SDC / DHC
Operation
EN2H-0221GE51 R0808
97
Para-
meter
Designation
Setting range / Setting values
Factory
setting
Setting
11 Constant
tem-
perature setpoint
(only if output was
set to constant
regulator)
10 ... 95°C
20
12 Minimum
temperature limit
10°C to setting value of
parameter 13
20
13 Maximum
temperature limit
Setting value of parameter 12 to
Setting value of parameter 30 in
"Heat generator" menu (OEM
maximum limit)
75
14 Temperature
increase of heating
circuit
–5 ... 20 K
Mixed
heating
circuit = 4
15
Follow-up time of
pump
0 ... 60 min
5
OFF OFF
1 Functional
heating
16 Screed
function
2 Screed-drying
heating
17 Return
maximum
temperature limit
10 ... 90
°
C
90
18*
P part X
P
1 ... 50 %/K
2
19*
Sampling time T
s
1 ... 600 s
20
20*
I part T
n
1 ... 600 s
270
21*
Actuator runtime
10 ... 600 s
120
1 Continuous
control
signal in end position
1
22* Actuator
end
position function
2 Control
signal
suppressed at end
position (actuator de-
energised)
23
Room control C-
factor (SDW 30
only)
1 ... 100
8