PRE(CxxLxxSxxx)
It is the operator that uses the pre-alarm state of a sensor.
Example: The equation of an output module is: OR (PRE (C1L1S2) PRE (C2L1S10))
If either of the two sensors (L1S2 of the control panel 1 or L1S10 of the control panel 2) is in pre-alarm,
the output module to which the CBE is associated is activated.
FLT(CxxLxxSxxx)
It is the operator that lets you use the state of a device or zone failure.
Example 1: The equation of an output module is: OR (FLT (C1L1S2) PRE (C2L1S10))
If either one of the two sensors (L1S2 of the control panel 1 or L1S10 of the control panel 2) is in failure
or pre-alarm, the output module to which the CBE is associated is activated.
Example2: The equation of an output module is: OR (FLT (Z1) FLT (Z2))
If any of the two Zones (Z1 or Z2) is faulty, the output module to which the CBE is associated is
activated.
DIS
It is the operator that allows the disarming of zones and points by activating a programmed input
module programmed with Type-SW "NONA" (does not generate an alarm in the central unit).
Example1: The equation of an input module is: (DIS (Z1))
When the input module is active, Zone 1 is disabled.
Example2: The equation of an input module is: (DIS C1L1M1))
When the input module is active, the L1M1 module of the control panel 1 is disabled.
Additionally, the DIS operator allows you to recover a zone or point disabled state by activating the
output modules.
Example: The equation of an output module is: (DIS (Z1))
When Zone 1 is disabled the output module is active.