MAN0530 Issue 09 October 03
Searchline Excel
2104M0506
where:
tttttttt
System type. The system type displayed is one of the following:
Display Text
System Type
Short Range
40m range system
Medium Range
120m range system
Long Range
200m range system
Duct Mount
0.5 - 5m range system
Note: It is not possible to change the system type. This is set during calibration and configuration of the
unit at the factory.
Path Length
The following message is displayed:
Path Length
nnnn
where:
nnnn
The path length in metres.
The following ranges of path length can be entered for the system types:
System Type
Minimum Range (m)
Maximum Range (m)
Step Size (m)
Short Range
5
40
1
Medium Range
20
120
1
Long Range
20
200
1
Duct Mount
0.5
5
0.1
Self Test
This starts the system self test process.
The following message is displayed:
Press Enter to
Perform checks
This message is displayed during the self test process after pressing
Enter
.
Processing Data
Please Wait
This message is displayed for three seconds at the end of a successful self test process.
Checks Passed
APPENDIX A - HANDHELD INTERROGATOR
>
>