background image

PRODUCT DATA

68-0145EF

® U.S. Registered Trademark
Copyright © 2001 Honeywell •  All Rights Reserved 

T410A,B

 Electric Heat Thermostats

GENERAL

The T410A,B Electric Heat Thermostats provide line voltage 

control of electric heating equipment. Snap-action switch 

makes heating circuit on temperature fall.

SPECIFICATIONS

IMPORTANT

The Specifications given in this publication do not 

include normal manufacturing tolerances. Therefore, 

this unit may not exactly match the listed specifica-

tions. Also, this product is tested and calibrated 

under closely controlled conditions, and some minor 

differences in performance can be expected if those 

conditions are changed. For exact engineering spec-

ifications, contact your Honeywell sales representa-

tive.

FEATURES

• Energy efficient and economical.
• UL listed up to 5 kW at 277 Vac.
• ncludes long-lasting Micro Switch™ mechanism.
• Rugged, plastic mounting base one-piece cover.
• Contemporary white finish complements any decor.
• Replaces virtually any wall-mounted electric heating 

thermostat.

Models:

T410A Electric Heating Thermostat: Spst switching heating 

circuit makes on temperature fall.

T410B Electric Heating Thermostat: Dpst switching; makes 

double line break with setting dial at OFF position; heating 

circuit makes on temperature fall.

Electrical Ratings (Noninductive Resistive Rating):

22A at 120/208/240 Vac; 19A at 277 Vac.

Wiring Connections:

6 in. (150 mm) copper leadwires, suitable for connecting to 

aluminum wiring if approved CO/ALR solderless wire con-

nectors are used.

Sensing Element:

Bimetal.

Setpoint Adjustment:

Setting dial on the face of the thermostat.

Temperature Range:

40° to 80°F (5° to 25°C).

Summary of Contents for T410A

Page 1: ...ell sales representa tive FEATURES Energy efficient and economical UL listed up to 5 kW at 277 Vac ncludes long lasting Micro Switch mechanism Rugged plastic mounting base one piece cover Contemporary white finish complements any decor Replaces virtually any wall mounted electric heating thermostat Models T410A Electric Heating Thermostat Spst switching heating circuit makes on temperature fall T4...

Page 2: ...Cover Assembly Includes locking cover screws Tinnerman clips wrench and range stops two plastic pins to insert inside cover for field selec tion of minimum and maximum temperature settings Fig 1 T410 approximate dimensions in in mm MERCURY NOTICE If this control is replacing a control that contains mercury in a sealed tube do not place your old control in the trash Dispose of properly Contact your...

Page 3: ...end and push solid wires into the outlet box 6 Remove thermostat cover by grasping the top and bot tom cover edge and pulling it outward away from the thermostat base 7 Turn the temperature setting dial so the setpoint indica tor is at the 12 o clock position to prevent damaging the dial stop 8 Mount the thermostat on the outlet box Tighten the two mounting screws included to secure the thermostat...

Page 4: ...ase 6 Turn the temperature setting dial so the setpoint indica tor is at the 12 o clock position to prevent damaging the dial stop 7 Mount the thermostat on the outlet box Tighten the two mounting screws included to secure the thermostat taking care to avoid excessive pressure on the setting dial See Fig 4 SETTINGS AND CHECKOUT Setting The thermostat temperature setting can be adjusted by turning ...

Page 5: ...présentant de Honeywell CARACTÉRISTIQUES Éconergétique et économique Répertorié UL jusqu à 5 kW sous 277 V c a Comporte un mécanisme Micro SwitchMC de longue durée Plaque de montage en plastique robuste couvercle monopièce Fini blanc contemporain s harmonisant à tous les décors Remplace presque tout thermostat mural pour chauffage électrique Modèles T410A Thermostat pour chauffage électrique commu...

Page 6: ...no E47434 guide no XAPX Certifié par l Association canadienne de normalisation CSA dossier no LR1322 Accessoire 272804A Jeu de butées d arrêt et de vis de verrouillage com prend des vis pour couvercle verrouillable des pinces Tin nerman une clé et des butées deux butées de plastique à insérer sous le couvercle pour sélectionner sur place les réglages minimal et maximal de la température Fig 1 Enco...

Page 7: ...fils et les insérer dans la boîte de sortie 6 Retirer le couvercle du thermostat en le tenant par les rebords supérieur et inférieur et en tirant vers soi en l éloignant de la base 7 Faire tourner le cadran de réglage du point de consigne jusqu à ce que l indicateur soit à la position midi 12 heures pour éviter d endommager les butées d arrêt du cadran 8 Installer le thermostat dans la boîte de so...

Page 8: ...ntihoraire le circuit de chauffage s ouvre et l appareil de chauffage cesse de fonctionner et com mence à refroidir Fig 5 Réglage du point de consigne MF5812B L1 SOUS TENSION L2 1 2 4 CONNECTEURS SANS SOUDURE ALIMENTATION FOURNIR AU BESOIN UN DISPOSITIF DE COUPURE ET UNE PROTECTION CONTRE LES SURCHARGES UTILISER DES CONNECTEURS SANS SOUDURE CO ALR POUR SERVICE SPÉCIAL LORSQUE LES CONDUCTEURS SONT ...