74-3450—2
6
Diagnostics
The Rooftop Unit Diagnostics screen provides a quick status
of critical system parameters.
Main—>BuildngVw—>Rooftop Unit Diagnostics
NOTES:
—
FanFailure appears only when monitoring a
system with a proof of air flow sensor.
—
EconoFailure appears only when the system has
an economizer.
—
Alarms feature will not be active unless the
system has an Excel 15A building manager.
Alarms
Use this screen to check for alarms and get information if an
alarm has occurred. Use Next and Prev to navigate through
the alarms. Use Ack to acknowledge alarms. Once an alarm
has been acknowledged it is no longer viewable via the
command display. Use Silence if the beep function is
activated.
To View Alarms
Press the Alarm softkey and enter the required password.
Main—>Alarms
Alarms are another diagnostic tool provided by RapidZone.
Critical system parameters are constantly monitored within
the RapidZone application. Any deviation outside of preset
limits will trigger an alarm. The RapidZone Command Display
indicates an active alarm by sounding an intermittent beep
and/or by flashing the !! indicator. Active alarms can be dis-
played by pressing the Alarms softkey.
NOTE: Once the conditions that triggered the alarm have
been cleared, a second alarm is issued with the orig-
inal text preceded by RTN (return to normal).
M18586A
Rooftop Unit Diagnostics
CoolFailure
EconoFailure
HeatFailure
LowStaticPAlm
FanFailure
!!
Schedule
-
Page Up
Page Down
Off
Off
Off
Off
Off
M18400
Alarm Details
Total # of Alarms = 39
<Object Name>
<Alarm Text>
<Additional Alarm Text>
Seq# 1 Of 39 Priority 1
Date/Time Aug/16/2000 10:30 AM
!!
Silence
Next
Prev
Ack