28
NFS2-640/E Programming Manual —
P/N 52742:L2 7/17/14
Programming
Basic Program
Mass Notification
When used for mass notification, special zones ZF20, ZF21, and ZF22 can be used to signal the
MN event.
NOTE:
During local or network Walk Test, activating a Mass Notification device will activate
associated special function zones according to CBE programming and simulate a Mass
Notification event. Any network nodes, zones, or devices not participating in Walk Test will not
participate in the simulated Mass Notification event.
Special Zones F1-F4
The control panel also provides four Special Zones, F1-F4, which are outputs that do not appear on
the Special Function Change screen. You can program Special Zones F1 to F4 into the CBE of an
output device. Descriptions of F1, F2, F3, and F4 are detailed below:
To view the status of Special Functions F1-F4, use the Read Status function (refer to the
NFS2-640
Operations Manual
).
Table 2.10 Summary of Special Zones
Special Zone
Lets you
F0=
PRESIG
Select a Presignal Delay Timer and select PAS (Positive Alarm
Sequence)
F5-F6=
TIME
Specify Time Control functions such as the start time, stop time, or
days of the week
F7=
HOL
Specify up to nine holiday dates. An F7-programmed device
activates on the specified holiday dates
F8=
CODE
Specify one of the following coding function selections: March Time,
Temporal, California, Two-Stage, Two-Stage Canada (3 minute or 5
minute), Two-Stage Canada Manual, System Sensor Strobes,
Gentex Strobes, or Wheelock Strobes. F8 only takes effect if you
program one or more NACs to F8
F9=
PRE
-
ALARM
Select a Pre-Alarm level: Alert or Action
FA (ZF10*)
Turn on when detector in verification mode. This is a fixed point and
is not programmable
FB (ZF16*)
Turn on if custom drill set to Y and the panel in Drill mode
FC (ZF18*)
Turn on when a CO alarm occurs
FD (ZF20*)
Turns on when a mass notification alarm occurs (Not applicable for
FirstCommand applications)
FE (ZF21*)
Turns on when a mass notification supervisory occurs
FF (ZF22*)
Turns on when a mass notification trouble occurs
NOTE: Special Function Zones FA through FF are not field programmable.
R0-R9=
REL
Program up to ten Releasing Zones, each with a selection for a
Delay Timer, an Abort Switch, a Cross Zone selection, or a Soak
Timer
* VeriFire Tools settings
Table 2.11 Special Output Functions F1-F4 (1 of 2)
Special Function
Specifies
F1 (Trouble less AC)
An output programmed to turn on/off if a system trouble—other
than an AC power loss—occurs