PAGE - 34
Programming Manual
AM_8200
NOTIFIER ITALIA
Doc. M-162.1-AM8200-ENG Rev A2
AM8200_manu-prog-ENG
At the end of the Auto-programming procedure a summary of the devices found on the line is displayed
Where:
The
PROT ( Protocol )
control
can display the table of devices for one of the two possible protocols: CLIP or ADV
TYPE =
Type of devices found ( see table above)
NEW
= N
ew device found
NFO
= Devices previously programmed but not coherent with what was detected during the Auto-Learn procedure
TOT
= total of devices detected on the line ( NEW + NFO + correctly programmed devices.)
MIS
= Devices previously programmed but not detected during the Auto-Learn
The
SAVE
control saves the devices detected during the Self-Learn according to the following mode:
-
NEW and NFO are
initialized through the default data.
-
MIS
are removed
-
The correctly programmed devices keep the current programming
The data relevant to the initialized devices can be subsequently changed by entering the point programming
procedure.
Sample screen for CLIP detectors.
Important Note:
On Each Line, can be installed
a max number of 30 devices using CLIP
protocol.