Commissioning
2. Remove the detector module of
Sensepoint XCL.
3. Configure the sink/source mode of
the detector. Refer to Current
Source/Sink Selection on page 17 on
details of how to do this.
4. Configure the required inhibit level
of the detector. Refer to section
Inhibit Level Selection on page 17 on
details of how to do this.
5. Check that all electrical connections
are terminated correctly according to
the connector terminal assignments
shown on 8 and 9.
6. Switch on the power supply to the
Sensepoint XCL.
a) For DC operation, use a voltmeter
set to measure DC voltage at the
detector. Check that the power
supply voltage between terminals
1 (+V) and 2 (0 V) is between 9 V
DC and 32 V DC for Modbus
versions and 11 V DC and 32 V
DC for analog versions.
b) For AC operation, use a voltmeter
set to measure AC voltage to
check that the power supply
voltage between terminals 1 and
2 is between 20 V AC and 27 V AC.
27