2.6 Safety precautions for EMC-compliant installation
Mains lines and sensor/data bus lines must be installed separate
from each other. A minimum of 2 cm space must be present
between the lines. It is permissible to cross lines.
x
a
b
y
ç
é
æ
a Mains 230 V AC
x 15 cm
b Data bus line 12 V AC
y 2 cm
For control devices with their own mains connection, separate
installation of mains and sensor/bus lines must absolutely be
ensured. If cable ducts are used, they are to be provided with cut-
off bridges.