RMA803 Remote Indicator User's Guide
22
4.3.6
Standard Display Abbreviations:
Table 6: The Standard Display abbreviations
The abbreviations will be seen during configuration or any alarm conditions.
Abbreviation
Meaning
Recommended action
Wrt Prtd
“Write Protected”
Device is in write protect mode
Change the mode to un protected and
then configure the device
Not Sprtd
“Not Supported”
Parameter is Not supported
The configuration is not supported. No
action.
Hi LMT
“High Limit”
Parameter Value is greater than
high limit value
Choose correct parameter value.
Low LMT
“Low Limit”
Parameter Value is less than low
limit value
Choose correct parameter value.
BAD-Tx
“Bad Transmitter”
Transmitter is in critical condition
Transmitter in critical fault. Correct the
transmitter.
LKNWNGD
“Last known good value”
Information only. It shows the last
measured good value when DE mode is
switched for Digital to analog. Please
note on a Digital to analog DE mode
change, power cycle is needed for the
mode change to be effective.
O/P Mode
“Output Mode”
Device is in Output mode.
This is applicable for DE digital mode
only. See section 6 “Calibration” for
more details.
RAM ERR
“Random Access Memory Error”
RAM corrupt
Hardware is faulty. Replace the
hardware
ROM ERR
“Random Access Memory Error”
ROM corrupt
Hardware is faulty. Replace the
hardware
FLW FLT
“Flow Fault”
Code Flow fault
Hardware is faulty. Replace the
hardware
RAM CRC
“RAM Cyclic Redundancy Check”
RAM CRC failure
Hardware is faulty. Replace the
hardware
BRW RST
“Brown out reset”
Power fluctuation is detected. To
recover, navigate to ‘RMA DG’ menu
and exit from Menu or power cycle the
device.
NVM ERR
“Non-Volatile Memory Error”
NVM corrupt
Hardware is faulty. Replace the
hardware
VCC FLT
“VCC Fault”
Power supply fault
Power cycle the device or replace the
hardware
SAT-LOW
“Saturation High”
PV Value is in low saturation
condition
If the loop current value falls below 3.81
mA, Low saturation status is set. This is
an information only.
SAT-HI
“Saturation Low”
PV Value is in high saturation
condition
. If the loop current value is above 20.49
mA, High saturation status is set. This is
an information only.
NO ERR
No error
Information only
For notes saturation refer to section
7.3.2
Summary of Contents for SmartLine RMA801
Page 2: ......
Page 11: ......
Page 50: ...39 RMA803 Remote Indicator User s Guide Revision 2 ...
Page 51: ...Revision 2 RMA803 Remote Indicator User s Guide 40 ...
Page 52: ...41 RMA803 Remote Indicator User s Guide Revision 2 ...
Page 57: ...Revision 2 RMA803 Remote Indicator User s Guide 46 Control Drawing 50089981 ...
Page 58: ...47 RMA803 Remote Indicator User s Guide Revision 2 ...
Page 59: ...Revision 2 RMA803 Remote Indicator User s Guide 48 ...