DIP
‐
SWITCH
SETTING
and
TERMINALS
CHART
1
Terminals
Connections
+
S1/RC
(1)
Sound
control
1:
24V
=
sound,
0V
=
silent
‐
S1/RC
(2)
Sound
control
1:
0V
=
sound,
24V
=
silent
+S2
(3)
Sound
control
2:
24V
=
sound,
0V
=
silent
R
(4)
Not
Connected.
Free
to
use
‐
S2
R
(5)
Sound
control
2:
0V
=
sound,
24V
=
silent
+
S3
(6)
Sound
control
3:
24V
=
sound,
0V
=
silent
‐
S3
(7)
Sound
control
3:
0V
=
sound,
24V
=
silent
ANM
(8)
Syncronism
TEST
(9)
LED
Control
see
DIP
3
CHART
2
DIP
Function
DIP1
Alarm
timing
DIP2
Alarm
timing
DIP3
Flash
control
DIP4
LED
mode
DIP5
Sound
pattern
selection
DIP6
Power
set
‐
up
DIP7
Power
set
‐
up
DIP8
OFF
–
Do
not
modify
CHART
3:
SOUNDER
TIMING
DIP
1 DIP
2
ALARM
TIMING
OFF
OFF
INFINITE
(BY
DEFAULT,
COMPLYING
TO
EN54
‐
3)
ON
OFF
3
MINUTES
(NOT
COMPLYING
TO
EN54
‐
3)
OFF
ON
(8
MINUTES
(NOT
COMPLYING
TO
EN54
‐
3)
ON
ON
15
MINUTES
(NOT
COMPLYING
TO
EN54
‐
3)
CHART
5:
LED
FLASHING
UNIT
DIP4
LEDs
MODE
OFF
STEADY
ON
ON
FLASHING
CHART
4:
FLASHING
SELECTION
DIP
3
FLASH
CONTROL
OFF
FLASH
CONTROLLED
BY
ALARM
INPUTS
ON
FLASH
CONTROLLED
BY
M9
TEST
INPUT
CHART
6:
AVERAGE
CURRENT
SELECTION
ONLY
SOUND
[Average
(Peak)
mA].
With
FLASHING
add
80mA
to
the
value
on
the
chart
DIP
5
OFF
DIP
5
ON
S1
S2
S3
S1
S2
S3
DIP
6
DIP
7
AVERAGE
CONSUMPTION
DIN33
Falling
(500
‐
1150Hz)
NFS32
dual
tone
(440
‐
554Hz)
ISO8021
‐
3
pulses
+
pause
(515Hz)
BS5839
Dual
Tone
(500
‐
1000Hz)
NEN2575
rising
+
pause
(500
‐
1200Hz)
Continuous
(625Hz)
OFF
OFF
100mA
60
(110
peak)
95
(95
peak)
60
(100
peak)
70
(100
peak)
70
(100
peak)
85
(90
peak)
ON
OFF
200mA
120
(180
peak)
150
(160 peak)
130
(210 peak)
200
(255 peak)
160
(285
peak)
180
(180 peak)
OFF
ON
400mA
250
(350
peak)
330
(370 peak)
250
(425 peak)
370
(470 peak)
290
(520
peak)
325 (350
peak)
ON
OFF