ID3000/ID2000 Fire Panel Configuration Tool Manual
Network
6 - 4
997-291, Version 3.05
November 2010
6.2.2 Procedure
To configure the panel for Master/Slave network
operation, do the following for the Master (the
Tool creates the data for Slaves automatically):
1
At the Specification Tab (
configure the number of Slaves and repeaters
on the network.
2
Select ‘Network Setup’ on the System
Parameters menu. The Master-Slave
Network Setup window is displayed with a
tabular view of the Master and Slaves. To
view the repeaters, click on the ‘+’ to the
left of the panel graphic (or click on ‘-’ to
hide the repeaters). All repeaters are initially
shown below the Master (see step 5).
Slaves for which a panel has already been
configured are shown by their panel name,
others are just shown as ‘Slave’.
3
The network configuration can be modified
in the Network Setup window (subject to the
limits given in
cursor to highlight one of the panels, then:
i
Insert Slave. A Slave panel is added at the
end of the table.
ii
Insert Repeater. A Repeater is added at the
end of the list of Repeaters for the panel.
iii Delete the highlighted panel or repeater (the
‘Delete’ key on your PC also does this).
iv OK to save changes [or Cancel (v) to discard
them].
2
1
Note:
The special case of a Stand Alone panel
(with or without repeaters) is configured
solely at the Specification Tab.
Slaves for which a panel name is displayed:
THESE NAMES ARE OVERWRITTEN if a
received Slave configuration has different (or
no) names. To retrieve the correct names, re-open
and save each of the Slave configurations.
3(i)
3(iii)
3(iv)
3(v)
3(ii)