C
OMMISSIONING
Honeywell
• 62
6
6.3.2
Frames MR7 and MR8
Follow the procedure described above to modify the EMC protection of the drive of frames MR7
and MR8 to EMC-level C4.
Figure 53.
Figure 54.
1
Remove the main cover of the drive and locate the jumper.
MR8 only:
Push down
the grounding arm. See Figure 53.
2
MR7 and MR8:
Locate the EMC box under the cover. Remove the screws of the
box cover to expose the EMC-jumper. Detach the jumper and re-fix the box cover.