PAGE - 72
Programming Manual
AM_8200
NOTIFIER ITALIA
Doc. M-162.1-AM8200-ENG Rev A2
AM8200_manu-prog-ENG
STR
Addressable Strobe which follows the status of the panel Sounder
N
TABLE ‐3
Call Points Advanced
CBE Y/N
PULL
Same as MON, but label “MANUAL Call Point”.”.
Y
NONA
Input Module Non Alarm (no display but CBE activation)
Y
MACK
Input Module to
ACK
– Silence Buzzer from an impulsive contact (KEY)
N
MTAC
Input Module to
SILENCE
from an impulsive contact (KEY)
N
MRES
Input Module to
RESET
from an impulsive contact (KEY)
N
MTRB
The call point not pressed generates a fault event
N
NCMN
The call point not pressed generates an Alarm event
Y
STAT
Same as NONA, but report any change in status (ON‐OFF‐ON)
Y
TABLE ‐4
Sounder / Strobe Advanced
CBE Y/N
GSND
Addressable Sounder that can be Silenced
Y
SND
Addressable Sounder that follows the status of the panel Sounder
N
GSTR
Addressable Strobe that can be Silenced
Y
STR
Addressable Sounder that follows the status of the panel Sounder
N
GPND
Sounder or strobe activated at each unrecognized alarm / fault, silenciable.
N
APND
Sounder or strobe activated at each unrecognized alarm, silenciable.
N
GAC
Sounder or strobe activated at each alarm
N
TPND
Sounder or strobe activated at each unrecognized fault.
N
GTC
Sounder or strobe activated at each fault (latch).
N
TRS
Sounder or strobe activated at each fault.
N
ZLFT
Sounder or strobe activated for faulty Device in the Zone
N
REM
Sounder or strobe controllable only by external commands
N
MAINF
Sounder or strobe activated for Power Failure
N
ZDIS
Sounder or strobe activated in case of exclusion of point or zone.
N