RP470A AND B PNEUMATIC SELECTOR RELAYS 

NOTE:

  

When the system is other than copper or poly-
ethylene tubing, adapt as shown in Fig. 3. Some 

models provide parts for adapting. 

CONNECT

 1/4 IN.

 (6 MM)

 PLASTIC 

CONNECT

 1/4 IN.
(6 MM)

COPPER 

RP470A/B 

POST FOR 
5/32 IN. (4 MM) O.D. 
PLASTIC TUBING 

5/32 IN. (4 MM) 
O.D. PLASTIC 
TUBING CUT 
TO LENGTH 

5/32 IN. X 1/4 IN. 
(4 MM X 6 MM) 

O.D. PLASTIC

 CONNECTOR 
(CCTI606B) 

1/4 IN. (6 MM) 
O.D. PLASTIC 
TUBING CUT TO
 LENGTH 

1/4 IN. (4 MM) O.D. 
PLASTIC/COPPER 
ADAPTER 
(CCTI633BT) 

1/4 IN. (6 MM) O.D. 
COPPER TUBING 

C8235 

Fig. 3. Adaptation piping. 

Port Identification Tables 

The following tables identify ports of older Honeywell 

pneumatic relays when upgrading installation. Refer to 
Tables 1 and 2. 

Table 1. RP470A Connections for a Higher-of-Two 

Pressures Application. 

RP470A  RP405A  RP407  RP904A  RO48B 

Input A 

P1 

P1 

1 & 2 

Input B 

P2 

P2 

4 & 5 

Output 

B1 

Main 

√ 

√ 

√ 

√ 

Table 2. RP470B Connections for a Lockout 

Operation. 

RP470B  RP405A  RP407  RP904A  RO48B 

Output 

P1 

P1 

1 & 2 

Pilot 

P2 

P2 

4 & 5 

Input 

B1 

Main 

√ 

√ 

√ 

√ 

CHECKOUT AND TEST 

RP470A - Higher-of-Two-Pressures Relay 

Ensure that the higher-of-two-input pressures at Ports 3 
and 5 is transmitted through output Port 2. 

RP470B - Lockout Relay or Repeater 

In a lockout relay application, ensure that the relay 

passes the signal at Port 2 to Port 3 if the pressure at 
Port 5 is lower than the pressure at Port 2. When the 

pressure at Port 5 is greater than the pressure at Port 2, 
lockout should occur. 

In a lower-of-two-pressures application, make sure that 

the output is the lower pressure. 

ENGINEERING DATA 

Specifications 

Models: 

RP470A Higher-of-Two Pressures Relay 
RP470B Lockout Relay or Repeater 

Operating Pressure Range: 

Normal: 0 to 18 psi (0 to 124 kPa) 
Maximum: 30 psi (207 kPa) 

Maximum Safe Air Pressure: 

30 psi (207 kPa) 

Ambient Operating Limits: 

Temperature: 0 to 140°F (-18 to 60°C) 
Relative Humidity: 5 to 95% 

Air Handling Capacity: 

0.039 scfm at 1 psi (18 ml/s at 

7 kPa) differential 

Construction: 

Molded plastic with neoprene diaphragm 

and valox valve seat 

Operation 

RP470A 

When the pressure at Port 3 is greater than the pressure 

at Port 5 (Fig. 4A), Port 3 supplies the output through 
Port 2 and the output at Port 2 equals the pressure at 

Port 3. When the pressure at Port 5 is greater than the 
pressure at Port 3 (Fig. 4B), Port 3 closes off and the 

output at Port 2 equals the pressure at Port 5. 

95-7231EF

  

Summary of Contents for RP470A

Page 1: ... 2 1 1 2 38 25 C3211 Fig 1 RP470A and B dimensions 3 5 2 1 BEFORE INSTALLATION In a lower of two pressures application the RP470B requires a 0 007 Filter Restrictor 14002913 002 if the input is not already restricted a one pipe device input INSTALLATION Mounting Suspend on tubing or mount on a surface See Fig 2 for surface mounting WALL OR PANEL RELAY NO 10 X 1 2 IN SHEET METAL SCREW OBTAIN LOCALL...

Page 2: ...re that the higher of two input pressures at Ports 3 and 5 is transmitted through output Port 2 RP470B Lockout Relay or Repeater In a lockout relay application ensure that the relay passes the signal at Port 2 to Port 3 if the pressure at Port 5 is lower than the pressure at Port 2 When the pressure at Port 5 is greater than the pressure at Port 2 lockout should occur In a lower of two pressures a...

Page 3: ...those having 0 007 restrictors 0 15 psi 1 03 kPa Fig 6 shows a typical application using three zone thermostats and two RP470A for control Each zone is controlled by a separate thermostat The thermostat that calls for the most cooling transmits the highest branchline pressure controls the cooling valve through one or both RP470A ZONE 1 DA THERMOSTAT ZONE 2 DA THERMOSTAT ZONE 3 DA THERMOSTAT N C DA...

Page 4: ...ssures selection Fig 10 shows the RP470B piped for the lowest of two pressures selection with a capacity type device input INPUT 1 RP470B RESTRICTOR EXH CAPACITY TYPE DEVICE INPUT 2 5 3 OUTPUT C4488 Fig 10 RP470B piped for lowest of two pressures selection with capacity type device input Fig 11 shows the RP470B piped for a lowest of two pressures selection with a one pipe bleed type device input I...

Page 5: ...s Corps gris et noir La Fig 1 donne l encombrement en millimètres pouces des RP470A et B 3 2 38 1 1 2 1 CF3211 Fig 1 Encombrement des RP470A et B 3 5 2 25 AVANT D INSTALLER CE PRODUIT Dans une application de commande par la plus basse de deux pressions il faut ajouter au RP470B un réducteur filtre de 0 018 mm pièce 14002913 002 si l entrée n est pas déjà réduite entrée d un appareil à un tuyau INS...

Page 6: ...isé comme dispositif de blocage RP470B RP405A RP407 RP904A RO48B Sortie 3 P1 M P1 1 2 Pilote 5 P2 P P2 4 5 Entrée 2 B B1 B 3 Canal princ M VÉRIFICATION ET ESSAI RP470A Relais de commande par la plus élevée de deux pressions S assurer que la plus élevée de deux pressions aux orifices 3 et 5 est acheminée dans l orifice de sortie 2 RP470B Relais de blocage ou répéteur Dans une application avec relai...

Page 7: ...Elle est de 2 07 kPa 0 30 psi comparativement à 1 03 kPa 0 15 psi dans les circuits comportant des réducteurs de 0 018 mm La Fig 6 montre une application type avec des thermostats à trois zones et deux relais de commande RP470A Chaque zone est commandée par un thermostat distinct Le thermostat exigeant le plus de refroidissement qui transmet la pression la plus élevée dans la canalisation secondai...

Page 8: ...essions avec une entrée munie d un capteur à variation de puissance ENTRÉE 1 2 5 3 RP470B RÉDUCTEUR PURGE ENTRÉE AVEC CAPTEUR À VARIATION DE PUISSANCE SORTIE CF4488 Fig 10 RP470B installé comme relais sélecteur de la plus basse de deux pressions avec une entrée munie d un capteur à variation de puissance La Fig 11 montre un RP470B installé comme relais sélecteur de la plus basse de deux pressions ...

Reviews: