Hydraulic Components
SDC / DHC
176 EN2H-0221GE51
R0808
Switch-on: Flow setpoint < (current room se heating limit
s 2 K)
Example:
Room setpoint = 22°C, heating limit setting = 2 K
Switch-off at flow setpoint 24°C (22°C + 2 K)
Switch-on at flow setpoint 26°C (22°C + 2 K + 2 K)
The SUMMER SWITCH-OFF function ("System Parameters"
menu, parameter 04) has priority over the HEATING LIMIT
function.
The FROST PROTECTION function ("System Parameters" menu,
parameter 05) has priority over the HEATING LIMIT function.
Boundary conditions