74-3450—2

Schedules

The RapidZone solution allows the user to define up to eight 

separate schedules that specify different periods throughout 

the day where temperatures in the assigned zones will be 

maintained at the occupied setpoint for comfort, or the unoc-

cupied setpoint for energy savings. Each of these schedules 

can be assigned to any single zone or combination of zones 

using the RapidZone software. Each RapidZone schedule 

consists of a normal daily schedule (Monday through Sunday) 

that allows the operating hours for each day to be separately 

defined. Each RapidZone schedule also provides for up to 

two temporary periods that can be programmed for unusual 

days where occupancy periods do not follow normal daily or 

special holiday hours, e.g. inventory or vacation times. 

Finally, each RapidZone schedule allows for the programming 

of up to three special days whose occupancy periods can be 

assigned to the various scheduled holidays throughout the 

year. Each of these components - daily, temporary and spe-

cial, are unique to the schedule being programmed and apply 

only to the zone(s) assigned to that schedule. Holidays are 

defined for, and available to, all schedules. Holidays may be 

assigned to include or exclude individual schedules as 

appropriate. 

The following is an illustration of the various components that 

make up a RapidZone schedule.

For more detailed information regarding schedules, refer to 

the XL15 Command Display Users Guide 74-2974.

To view or modify a schedule, from the Main screen select 

BuildngVw then Zone Data. Highlight the zone whose sched-

ule you want to view/modify and press the Schedule softkey.

M18581

DAYS

NORMAL 

OPERATING

HOURS

FOR ZONES

ASSIGNED TO 

SCHEDULE 1

(ZONES 1, 2 & 5)

SPECIAL

(OPTIONAL)

SPECIAL HOURS

THAT CAN BE

ASSIGNED TO

HOLIDAYS

TEMP

(OPTIONAL)

TEMPORARY

OPERATING

HOURS NOT 
ASSOCIATED

WITH HOLIDAYS

SCHEDULE 1

FOR

ZONES 1, 2 AND 5

MONDAY

TUESDAY

WEDNESDAY

THURSDAY

FRIDAY

SATURDAY

SUNDAY

Sp1
Sp2
Sp3

T1
T2

DAYS

NORMAL 

OPERATING

HOURS

FOR ZONES

ASSIGNED TO 

SCHEDULE 2

(ZONES 3, 4 & 6)

SPECIAL

(OPTIONAL)

SPECIAL HOURS

THAT CAN BE

ASSIGNED TO

HOLIDAYS

TEMP

(OPTIONAL)

TEMPORARY 

OPERATING

HOURS NOT 
ASSOCIATED

WITH HOLIDAYS

SCHEDULE 2

FOR

ZONES 3, 4 AND 6

Summary of Contents for S7760A

Page 1: ...or to configure and monitor your rooftop unit RTU and zone controllers For more information refer to the RapidZone Application Guide 74 3449 and the S7760A Command Display User Guide 74 2974 The command display is an easy way to make changes to the schedules and other configuration options after the Rapid Zone application is downloaded Room temperature setpoints occupancy schedules equip ment alar...

Page 2: ...display the override screen where you can set timed or continuous Occupied or Unoccupied override NOTES The Occupied setpoint defines the comfort level desired during periods when a given area or zone is in use The Unoccupied setpoint captures operational equipment and energy savings during periods when a given area or zone is not in use In zones with temperature sensor and setpoint adjustment the...

Page 3: ...ly temporary and spe cial are unique to the schedule being programmed and apply only to the zone s assigned to that schedule Holidays are defined for and available to all schedules Holidays may be assigned to include or exclude individual schedules as appropriate The following is an illustration of the various components that make up a RapidZone schedule For more detailed information regarding sch...

Page 4: ...values The Occ on line E1 indicates that RapidZone will control to the occupied setpoint from 7 00 AM until the next scheduled event E2 The Unocc on line E2 indicates that RapidZone will control to the unoccupied setpoint from 6 00 PM on UNCNFIG unconfigured indicates that no change occurs from the previously programmed event e g E2 NOTE The STNDBY is not used in the RapidZone applica tion and sho...

Page 5: ...ific Holiday and press the Select key to view or modify the start stop dates and select the special or daily occupancy hours that should be used M18308 SCHEDULE 1 Special_1 E1 08 00 AM OCC E2 01 00 PM UNOCC E3 02 00 PM UNCNFIG E4 08 00 PM UNCNFIG E5 09 00 PM UNCNFIG E6 11 00 PM UNCNFIG Apply NxtSpecial M18309 Applies to SCHEDULE 1 Holiday One Holiday Two Holiday Three Holiday Four Holiday Five Hol...

Page 6: ...ss the Alarm softkey and enter the required password Main Alarms Alarms are another diagnostic tool provided by RapidZone Critical system parameters are constantly monitored within the RapidZone application Any deviation outside of preset limits will trigger an alarm The RapidZone Command Display indicates an active alarm by sounding an intermittent beep and or by flashing the indicator Active ala...

Page 7: ...ion failure Input Network Failure Network communication failure Input Rem Poll Alarm Network communication failure FreezeStat Coil freeze protection is activated Refer to the RapidZone Application Guide 74 3449 for addi tional details Setting Changes Setup Use this screen to change the display settings or to turn on and off the alarm beep Main Settings Setup NOTE Be sure to press the Apply key to ...

Page 8: ...ys bypass damper position as a percent open Cooling Stages displays the number of cooling stages that are commanded on Econ Mixed Air displays mixed air temperature Control sensor displays mixed air temperature Control Setting displays mixed air setpoint see IMPORTANT below EPID Output displays economizer damper position as a percent open Fan Command displays the fan control output state Heating S...

Page 9: ...ixture of outside economizer air and return air prior to being heated or cooled An economizer must be part of the system for this to be displayed DATA POINT INFORMATION Rooftop Unit Data RTU Controller discharge air temperature BuildngVw Rooftop Unit Data Cooling Stages number of active cooling stages BuildngVw Rooftop Unit Data Discharge Temperature discharge air temperature BuildngVw Rooftop Uni...

Page 10: ...sure alarm status off no alarm BuildngVw Rooftop Unit Diagnostics Zone Data Room Temperature room temperature of selected zone BuildngVw Zone Data Zone Name Control Setting room temperature setpoint of selected zone BuildngVw Zone Data Zone Name press ChngValue to modify Occupancy Status indicates current setpoint Occupied or Unoccupied BuildngVw Zone Data Zone Name press Override to modify Operat...

Page 11: ...11 74 3450 2 ...

Page 12: ...74 3450 2 J H Rev 02 01 Copyright 2001 Honeywell All Rights Reserved www honeywell com Printed in U S A on recycled paper containing at least 10 post consumer paper fibers ...

Reviews: