background image

  INSTALLATION INSTRUCTIONS

95-7735

Q7055C Building Network Adapters

BNA-1C/2CS

WARNING

This equipment generates, uses and can radiate 
radio frequency energy, and if not installed and 
used in accordance with the Instructions Manual, 
may cause interference with radio communication. 
It has been tested and found to comply with the 
limits for a Class A computing device pursuant to 
Subpart J of Part 15 or FCC Rules, which are 
designed to provide reasonable protection against 
such interference when operated in a commercial 
environment. Operation of this equipment in a 
residential area is likely to cause interference, in 
which case, users at their own expense will be 
required to take whatever measures may be 
required to correct the interference. Any 
unauthorized modification of this equipment may 
result in the revocation of the owner's authority to 
continue its operation.

GENERAL

The Q7055C series Building Network Adapters (BNA) provide 
connection of a Honeywell

®

 controller communication bus to 

an industry standard 10/100BaseT Ethernet LAN. The 
Building Network Adapter (BNA) delivers exceptional price/ 
performance to meet the requirements of both building owners 
and service providers. With its combination of scalable 
performance, density, and low per-port pricing, the BNA 
allows network-layer capabilities to be extended to a much 
wider range of network configurations and environments. 
High-performance network and services, including traffic 
management, are now available to additional locations 
throughout the network. 

The BNA uses the LAN-connection to provide a seamless 
communication to the requesting device. Status information 
such as LAN communication activity, field bus traffic 
communication, and system Heartbeat of the BNA is indicated 
by LEDs on the front of the device.

The BNA models provide an interface from various Honeywell 
controller buses that use RS-485 signals to a local area 
network using 802.3 Ethernet protocol. This allows data to be 
used by high-level Building Management Systems such as the 
Honeywell Enterprise Buildings Integrator (EBI)

.

This Installation Instruction covers the following BNA devices:

Q7055C1009 BNA-1C. Provides a single RS-485 DC 
coupled C-Bus-compatible communication channel for 
Excel 5000

®

 family devices with up to 76.8 kbps.

Q7055C1017 BNA-2CS. Provides two RS-485 DC 
coupled C-/S-Bus compatible communication chan-
nels for Excel Classic and XL5000 family devices in 
smoke control systems with up to 76.8 kbps.

Additionally, each BNA is equipped with a RJ-45 10/100BaseT 
connector, plus an RS-232 interface. (see Fig. 1).

Fig. 1. BNA network.

The Q7055C Building Network Adapter is used in systems for 
signaling smoke control of fire (UL 864-9th), UL 916, and 
general purpose signaling (UL 2017). Also applies to CEC 
22.1 standard. In UL 2017 applications, the product can be 
used as either a type SM (Self-Monitored) or type AM 
(Attendant-Monitored) system.

SPECIFICATIONS

Models: 

Q7055C1009 Building Network Adapter BNA-1C. Provides a 

single RS-485 DC coupled C-Bus-compatible 
communication channel for XL800 and Excel 5000 family 
devices with up to 76.8 kbps. 

WORKSTATION 

EBI 

BNA-1C 

SINGLE C-BUS  

(ONLY FOR XL5000, IRC AND EMC 

 CONTROLLERS FAMILIES) 

ETHERNET 

WORKSTATION 

M25320 

 

LOCAL AREA NETWORK 

 

TWO C-/S-BUS

(FOR EXCEL IRC,

EMC, EXCEL CLASSIC

AND XL5000

CONTROLLERS FAMILIES)

BNA-2CS 

 

 

Summary of Contents for Q7055C Series

Page 1: ...n to provide a seamless communication to the requesting device Status information such as LAN communication activity field bus traffic communication and system Heartbeat of the BNA is indicated by LEDs on the front of the device The BNA models provide an interface from various Honeywell controller buses that use RS 485 signals to a local area network using 802 3 Ethernet protocol This allows data ...

Page 2: ... product has been received without dam age 2 Verify that the correct BNA device has been delivered 3 Check the package contents The following items are included in each product package Building Network Adapter device 50017367 001 Power Supply Building Network Adapter Installation Instructions Bag of installation materials as follows one 3 pole Phoenix power connector one or two Phoenix con troller...

Page 3: ...x Tx 100 Boot NML M25115 Place the BNA adapter with the topside down on the desk Remove the four feet from the bottom of the BNA by pushing horizontally away from the housing with a flat screwdriver Push the four inserts included fully and horizontally into the housing Adjust the four retaining clips included on top of the inserts Fasten the retaining clips with the included four screws Use the ho...

Page 4: ...ICLE 760 ALL POWER LIMITED WIRING MUST BE SEPARATED FROM ALL NON POWER LIMITED WIRING BY A MINIMUM DISTANCE OF 1 4 IN 6 MM NOTE TYPICAL MOUNTING LOCATION FOR Q7055 BUILDING NETWORK ADAPTER BNA 1 G GROUNDING CONDUCTOR 2 GROUND CONNECTION 8 32 STUD WITH 8 32 KEPS NUT 3 GROUND CONNECTION FOR 14507678 SERIES ETHERNET PROTECTOR AND OTHER LOW VOLTAGE EQUIPMENT 4 DRILLED MOUNTING HOLES FOR 14507719 001 8...

Page 5: ...crew terminals wire a cable to the 24 V and GND terminals on the power supply 2 Strip the two power cable ends and insert each cable end into the openings of the 3 pole Phoenix connectors that are marked for power 3 Fasten them with a screwdriver 4 Connect a chassis ground to the third position on this connector as marked NOTE The polarity of the 3 pole Phoenix power con nector for DC power suppli...

Page 6: ...ct a BNA device to a LAN via an Ethernet Hub the required cable should be configured as shown in Fig 9 Fig 9 Straight through pinning for BNA to EthernetHub connections Connect BNA to Workstation When a BNA needs a direct connection to a workstation without using an Ethernet Hub a crossover cable is required Fig 10 shows how the different signals should be connected Fig 10 Crossover pinning for BN...

Page 7: ...atus using three LEDs 10LNK Ethernet speed of 10 mbps indicator Green If this LED is lit then the Ethernet link is operating at 10 mbps 100LNK Ethernet speed of 100 mbps indicator Green If this LED is lit then the Ethernet link is operating at 100 mbps Activity Link activity indicator Green will blink if there is any activity transmission reception on the LAN Fig 12 Parts and controls on rear side...

Page 8: ...ures and practices contained in applicable NFPA and UL standards The Q7055C BNA has no user replaceable fuses For service contact your local Honeywell Automation Control Solutions office as listed in the phone book or contact a regional office as shown at the end of this document Jameco IS A REGISTERED TRADEMARK OF ARNDT ELECTRONICS ELPAC IS A REGISTERED TRADEMARK OF JSR CORPORATION HONEYWELL EXCE...

Page 9: ...Q7055C BUILDING NETWORK ADAPTERS BNA 1C 2CS 9 95 7735 ...

Page 10: ...Honeywell Pacific Level 3 2 Richardson Place North Ryde NSW 2113 In North America Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 In Asia Zhang Jiang Hi Tech Park No 430 Li Bing Rd Pudong New Area Shangai 201203 China In Europe Middle East Africa India Hermes Plaza Hermeslaan 1H B 1831 Diegem Belgium www honeywell com buildingsolutions ...

Reviews: