31475 98 36 7 6551 28 2 2 29975 100 37 8 6301 30 1 1 28558 102 38 9 6062 32 0 0 27219 104 40 0 5834 34 1 1 25949 106 41 1 5614 36 2 2 24749 108 42 2 5404 38 3 3 23613 110 43 3 5203 40 4 ...

Page 134: ...d hold the blank space or arrow in the lower right hand corner of the screen until the display changes hold for about 4 seconds Fig 316 2 Press REMOVE then YES to disconnect from the old thermostats 3 To reconnect the thermostat go to Linking RedLINK Accessories beginning on page 16 At the Indoor Sensor RedLINK Internet Gateway Entry Exit Remote Vent Filter Boost Remote or TrueSTEAM Wireless Adapt...

Page 135: ... 1 Emergency Heat Stage 1 W3 Heat Stage 3 AUX 2 Backup Heat Stage 2 Emergency Heat Stage 2 Y Compressor Stage 1 Y Compressor Stage 1 Y2 Compressor Stage 2 Y2 Compressor Stage 2 G Fan Relay G Fan Relay A Connect to Economizer Module or Lighting Panel TOD L A Connect to Compressor Monitor Zone Panel Economizer Module or Lighting Panel TOD U1 U1 U2 U2 U3 U3 Universal relay for humidification dehumidi...

Page 136: ...k under the loosened screw See Fig 317 3 Securely tighten each screw 4 Push excess wire back into the hole 5 Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat 6 See Fig 319 327 for typical wiring hookups Table 14 THX9321 Terminal Designation Descriptions Conventional System Heat Pump Terminal Description Terminal Description C Common wire from secondary sid...

Page 137: ...ot water fan coil with forced air furnace backup heat 333 Hot water radiant heat with backup heat single zone application 334 Hot water radiant heat with backup forced air heat Zoned with forced air zone panel and zone valves 335 Hot water radiant heat with backup forced air heat Zoned with forced air zone panel and hot water panel 336 Hot water fan coil with forced air furnace backup heat 337 Woo...

Page 138: ...oor sen sor discharge sensor return sensor dry contact device to display an alert or an occupancy sensor for remote setback 3 Remove jumper s if using separate transformers 4 See Economizer Module Wiring Diagrams beginning on page 151 5 Connect wireless adapter to ABCD for extended wireless range HEAT STAGE 1 HEAT STAGE 2 HEAT STAGE 3 FAN TO THERMOSTAT STATUS LEDS JUMPERS SENSORS CONV FURNACE R C ...

Page 139: ...upancy sensor for remote setback 3 L A terminal sends continuous output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD See Economizer Module Wiring Diagrams beginning on page 151 4 Connect wireless adapter to ABCD for extended wireless range CHANGEOVER VALVE BACKUP HEAT STAGE 1 FAN RELAY SENSORS TO THERMOSTAT HEAT PUMP AIR HANDLER TRANSFORMER 120 VAC 24 VAC COMPRES...

Page 140: ...TOD See Economizer Module Wiring Diagrams beginning on page 151 4 Wire a maximum of 4 sensors using the S1 S4 terminals S1 S4 terminals can be connected to an indoor sensor outdoor sen sor discharge sensor return sensor dry contact device to display an alert or an occupancy sensor for remote setback 5 Connect wireless adapter to ABCD for extended wireless range NOTE For setup and operation see Geo...

Page 141: ...othermal radiant heat You must install a field jumper if radiant heat is powered by system transformer Do NOT install a field jumper if radiant heat has its own transformer 5 Remove jumper if using separate transformers 6 Connect the THP9045 Wiresaver Module to the K terminal in heating cooling applications that do not have a common wire at the thermostat The K terminal cannot be used in heat only...

Page 142: ... dedicated terminals for Conventional Heat Stage 3 and Backup Heat Stage 2 for Heat Pumps Powering universal relay with system transformer THX9321 shown Fig 326 Prestige THX9321 powering universal relay with system transformer Powering universal relay with separate heating transformer THX9321 shown Fig 327 Prestige THX9321 powering universal relay with separate heating transformer 1 U1 U2 U3 termi...

Page 143: ...24 VAC 120 VAC T T R C ZONE VALVE TR TH END SWITCH 1 1 2 2 TRANSFORMER R IS JUMPERED TO RH 1 EIM W W2 W3 Y Y2 G A M31478 24 VAC 120 VAC R C SERIES 20 VALVE C R 5 B 4 W 6 1 TRANSFORMER REMOVE THE JUMPER FROM RH TO RC WHEN USED WITH AQ2000 SERIES PANEL 1 THERMOSTAT EIM RC RH W W2 W3 Y2 G M31479 24 VAC 120 VAC R C HOT WATER RELAY PANEL ZONE 1 RH W 1 O B AUX1 AUX2 O Y Y2 G R C L A TO THERMOSTAT THERMO...

Page 144: ...tall a field jumper if radiant heat is powered by system transformer Do NOT install a field jumper if radiant heat has its own transformer 3 L A terminal sends continuous output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD See Economizer Module Wiring Diagrams beginning on page 151 4 Y2 used with heat pumps that have 2 compressor stages NOTE For setup and operati...

Page 145: ... WITH A CALL FOR HEAT THE THERMOSTAT WILL ENERGIZE ONLY THE FAN WITH A CALL FOR STAGE 1 HEAT IF THE WOOD STOVE IS HOT HEAT COMES FROM THE FAN COIL IF THE WOOD STOVE IS COLD ONLY THE FAN RUNS THE THERMOSTAT WILL UPSTAGE TO THE FURNACE AS NEEDED TO MAINTAIN THE TEMPERATURE L TO THERMOSTAT THERMOSTAT EIM CONV FURNACE M31482 1 2 1 2 W W2 W3 W Y G R C THE BOILER IS CONTROLLING THE CIRCULATOR PUMP IN TH...

Page 146: ... air zone panel and zone valves TRANSFORMER 24 VAC 120 VAC M34526 ZONE VALVE TR TH END SWITCH C R W W2 W3 W Y G R C HZ311 HZ322 OR HZ432 ZONE PANELS COULD BE USED TO CONTROL A FORCED AIR FURNACE ZONED WITH DAMPERS THE BOILER IS CONTROLLING THE CIRCULATOR PUMP IN THIS DIAGRAM L TO THERMOSTAT THERMOSTAT EIM CONV ZONE 1 1 2 1 2 BOILER T T RELAY 3 1 ...

Page 147: ...G R C HZ311 HZ322 OR HZ432 ZONE PANELS COULD BE USED TO CONTROL A FORCED AIR FURNACE ZONED WITH DAMPERS AN AQ2000 SERIES HOT WATER ZONE PANEL OR OTHER RELAY BASED HOT WATER ZONE 3 PANEL COULD BE USED L TO THERMOSTAT THERMOSTAT EIM CONV ZONE 1 ZONE 1 1 2 1 2 RELAY 3 1 W W2 W3 W Y G R C CONFIGURE THE THERMOSTAT TO ENERGIZE THE FAN WITH A CALL FOR HEAT THE BOILER IS CONTROLLING THE CIRCULATOR PUMP IN...

Page 148: ...l sends continuous output when thermostat is set to EM HEAT mode except when set up for Economizer or TOD See Economizer Module Wiring Diagrams beginning on page 151 4 Y2 used with heat pumps that have 2 compressor stages NOTE In Fig 338 the thermostat will energize only the fan with a call for stage 1 heat If the wood stove is hot heat comes from the fan coil If the wood stove is cold only the fa...

Page 149: ...y to the low speed fan for dehumidification control at the equipment The EIM relay can be set to be normally open or normally closed in the thermostat installer setup POWERED HUMIDIFIER RH RC R C U3 U3 U2 U2 U1 U1 24 VAC 120 VAC 24 VAC 120 VAC 24 VAC 1 POWERED VENTILATOR RH RC R C 24 VAC U3 U3 U2 U2 U1 U1 24 VAC 120 VAC 24 VAC 120 VAC 1 POWERED DEHUMIDIFIER RH RC R C U3 U3 U2 U2 U1 U1 24 VAC 120 V...

Page 150: ...open dry contacts when set up for a stage of heating or cooling 2You must install a field jumper if the stage of heating or cooling is powered by the system transformer Do NOT install a field jumper if the stage of heating has its own transformer 1 2 U3 U3 U2 U2 U1 U1 120 VAC 24 VAC 24 VAC HEAT STAGE 3 COOL STAGE 3 COOL STAGE 4 OR GEOTHERMAL RADIANT HEAT RH RC R C TRANSFORMER ...

Page 151: ...minal AUX 2 is present only on the Equipment Interface Module 3 Connect the changeover valve from the roof top unit to the normally open contacts of an isolation relay to prevent feedback into the economizer module during defrost If this is not done when the system goes into defrost it will change the economizer into cooling mode due to the feedback and open the outside damper while in heating mod...

Page 152: ...installer setup ISU 2220 These terminals are powered by the cooling transformer Rc terminal 2 Terminal AUX 2 is present only on the Equipment Interface Module 3 Add a normally closed relay as shown to make the W7213 W7214 Economizer Module compatible with the thermostat The ther mostat energizes the A or L A terminal during Occupied Periods 120 VAC Y1 Y2 AUX AUX 2 G 24 VAC O OR B N 3 4 1 2 5 TR1 T...

Page 153: ...ing next to control contactors or near light dimming circuits electric motors or welding equipment Avoid poor wiring connections Avoid intermittent or missing building earth ground CAUTION Electrical Shock Hazard Can cause electrical shock or equipment damage Disconnect power supply before connecting wiring Wiring must comply with applicable codes ordinances and regulations 1 Wire C7089U1006 Outdo...

Page 154: ...intermittent or missing building earth ground CAUTION Electrical Shock Hazard Can cause electrical shock or equipment damage Disconnect power supply before connecting wiring Wiring 4 C7189U1005 sensors 10k ohm for temperature averaging network Select 10K in the Installer Setup ISU 5030 when using C7189U1005 sensor s Fig 351 Wiring 4 C7189U sensors Wiring 2 TR21 sensors 20k ohm and 1 TR21 A sensor ...

Page 155: ...FURNACE 4 4 1 5 5 2 2 2 CONNECT POWER THM4000R CONNECTED WIRELESS SETUP 1 3 3 1 PRESTIGE THERMOSTATS CAN BE POWERED BY ANY TRANSFORMER IN THIS EXAMPLE THEY ARE POWERED BY THE SAME TRANSFORMER THAT POWERS THE HZ432 THERE CAN BE UP TO 4 PRESTIGE THERMOSTATS USED WITH A SINGLE THM4000R WIRELESS ADAPTER AND HZ432 ZONE PANEL THE THM4000R CANNOT BE USED IF THERE ARE MORE THAN 4 ZONES IN THE SYSTEM RH RC...

Page 156: ... OT OT AZ1 AZ2 ZONE 4 DAMPER THERMOSTAT EQUIPMENT POWER SENSORS ACCESSORIES R C C7735A1000 DATS A B C D WIRELESS C R W W2 Y Y2 G FURNACE AFS 5 4 1 5 2 2 R C 1 4 3 3 1 A DEDICATED TRANSFORMER SHOULD POWER THE HZ432 IF A DIFFERENT TRANSFORMER IS USED TO POWER THE EIM THE JUMPER FROM R TO RH NEEDS TO BE REMOVED AND THE RH AND RC FROM EIM GETS WIRED TO R ON THE ZONE THAT THE EIM IS WIRED TO THE PRESTI...

Page 157: ... Dehumidifier Fan Control to Equipment Controls Fan RH RC W1 E W2 W3 Y1 Y2 G O B DS BK MCR31523 EQUIPMENT C R W Y G FURNACE TrueZONE PANEL PRESTIGE IAQ EIM ERV HRV INTERLOCK B G R AUX W B G R 2 2 1 1 SELECT THE TERMINALS WIRED TO THE VENTILATOR AT ISU 10020 U1 U2 U3 TO VENTILATE IN ALL ZONES SET ISU 10060 VENTILATION FAN CONTROL TO EQUIPMENT CONTROLS FAN FOR ALL ZONE PANEL WIRING NOT SHOWN IN THIS...

Page 158: ...Prestige IAQ thermostats or wireless FocusPRO thermostats with an HZ322 or up to four 2 wire Prestige IAQ thermostats or wireless FocusPRO thermostats with an HZ432 HZ432 with a TAZ 4 add a zone You cannot use a wireless adapter when a TAZ 4 is used Each 2 wire Prestige IAQ thermostat used would need a separate THM5421R Equipment Interface Module The equipment interface module would wire to the zo...

Page 159: ...ed to provide a separation distance of at least 20 cm from all persons and must not be co located or operating in conjunction with any other antenna or transmitter Portable Comfort Control This portable transmitter with its antenna complies with FCC and Industry Canada RF exposure limits for general population uncontrolled exposure This device must not be co located or operating in conjunction wit...

Page 160: ...WITH EIM Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 68 0311 02 M S Rev 04 13 Printed in United States ...

Reviews: