background image

7

60-2035—9

RA890G

OPERATION AND CHECKOUT

Fig. 6—Flame  current check.

M8716

W136A

196146  METER 
CONNECTOR 
PLUG (SUPPLIED 
WITH W136)

BLACK

BLACK

RED

RED

FLAME
CURRENT
TEST JACK

RA890

PILOT TURNDOWN TEST

CAUTION

The pilot turndown test should be performed only
by qualified personnel, and the instructions should
be followed carefully.

On systems that prove a pilot before the main fuel valve

can be opened, perform a pilot turndown test to prove that the
main burner can be lighted by the smallest pilot that will hold
in the flame relay. Perform a flame current check before and
after the pilot turndown test.

1. Open the main power switch.
2. Shut off the fuel supply to the main burner only by

closing the manual main burner shutoff cock. Do not shut off
the fuel supply to the pilot valve.

3. Restore power to the relay.
4. Start the system by raising the setpoint of the control-

ler (or pressing the START button). The pilot will light and
pull in the flame relay.

5. Reduce the size of the pilot flame to the turndown

condition by slowly closing the manual valve on the pilot gas
line. At the turndown condition, the pilot will be small
enough to just barely hold in the flame relay (2K).

a. Turn down the pilot until relay 2K drops out.
b. Turn the pilot back up slowly just until relay 2K pulls

back in.

c. Again turn the pilot down slightly, but not enough so

the relay drops out.

If the relay drops out again, simply turn up the pilot and

try again. The closer the pilot is to the dropout condition, the
more conclusive the test will be.

6. Check that the pilot is lit and relay 2K is pulled in.
7. Open the manual main burner shutoff cock. Main

flame should light smoothly within one second. If the burner
does not light within one second, close the shutoff cock
 and
shut off power to the relay. Proceed to step 9.

8. If the burner lights, repeat step 7 two or three times to

verify smooth lightoff.

9. If the lightoff is unsatisfactory, readjust the flame

detector to require a larger pilot flame to hold in the flame

relay. This usually requires resighting the detector farther
out on the axis of the pilot flame.

CAUTION

If the pilot needs to be adjusted and rechecked,
allow five minutes for the purge of unburned gases
in the firebox before proceeding to the next step.

10. Repeat the entire turndown test until the flame is

established promptly in step 7.

11. Turn up the pilot to full flame at the completion of the

test. Perform a flame current check before leaving the job.

IGNITION SPARK RESPONSE TEST

The flame detection system should not respond to the

ignition spark (no meter movement). To determine flame
detector sensitivity to ignition spark, perform the following
steps:

1. Shut off pilot and main fuel manual valves.
2. Connect a W136 Microammeter and 196146 Test

Cable into the test jack on the RA890G. (See Flame Current
check procedure section.)

3. Raise the controller setpoint. This should energize the

ignition transformer and produce an ignition spark.

4. The W136 Meter should not indicate a signal present.
5. If the meter indicates UV is being detected, resight the

flame detector until the UV signal is eliminated. It may be
necessary to construct a barrier to block the ignition spark
from the detector view. Continue adjusting until the ignition
spark flame signal is less than one-fourth microampere.

NOTE: The Honeywell Q624A Solid State Spark Generator

prevents detection of ignition spark when properly ap-
plied with flame detection systems using C7027, C7035,
or C7044 Minipeeper Ultraviolet Flame Detectors. The
Q624A is for use only with gas pilots.

SAFE SHUTDOWN CHECKS LIMIT ACTION

With the burner operating, lower the high limit setting to

simulate an overheated boiler or furnace. Normal shutdown
should occur. Restore the normal limit setting; the burner
should restart.

FLAME FAILURE RESPONSE TEST

With the burner operating for a period of five minutes,

close the manual fuel valves to simulate a flame failure. The
W136 Meter reading should drop to zero within the flame
response timing of the flame safeguard relay (0.8 to 3 sec-
onds nominal). This action should be followed by safety
switch lockout (15 seconds nominal). After the safety switch
cools, open the manual valves. The burner should restart
when the safety switch is reset.

If the meter reading does not drop to zero within the

allowed time, replace the UV detector and repeat the test.

IMPORTANT: Repeat ALL required checkout tests after

all adjustments are complete. ALL tests must be satis-
fied with the flame detector in its FINAL position.

Summary of Contents for RA890G

Page 1: ...es resistance to vibration Push to reset safety switch button is in dust resis tant enclosure Safe start check prevents start if flame or flame simulating failure is present Automatic safety switch lockout if flame fails on start or if flame is not re established after a flame failure When limit control opens control de energizes ignition and fuel valves but safety switch lockout will not occur Te...

Page 2: ...uty 125VA 125VA Alternate Rating 25 VA pilot duty plus one or more motorized valves with total rating of 400 VA opening 200 VA holding MAXIMUM Models without alarm contacts 50 Hz 115 F 46 C 60 Hz 125 F 52 C Models with alarm contacts 50 Hz 105 F 41 C 60 Hz 115 F 46 C ALARM CONTACTS Optional Isolated spdt contacts Alarm terminals are male quick connects female quick connectsincludedforfieldinstalla...

Page 3: ... plicable local electrical codes ordinances and regulations 2 Limitsmustberatedtocarryandbreakcurrentto theignitiontransformer pilotvalve orfirststage oilvalve andmainfuelvalve s simultaneously 3 AllexternaltimersmustbeListedorComponent Recognized by authorities that have jurisdiction forthespecificpurposesforwhichtheyareused Follow the burner manufacturer instructions when sup plied otherwise pro...

Page 4: ...ORTANT Do not run high voltage ignition trans former wires in the same conduit with the flame detector wiring 5 Refer to Fig 2 and 3 for typical field wiring connec tions Follow the burner manufacturer s wiring diagram if provided Fig 2 Gas system with interrupted ignition APPLICATIONS Either a line or low voltage controller can be used If a line voltage controller is used connect it between the l...

Page 5: ...E OIL VALVE IF USED OIL VALVE OperationAnd Checkout CAUTION 1 Use extreme care while testing the RA890G line voltage is present on some terminals and contacts when power is On 2 Disconnect power supply before removing cover removing RA890G from subbase or reinstalling RA890G onto subbase PRELIMINARY CHECKS Before placing the system in operation complete the following preliminary checks 1 Check wir...

Page 6: ...an a needle width 2 The flame current is at least 1 5 microamperes for an ultraviolettypedetectorsuchasusedwiththeRA890G If a satisfactory reading is not obtained check the power sourcefortheproperlinevoltage andtheflamesizeandthe detector for proper sensing Directions for obtaining a steady current reading are included in the instructions packed with the C7027 C7035 or C7044 Ultraviolet Flame Det...

Page 7: ...tes for the purge of unburned gases in the firebox before proceeding to the next step 10 Repeat the entire turndown test until the flame is established promptly in step 7 11 Turn up the pilot to full flame at the completion of the test Perform a flame current check before leaving the job IGNITION SPARK RESPONSE TEST The flame detection system should not respond to the ignition spark no meter movem...

Page 8: ... lens 6 DO NOT MANUALLY PUSH IN THE RA890 RE LAYS This may damage the relays and it is an unsafe practice because it overrides the protective features of the relay Clean relay contacts only as instructed below PERIODIC MAINTENANCE The specific maintenance schedule setup depends on severalfactorsincludingtypeofequipmentbeingcontrolled operating conditions dirt and heat especially cost of a nuisance...

Page 9: ...e flame detector or external circuit Replace the detector TEST STARTING OPERATION 6 Set controller to call for heat increase setpoint 7 Observe load relay for pull in a Load relay pulls in to light pilot and start burner proceed to step 11 b Load relay does not pull in proceed to step 8 c Loadrelaypullsinbutdoesnotlightorburnerdoesnot start proceed to step 10 8 Check line voltage controller if use...

Page 10: ...result from extreme low voltage notifypowercompany orfromalooseconnection tighten Flame relay chatter may result from improper combus tion adjust burner or soot or carbon on flame detector clean and correct the cause REPEATED LOCKOUTS OR CONTROL FAILURES The most common causes of repeated failure of this control or flame detector or of repeated lockouts are a High ambient temperatures over 125 F 5...

Page 11: ...11 60 2035 9 ...

Page 12: ...Home and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A www honeywell com bbc ...

Reviews: