MAN0905_Issue 7_07/17
Searchpoint Optima Plus with optional HART
®
output
Operating Instructions
2108M0550
93
Read these notes if the Honeywell MC Toolkit is being used to communicate with
Searchpoint Optima Plus.
Please be aware that in some cases the MC Toolkit will not display messages as detailed in these
instructions.
Several specific instances are given below: -
1. In section 12.7, “Calibrate the 4-20 mA Loop” the MC Toolkit will not display a message that data
is being collected between steps 6 and 7, and between steps 9 and 10.
2. In section 13.6 “Re-zero Searchpoint Optima Plus” the MC Toolkit will not display a message that data
is being collected during step 6.
3. In section 13.7 “Calibration” the MC Toolkit will not display a message that data is being collected
during steps 8 and 12.
The MC Toolkit will not display any punctuation in the software version, e.g. version 5.2 will be displayed as
version 52.
21. Appendix 3 – Special Notes for
Honeywell MC Toolkit Users