AM_8200
Programming Manual
PAGE - 63
AM82000_manu-prog-ENG
Doc. M-162.1-AM8200-ENG Rev A2
NOTIFIER ITALIA
Which is equivalent to: 1 - IF BOTH group G1 and group G2 are active
2 - OR
3 – Group G3 is ACTIVE and both group G4 and group G5 are active.
N.B.: the equation must be written without inserting spaces between the characters to be entered.
Sensor remote led in CBE
This is required to use a single LED repeater connected to a single sensor, but indicate a multiple sensors alarm
for a common area (Hospitals, Military dormitory, etc)
To manage the LED output on the sensor the direct CBE (sensors, input modules and groups), will change so
they can be used for the activation of this output on sensor.
Example:
If inside C1L1S1 programming the CBE is = (C1L1S2 C1L1S3)
Then
When C1L1S1 is in Alarm, the LEDs outputs on C1L1S2 and C1L1S3 will be ALSO activated.
Additionally, as usual , also :
-
Direct Groups can take place inside a Direct formula of «input» Points (sensors and input modules)
-
Reverse Groups can take place inside operands on reverse formulas for points (LED output on sensors
and Output modules).
CBE “Null”
:
equation
You can also not program any equation for a device.
In this case:
- If the device in question is an input sensor or module, the control unit will activate only all general visual and
sound indications (Alarm LED on the front panel, General Alarm RELAY, BUZZER and possible output modules
programmed through TYPE ID software for general signallings).
- If the device in question is an output module, this output will never be activated unless it is programmed
through TYPE ID software for general signallings.
N. B.: for output modules, the control unit does not allow to program an equation if the module has a
TYPE ID for general signalling.
Refer to Appendix:
Modules Software Type_ID
at the end of this manual.