RTU Controller:
displays discharge air temperature
DischargeAir Temp
: displays discharge air temperature
Fan Status
: indicates the actual fan status when an
optional fan sensor has been installed
Outdoor Air Temp
: displays outside air temperature
Status Filter
: displays alarm when filter needs service
IMPORTANT
The Rooftop Unit Control settings can be modified
by pressing the ChngValue softkey and entering
the new values. In RapidZone all three settings
(occupied, standby and unoccupied) must be set to
the same value.
NOTES:
—
This screen displays heating stages or Mod
Heating and cooling stages or Mod Cooling
depending on the type of heating and cooling
being used.
—
Additional data for some items is available by
highlighting the item and pressing Select.
—
The mixed air temperature refers to the
temperature of the mixture of outside
(economizer) air and return air prior to being
heated or cooled. An economizer must be part of
the system for this to be displayed.
DATA POINT INFORMATION
Rooftop Unit Data
RTU Controller
: discharge air temperature
BuildngVw —> Rooftop Unit Data
Cooling Stages
: number of active cooling stages
BuildngVw —> Rooftop Unit Data
Discharge Temp
erature: discharge air temperature
BuildngVw —> Rooftop Unit Data
Duct Static Press
ure: duct static pressure
BuildngVw —> Rooftop Unit Data
—
press ChngValue to modify
Economizer Mixed Air
: temperature of the mixed air
(return air + outside air)
BuildngVw —> Rooftop Unit Data
—
press ChngValue to modify
Heating Stages
: number of active heating stages
BuildngVw —> Rooftop Unit Data
Mod Cooling
: cooling valve percentage open
BuildngVw —> Rooftop Unit Data
Mod Heating
: heating valve percentage open
BuildngVw —> Rooftop Unit Data
Outdoor Air Temp
erature: outdoor air temperature
BuildngVw —> Rooftop Unit Data—>RTU Controller
Status Filter
: displays alarm on dirty filter
BuildngVw —> Rooftop Unit Data—>RTU Controller