60-2035—9

2

RA890G

SPECIFICATIONS  •  ORDERING INFORMATION

Specifications

TRADELINE® MODELS
TRADELINE® models are selected and packaged to pro-

vide ease of stocking, ease of handling, and maximum
replacement value. TRADELINE® model specifications
are the same for standard models except as noted below.

TRADELINE® MODELS AVAILABLE: RA890G

Protectorelay™ Primary Control—120 Vac, 50/60 Hz.

STANDARD MODELS
MODEL:  RA890G Protectorelay™ Primary Control.
VOLTAGE AND FREQUENCY: 120V, 208V, 220V, 240V;

50/60 Hz models.

VOLT-AMPERE RATING:

60 Hz: 14 VA maximum, 12 VA standby.
50 Hz: 18 VA maximum, 17 VA standby.

POWER CONSUMPTION:

60 Hz: 9.5W maximum, 3W standby.
50 Hz:10W maximum, 4W standby.

FLAME FAILURE RESPONSE TIME:  0.8 or 3 seconds

(nominal; separate models). 3 second response time rec-
ommended for nonrecycling cutoff system.

FLAME ESTABLISHING PERIOD:  Up to 15 seconds

(nominal).

RECYCLE TIME:  Occurs immediately when flame loss is

recognized. See Flame Failure Response Time.

SAFETY SWITCH TIMING (LOCKOUT TIMING): 15 sec-

onds. Timings are proportional with input voltages and
temperatures. For RA890 classified in Underwriters Labo-
ratories Inc gas groups 6 and 6a and oil group 8, the
maximum safety switch timing with voltages ranging
from 70 to 110 percent of rated voltage and with ambients
ranging from 32

°

F (0

°

C) to 115

°

F (66

°

C) are allowed to

be as high as 50 seconds.

DIMENSIONS (Including Subbase):  Approximately 5 x 5

x 5 (127 x 127 x 122 mm).

AMBIENT TEMPERATURE RATING:

MINIMUM: Models with 15 second safety switch:

 -20

°

F (-29

°

C).

Terminal

Electrical Load

120

Vac

240

Vac

3

Burner

Motor

Full Load

5.2A

2.6A

Locked Rotor

31.2A

15.6A

Ignitiona

3.0A

1.5A

Pilot Fuel Valve

25VA

25VA

4

Ignitiona

3.0A

1.5A

5

Main Valve (Pilot Duty)

125VA

125VA

Alternate Rating: 25 VA pilot duty plus one or
more motorized valves with total rating of 400
VA opening, 200 VA holding.

MAXIMUM:  Models without alarm contacts:

50 Hz: 115

°

F, 46

°

C.

60 Hz: 125

°

F, 52

°

C.

Models with alarm contacts:

50 Hz: 105

°

F, 41

°

C.

60 Hz: 115

°

F, 46

°

C.

ALARM CONTACTS (Optional):  Isolated spdt contacts.

Alarm terminals are male quick-connects (female quick-
connects included for field installation). See rating above.

FLAME DETECTOR:  C7027, C7035 or C7044 Ultraviolet

Flame Detector.

MOUNTING:  Q270A Universal Mounting Base (ordered

separately).

ELECTRICAL RATINGS:

a

 If ignition and motor are connected to terminal 3, terminal

4 cannot be used. This prevents overloading relay 1K.

Alarm Contacts: 3.0 A at 24 Vac, or 75 VA pilot duty at

120 Vac in suitable wiring enclosure.

Low Voltage Control Circuit (T-T): 0.17A.

NOTE: Allowable inrush can be up to ten times the pilot duty

rating.

Ordering Information

When purchasing replacement and modernization products from your TRADELINE

®

 wholesaler or distributor, refer to the Tradeline

Catalog or price sheets for complete ordering number, or specify—

1. Order number specify TRADELINE®, if desired.

4.  Alarm contacts, if desired.

2. Voltage and frequency.

5.  Accessories, if desired.

3. Flame response time.

If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:

1. Your local Home and Building Control Sales Office (please check the white pages of your phone directory).
2. Home and Building Control Customer Logistics

Honeywell Inc., 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and
Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

Summary of Contents for RA890G

Page 1: ...es resistance to vibration Push to reset safety switch button is in dust resis tant enclosure Safe start check prevents start if flame or flame simulating failure is present Automatic safety switch lockout if flame fails on start or if flame is not re established after a flame failure When limit control opens control de energizes ignition and fuel valves but safety switch lockout will not occur Te...

Page 2: ...uty 125VA 125VA Alternate Rating 25 VA pilot duty plus one or more motorized valves with total rating of 400 VA opening 200 VA holding MAXIMUM Models without alarm contacts 50 Hz 115 F 46 C 60 Hz 125 F 52 C Models with alarm contacts 50 Hz 105 F 41 C 60 Hz 115 F 46 C ALARM CONTACTS Optional Isolated spdt contacts Alarm terminals are male quick connects female quick connectsincludedforfieldinstalla...

Page 3: ... plicable local electrical codes ordinances and regulations 2 Limitsmustberatedtocarryandbreakcurrentto theignitiontransformer pilotvalve orfirststage oilvalve andmainfuelvalve s simultaneously 3 AllexternaltimersmustbeListedorComponent Recognized by authorities that have jurisdiction forthespecificpurposesforwhichtheyareused Follow the burner manufacturer instructions when sup plied otherwise pro...

Page 4: ...ORTANT Do not run high voltage ignition trans former wires in the same conduit with the flame detector wiring 5 Refer to Fig 2 and 3 for typical field wiring connec tions Follow the burner manufacturer s wiring diagram if provided Fig 2 Gas system with interrupted ignition APPLICATIONS Either a line or low voltage controller can be used If a line voltage controller is used connect it between the l...

Page 5: ...E OIL VALVE IF USED OIL VALVE OperationAnd Checkout CAUTION 1 Use extreme care while testing the RA890G line voltage is present on some terminals and contacts when power is On 2 Disconnect power supply before removing cover removing RA890G from subbase or reinstalling RA890G onto subbase PRELIMINARY CHECKS Before placing the system in operation complete the following preliminary checks 1 Check wir...

Page 6: ...an a needle width 2 The flame current is at least 1 5 microamperes for an ultraviolettypedetectorsuchasusedwiththeRA890G If a satisfactory reading is not obtained check the power sourcefortheproperlinevoltage andtheflamesizeandthe detector for proper sensing Directions for obtaining a steady current reading are included in the instructions packed with the C7027 C7035 or C7044 Ultraviolet Flame Det...

Page 7: ...tes for the purge of unburned gases in the firebox before proceeding to the next step 10 Repeat the entire turndown test until the flame is established promptly in step 7 11 Turn up the pilot to full flame at the completion of the test Perform a flame current check before leaving the job IGNITION SPARK RESPONSE TEST The flame detection system should not respond to the ignition spark no meter movem...

Page 8: ... lens 6 DO NOT MANUALLY PUSH IN THE RA890 RE LAYS This may damage the relays and it is an unsafe practice because it overrides the protective features of the relay Clean relay contacts only as instructed below PERIODIC MAINTENANCE The specific maintenance schedule setup depends on severalfactorsincludingtypeofequipmentbeingcontrolled operating conditions dirt and heat especially cost of a nuisance...

Page 9: ...e flame detector or external circuit Replace the detector TEST STARTING OPERATION 6 Set controller to call for heat increase setpoint 7 Observe load relay for pull in a Load relay pulls in to light pilot and start burner proceed to step 11 b Load relay does not pull in proceed to step 8 c Loadrelaypullsinbutdoesnotlightorburnerdoesnot start proceed to step 10 8 Check line voltage controller if use...

Page 10: ...result from extreme low voltage notifypowercompany orfromalooseconnection tighten Flame relay chatter may result from improper combus tion adjust burner or soot or carbon on flame detector clean and correct the cause REPEATED LOCKOUTS OR CONTROL FAILURES The most common causes of repeated failure of this control or flame detector or of repeated lockouts are a High ambient temperatures over 125 F 5...

Page 11: ...11 60 2035 9 ...

Page 12: ...Home and Building Control Helping You Control Your World Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario M1P 2V9 Printed in U S A www honeywell com bbc ...

Reviews: