Q7055C BUILDING NETWORK ADAPTERS BNA-1C/2CS

95-7735

4

Fig. 5. Typical mounting of Q7055C BNA Assembly on 14006090-555151 series Communications Panel.

WIRE PER NEC FOR FIRE ALARM 

M25288 

POWER LIMITED AREA 

NON-POWER  
LIMITED AREA 

SYSTEM WIRING IS CLASSIFIED AS EITHER POWER LIMITED OR NON-POWER LIMITED 
PER NEC ARTICLE 760. ALL POWER LIMITED WIRING MUST BE SEPARATED FROM ALL 
NON-POWER LIMITED WIRING BY A MINIMUM DISTANCE OF 1/4 IN. (6 MM). 

 
 
NOTE:  

TYPICAL MOUNTING LOCATION FOR Q7055 BUILDING NETWORK ADAPTER (BNA).

G = GROUNDING CONDUCTOR 
 
 
 

GROUND CONNECTION. 8-32 STUD WITH 8-32 KEPS NUT. 
 
 
 

GROUND CONNECTION FOR 14507678 SERIES ETHERNET PROTECTOR AND OTHER 
LOW VOLTAGE EQUIPMENT. 
 
 

DRILLED MOUNTING HOLES FOR 14507719-001 8 PORT ETHERNET HUB (IF USED). 
 
 

 

 
 

N  G 

BNA 

6

6

14503899-002 MOV FACTORY INSTALLED
ON TERMINAL STRIP.

Summary of Contents for Q7055C Series

Page 1: ...n to provide a seamless communication to the requesting device Status information such as LAN communication activity field bus traffic communication and system Heartbeat of the BNA is indicated by LEDs on the front of the device The BNA models provide an interface from various Honeywell controller buses that use RS 485 signals to a local area network using 802 3 Ethernet protocol This allows data ...

Page 2: ... product has been received without dam age 2 Verify that the correct BNA device has been delivered 3 Check the package contents The following items are included in each product package Building Network Adapter device 50017367 001 Power Supply Building Network Adapter Installation Instructions Bag of installation materials as follows one 3 pole Phoenix power connector one or two Phoenix con troller...

Page 3: ...x Tx 100 Boot NML M25115 Place the BNA adapter with the topside down on the desk Remove the four feet from the bottom of the BNA by pushing horizontally away from the housing with a flat screwdriver Push the four inserts included fully and horizontally into the housing Adjust the four retaining clips included on top of the inserts Fasten the retaining clips with the included four screws Use the ho...

Page 4: ...ICLE 760 ALL POWER LIMITED WIRING MUST BE SEPARATED FROM ALL NON POWER LIMITED WIRING BY A MINIMUM DISTANCE OF 1 4 IN 6 MM NOTE TYPICAL MOUNTING LOCATION FOR Q7055 BUILDING NETWORK ADAPTER BNA 1 G GROUNDING CONDUCTOR 2 GROUND CONNECTION 8 32 STUD WITH 8 32 KEPS NUT 3 GROUND CONNECTION FOR 14507678 SERIES ETHERNET PROTECTOR AND OTHER LOW VOLTAGE EQUIPMENT 4 DRILLED MOUNTING HOLES FOR 14507719 001 8...

Page 5: ...crew terminals wire a cable to the 24 V and GND terminals on the power supply 2 Strip the two power cable ends and insert each cable end into the openings of the 3 pole Phoenix connectors that are marked for power 3 Fasten them with a screwdriver 4 Connect a chassis ground to the third position on this connector as marked NOTE The polarity of the 3 pole Phoenix power con nector for DC power suppli...

Page 6: ...ct a BNA device to a LAN via an Ethernet Hub the required cable should be configured as shown in Fig 9 Fig 9 Straight through pinning for BNA to EthernetHub connections Connect BNA to Workstation When a BNA needs a direct connection to a workstation without using an Ethernet Hub a crossover cable is required Fig 10 shows how the different signals should be connected Fig 10 Crossover pinning for BN...

Page 7: ...atus using three LEDs 10LNK Ethernet speed of 10 mbps indicator Green If this LED is lit then the Ethernet link is operating at 10 mbps 100LNK Ethernet speed of 100 mbps indicator Green If this LED is lit then the Ethernet link is operating at 100 mbps Activity Link activity indicator Green will blink if there is any activity transmission reception on the LAN Fig 12 Parts and controls on rear side...

Page 8: ...ures and practices contained in applicable NFPA and UL standards The Q7055C BNA has no user replaceable fuses For service contact your local Honeywell Automation Control Solutions office as listed in the phone book or contact a regional office as shown at the end of this document Jameco IS A REGISTERED TRADEMARK OF ARNDT ELECTRONICS ELPAC IS A REGISTERED TRADEMARK OF JSR CORPORATION HONEYWELL EXCE...

Page 9: ...Q7055C BUILDING NETWORK ADAPTERS BNA 1C 2CS 9 95 7735 ...

Page 10: ...Honeywell Pacific Level 3 2 Richardson Place North Ryde NSW 2113 In North America Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 In Asia Zhang Jiang Hi Tech Park No 430 Li Bing Rd Pudong New Area Shangai 201203 China In Europe Middle East Africa India Hermes Plaza Hermeslaan 1H B 1831 Diegem Belgium www honeywell com buildingsolutions ...