PRO-2200 Enclosure PRO22ENC1 & PRO22ENC2
19
Installation Guide
Cable Specifications
Application
ESG Part No.
AWG
Description
Max. Dist.
Imp.
Cap.
N-485 connections*
NC2442-TN
N/A
Belden 9842
4000' (1200 m)
120
Ω
12.8pf/ft
N/A
or equivalent
CR-1, TR-1, CI-1, KR-1
NC1861-BL
18
6 conductor shielded
500' (152 m)
Wiegand card readers
NR-1 magstripe reader
NC1861-BL
18
6 conductor shielded
500' (152 m)
PR-1-280 Cotag reader:
280 read head to SZC
NC1861-BL
18
6 conductor shielded
300' (91 m)
SZC to N-1000-II
NC1861-BL
18
6 conductor shielded
500' (152 m)
PR-2 Hughes reader:
scanner to reader
NC1861-BL
18
6 conductor shielded
30' (9 m)
reader to N-1000-II
NC1861-BL
18
6 conductor shielded
500' (152 m)
PR-3, PR-5 Indala readers:
A-3/A-5 read head to RE-2
NC18121-YL
18
12 conductor shielded
75' (23 m)
RE-2 to N-1000-II
NC1861-BL
18
6 conductor shielded
500' (152 m)
PR-20 , PR-22 Indala readers:
A-20/A-22 read head
to RE-2
NC18121-YL
18
12 conductor shielded
75' (23 m)
RE-2 to N-1000-II
NC1861-BL
18
6 conductor shielded
500' (152 m)
PR-10, PR-12 Indala readers: NC1861-BL
18
6 conductor shielded
500' (152 m)
HG-3 hand geometry reader:
NC1861-BL
18
6 conductor shielded
500' (152 m)
5 conductor keypad
NC1861-BL
18
6 conductor shielded
500' (152 m)
Alarm input points
NC 2221-BR
22
2000' (610 m)
Relay outputs
NC 1821-OR
18
twisted pair, shielded
2000' (610 m)
NOTE: For Plenum rated cable just add a “P” to Engineered Systems part number prefix; for example
NC1861-BL becomes PNC1861-BL
Summary of Contents for PRO-2200
Page 1: ...PRO 2200 Enclosure Installation Manual Part Number PRO22ENC1 PRO22ENC2 TD1138 rev0801 ...
Page 20: ...PRO 2200 Enclosure PRO22ENC1 PRO22ENC2 21 Installation Guide NOTES ...
Page 21: ...22 PRO 2200 Enclosure PRO22ENC1 PRO22ENC2 Installation Guide NOTES ...
Page 22: ...PRO 2200 Enclosure PRO22ENC1 PRO22ENC2 23 Installation Guide ...