SDC / DHC
Operation
EN2H-0221GE51 R0808
89
5.4.3 "Hot-water circuit" menu (DHW)
This menu contains all parameters required to program the
hot-water circuit, except the switch time programs.
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
Hot
water
Hot water at night
10°C to normal hot-water
temperature
40
OFF
No legionella protection OFF
Mon to
Sun
Legionella protection on
specified day of week
Legio
protect
ion day
Legionella
protection day
ALL Legionella
protection
every day
03 Legionella
protection time
00:00 ... 23:00 hours
02:00
04 Legionella
protection
temperature
10 °C to setting value of
parameter 06
65
1 Hot-water
circuit
temperature sensor
1
05
Transducer for hot-
water circuit
2 Hot-water
circuit
temperature controller
(thermostat)
06 Maximum
temperature limit
for hot water circuit
20°C to heat generator maximum
temperature
If parameter 07 = 7:
20 to 90°C.
In automatic mode, from hot-
water circuit minimum
temperature.
65