4.2 Cabling recommendations
The cable used should be appropriate for the hazardous area classification and meet local, national and
company regulations. The use of industrial grade, suitably armoured field cable is recommended.
For example, three-core copper cable, with screen (90% coverage) and suitable mechanical protection (e.g.
steel wire armour or conduit).
When using HART
®
communications, there are some additional considerations. In particular, low
capacitance cable should be used. Further detailed information can be found at the HART
®
Communication
Foundation’s website www.hartcomm.org.
4.3 Earth regimes
Any earthing regime employed must avoid earth loops.
The following information is provided to assist with proper earthing of Searchpoint Optima Plus: -
• Searchpoint Optima Plus has an earth wire (green and yellow) for connection to protective earth.
This is connected to the enclosure and isolated from the other wires. Maximum voltage between earth
and the other wires is 500 V.
• There is an earthing point on the outside of the Searchpoint Optima Plus enclosure for connection to
protective earth. Alternatively, an earth connection can be made via the mounting thread, e.g. to conduit,
a metal junction box, or a continuity plate in a plastic junction box.
• Searchpoint Optima Plus does not require an instrument earth connection.
4. Electrical Installation
Circuitry
Searchpoint Optima Plus Enclosure
Power, Signal and
Communications Wires
Earth Wire
(Green / Yellow)
RFI Protection
Filters
Protective Earth
Three options to connect to protective earth:-
1. Green / Yellow Earth wire
2. External Earth point
3. Mounting Thread