SPM Flex Gas Detector
Wiring and tubing
• The safety of any system incorporating the SPM Flex gas detector is
the responsibility of the assembler of the system�
• Position a permanently-installed SPM Flex gas detector so that it does
not interfere with access to the dedicated circuit breaker�
• Use only the specified power adaptor/charger (see
)�
• Use the power adaptor/charger only in indoor applications�
CAUTION
!
Do not wire relays and 4-20 mA in the same wire bundle�
NOTE
Typical fixed installation topologies
The SPM Flex gas detector has flexible installation options that allow the user to
select the one most suitable for a specific application� The detector is supplied
with weather-sealed connectors for power, Ethernet, and communications
(for relays or 4-20 mA)� The Ethernet port can be replaced with an appropriate
connection in accordance with local codes (allowing the user to wire directly to
the terminal block)� Install each detector near a dedicated circuit breaker�
This table shows the default wiring configuration for the IP-rated communication
connector when installed by Honeywell Analytics� The relays are labeled for the
factory default but the configuration can be modified to have a single alarm and
separate faults�
Relay/mA Terminal Connections
Front View
No.
Color
Relay/mA Terminal Connections
mA Sink
mA Source Isolated mA*
1
2
3
5
4
6
7
8
1
Red
Alarm2 NO
Alarm2 NO
Alarm2 NO
2
Black
Alarm2 COM Alarm2 COM Alarm2 COM
3
White
Alarm1 NO
Alarm1 NO
Alarm1 NO
4
Green
Alarm1 COM Alarm1 COM Alarm1 COM
5
Brown
Fault NO
Fault NO
Fault NO
6
Blue
Fault COM
Fault COM
Fault COM
7
Yellow
24 VDC +
4-20 mA -
4-20 mA -
8 White/Black 4-20 mA +
24 VDC -
4-20 mA +
*default pin configuration
Electrical connection is made via conduit directly to ports or via the connector
(see Figure 1,
“Connectors and ports” on page 10
� The terminals used are
suitable for conductors of 20 to 14 AWG (0�8 to 1�6 mm dia�)�
Summary of Contents for SPM Flex
Page 1: ...SPM Flex Single Point Monitor Gas Detector User Manual ...
Page 2: ......
Page 27: ...27 SPM Flex Gas Detector Setup Installation drawing Figure 18 Installation drawing ...
Page 70: ...70 SPM Flex Gas Detector ...
Page 73: ......
Page 74: ......
Page 75: ......
Page 76: ...SPM Flex Gas Detector User Manual 1998M0845 Revision 07 October 2016 2016 Honeywell Analytics ...
Page 77: ......