92
MAN0530 Issue 09 October 03
Searchline Excel
2104M0506
8.3.2 Receivers
Open-Path
UL approved
M20/0.75in. NPT or
M20/0.5in. NPT adaptor
IS Cable
Length 15m max.
DX100/DX100 (M) UL
Termination Unit
Class I Div 1
Groups B, C, D
(Tamb -25 to +40 C)
o
SHC1 Handheld
Interrogator
Class I Div 1
Groups B, C, D
(Tamb -50 to +40 C)
o
Receiver
Class I Div 1 Groups B, C, D
Class I Zone 1 AEx d IIB + H2
(Tamb -40 to +65 C)
o
Flexible conduit
- must conform with the relevant US
installation codes of practice
(see Control Drawing 2104E0045)
(customer supplied)
Cross-Duct
DX100/DX100 (M) UL
Termination Unit
Class I Div 1
Groups B, C, D
(Tamb -25 to +40 C)
o
SHC1 Handheld
Interrogator
Class I Div 1
Groups B, C, D
(Tamb -50 to +40 C)
o
Receiver
Class I Div 1 Groups B, C, D
Class I Zone 1 AEx d IIB + H2
(Tamb -40 to +65 C)
o
UL approved
M20/0.75in. NPT or
M20/0.5in. NPT adaptor
IS Cable
Length 15m max.
Solid conduit
-
must conform with the relevant US
installation codes of practice
(see Control Drawing 2104E0045)
(customer supplied)
8. CERTIFICATION
UL approved
M20/0.5in. NPT adaptor
Note: Later units
1
/
2
" NPT
threaded without adaptor
UL approved
M20/0.5in. NPT adaptor
Note: Later units
1
/
2
" NPT
threaded without adaptor
Conduit
seal
required
within 6"
often closure
(see OEM
details
for J/B)
Conduit
seal
required
within 6"
often closure
(see OEM
details
for J/B)
(see also "Electrical Insulation" Cross-Duct Section 4)