8. CERTIFICATION
8.4
CSA/FM
8.4.1 Transmitters
8.4.2 Receivers
CSA approved
M20/0.5in. NPT adaptor
IS Cable
Length 15m max.
DX100/DX100(M) CSA
Termination Unit
Class I Div 1
Groups B, C, D
(Tamb -55 to +40 C)
o
SHC1 Handheld
Interrogator
Class I Div 1
Groups B, C, D
(Tamb -55 to +40 C)
o
Receiver
Class I Div 1 Groups B, C, D
T5 and Exd IIC T5
(Tamb -40 to +65 C)
o
Flexible conduit
-
must conform with the relevant
Canadian installation codes of practice
(see Control Drawing 2104E0097)
(customer supplied)
CSA Transmitter:
Class 1 Div 1 Groups B, C & D T5
and Exd 11C T5 (Tamb -40 to -40 to +65
o
C)
FM Transmitter:
Class 1 Div 1, Groups B, C & D (-40 to -40 to +65
o
C)
CSA/FM approved
explosion proof
junction box
Conduit seal
required
(see OEM J/B details)
CSA approved
M20/
1
/
2
NPT threaded
without adaptor
Note: Later units
1
/
2
" NPT
threaded without adaptor
Flexible conduit (customer supplied) -
must conform with the relevant US and
Canadian installation codes of practice
(conduit seal required within 30" of transmitter)
CSA Receiver:
Class 1 Div 1 Groups B, C,
D, T5 & Exd 11C T5
(Tamb -40 to +65
o
C)
DX100/DX100(M) CSA/FM
Termination Unit Class
I
Div 1
Groups B, C, D (Tamb -40 to +65
o
C)
SHC1 Handheld
Interrogator CSA/FM
Class 1 Div 1
Groups B, C, D
(Tamb -40 to +65
o
C)
FM Receiver:
Class 1 Div 1
Groups
B, C & D
(-40 to +65
o
C)
CSA approved
M20/0.5in. NPT adaptor
Note: Later units
1
/
2
" NPT
threaded without adaptor Flexible conduit (customer supplied) -
must conform with the relevant US and
Canadian installation codes of practise
(conduit seal required within 30" of transmitter)
IS Cable
Length
15m max.
Conduit
seal
required
within
6" offence
(see OEM
J/B details)