Installation
NOTE
Where possible, spur or ‘T’ connections should be avoided. Always
keep the spur connection as short as possible.
Cable Specification for Modbus Connection
Type
Cable Spec
Max Length
Modbus
0.5 mm
2
to 2.5 mm
2
twist pair shied cable
1000 m
Terminal Resistor
Connect a 120
Ω
, 0.25 W terminal resistor between the A and B
terminals at the end of the line.