Satellite XT R Version
6-14
Alarm 2 Relay
Allows the user to set the Alarm 2 Relay state.
Use the <set> key to enter.
The instrument will show the actual setting.
Deenergized / NO
Defines the Alarm 2 Relay to be deenergized (normally
open contact).
Press the cursor keys <up> or <down> to change.
Press the <set> key to confirm or <esc> to exit.
Energized / NC
Defines the Alarm 2 Relay to be energized (normally
closed contact).
Press the cursor keys <up> or <down> to change.
Press the <set> key to confirm or <esc> to exit.
Fault Relay
Allows the user to set the Fault Relay state.
Use the <set> key to enter.
The instrument will show the actual setting.
Deenergized / NO
Defines the Fault Relay to be deenergized (normally
open contact).
Press the cursor keys <up> or <down> to change.
Press the <set> key to confirm or <esc> to exit.
Energized / NC
Defines the Fault Relay to be energized (normally closed
contact).
Press the cursor keys <up> or <down> to change.
Press the <set> key to confirm or <esc> to exit.
s e l e c t :
2
o f 3
R E L A Y S T A T E
A L ARM 2 RE L A Y
s e l e c t :
1
o f
2
A L A R M 2 R E L A Y
DE ENERG I Z ED / NO
s e l e c t :
2
o f
2
A L A R M 2 R E L A Y
ENERG I Z ED / NC
s e l e c t :
3
o f 3
R E L A Y S T A T E
F AU L T RE L A Y
s e l e c t :
1
o f
2
F A U L T R E L A Y
DE ENERG I Z ED / NO
s e l e c t :
2
o f
2
F A U L T R E L A Y
ENERG I Z ED / NC
Configuration - Section 6