ID3000/ID2000 Fire Panel Configuration Tool Manual
Control Matrix
4 - 9
997-291, Version 3.05
November 2010
4.1.4.2 Minimum Configuration
A minimum configuration requires:
a. At least one Control Matrix alarm entry. If
an AUTO/MANUAL ONLY switch is
installed, at least two alarm entries will be
required (one for the auto + manual case
and one for the manual only case). If an
IMMEDIATE release switch is provided, an
alarm entry is required for this case also.
b. A Non-fire Control Matrix entry to define each
Extinguishing System-unique switch on the
system (e.g. Abort, Hold etc.).
c. An Extinguishing Control Matrix entry for
each module that is activated/deactivated
in response to the alarm and non-fire entries
(e.g. sounders, strobes, direction valve,
release module etc.).
More complex systems may require numerous
rules, including alarm rules that do not have an
extinguishing system as an output (e.g. a rule
to activate sounders when sensors detect an
alarm but the extinguishing system is set to
OFF).
Use co-incidence rules to prevent non-fire
devices activating the release when there is no
alarm.